3 Function

System information

This device is a product of the KNX system and complies with the KNX directives. Detailed
technical knowledge obtained in KNX training courses is a prerequisite to proper understanding. 
The function of this device depends upon the software. Detailed information on loadable
software and attainable functionality as well as the software itself can be obtained from the
manufacturer´s product database. Planning, installation and commissioning of the device are
carried out with the aid of KNX-certified software. The latest versions of product database and
the technical descriptions are available on our website.

Intended use

-

Switching of electrical loads with potential-free contacts

-

Switching of electrically-driven Venetian blinds, roller shutters, awnings and similar
hangings

-

Switching of electrothermal actuators

-

Polling of conventional switching or push-button contacts, window contacts etc. in KNX
systems, for reporting of states, meter levels, operation of loads, etc.

-

Polling of external temperature sensors for heating control

-

Logic functions to control building functions

-

Mounting on DIN rail according to EN 60715 in distribution boxes

Product characteristics

-

Actuator functions Switching, Venetian blind, electrothermal drives

-

Actuator function switchable in pairs

-

Integrated push-button interface with 6 inputs 

-

2 inputs for temperature sensors

-

Outputs can be operated manually

-

Feedback in manual mode and in bus mode

-

Scene function

-

Disabling of individual outputs manually or by bus

Switching function

-

Max. 6 switching outputs

-

Operation as NO or NC contacts

-

Logic and restraint function

-

Feedback function

-

Central switching function with collective feedback

-

Time functions: switch-on delay, switch-off delay, staircase lighting timer with run-on time

Blind function

-

Max. 3 Venetian blind outputs

-

Suitable for 230 V AC motors

-

Blind/shutter position directly controllable

-

Slat position directly controllable

-

Feedback of movement status, blind/shutter position and slat position

-

Forced position through higher-level controller

-

Safety function: 3 independent wind alarms, rain alarm, frost alarm

-

Sun protection function

Actuator function

-

Max. 2 outputs for electrothermal drives

-

Switching operation or PWM operation

-

Actuators with characteristics opened or closed without power controllable

-

Emergency operation in case of bus voltage failure for summer and winter

-

Protection against seized valves 

-

Forced position 

-

Cyclical monitoring of the input signals can be parameterized 

i

PWM operation: electrothermal actuators only have the positions Open and Closed. In
PWM operation, switch-on and switch-off during the drive's cycle time achieves an almost
constant behaviour. Cycle times < 15 minutes shorten the lifespan of the relay outputs

2/7

82596803
j0082596803

26.01.2017

Multi station

Summary of Contents for JUNG 23066REGHE

Page 1: ...o use a cut off relay if necessary The motors may be destroyed Use only venetian blind motors with mechanical or electronic limit switches Check the limit switches for correct adjustment Observe the specifications of the motor manufacturers Device can be damaged Danger of electric shock on the SELV PELV installation Do not connect loads for mains voltage and SELV PELV together on a single switch a...

Page 2: ...grated push button interface with 6 inputs 2 inputs for temperature sensors Outputs can be operated manually Feedback in manual mode and in bus mode Scene function Disabling of individual outputs manually or by bus Switching function Max 6 switching outputs Operation as NO or NC contacts Logic and restraint function Feedback function Central switching function with collective feedback Time functio...

Page 3: ...LED A1 flashes o Deactivate Press the c button for approx 5 s Short time manual operation o Activate Press the c button briefly Automatic return to bus operation 5 s after last operation Operating an output in manual mode o Keep pressing the c button until the LED 5 of the selected output flashes o Press the ON n or OFF o button Short Switch on switch off adjust slats or stop Long Move hanging upw...

Page 4: ...orm a Venetian blind output In each case the left hand relay output A1 A3 A5 is intended for the up direction n and the right hand load output A2 A4 A6 for the down direction o o Connect electrothermal drives to relay outputs A1 A2 i Delivery state The outputs can be operated using a keypad Outputs are set as venetion blind outputs Switching inputs DANGER When the mains voltage is connected to the...

Page 5: ... downwards operation time of the hanging o Measure slat adjusting time between Open and Closed o Enter the measured values in the parameter setting Downwards travel in minutes seconds and operation time extension in percent Load the address and the application software o Switch on the bus voltage o Press the programming button The programming LED lights up o Assign physical address The programming...

Page 6: ...amps uncompensated 1000 W parallel compensated 1160 W 140 µF Electrothermal actuators Cycle time min 15 min Load connections Connection mode Screw terminal single stranded 0 5 4 mm Finely stranded without conductor sleeve 0 5 4 mm Finely stranded with conductor sleeve 0 5 2 5 mm Inputs Rated voltage DC 3 3 V SELV Signal duration min 100 ms NO contacts max 50 NC contacts max 50 Cable length max 30 ...

Page 7: ...ALBRECHT JUNG GMBH CO KG Volmestraße 1 58579 Schalksmühle GERMANY Telefon 49 2355 806 0 Telefax 49 2355 806 204 kundencenter jung de www jung de 7 7 82596803 j0082596803 26 01 2017 Multi station ...