4 Operation
Operating elements
Figure 2
(5) Status LEDs for outputs
(7) Button
c
– Manual operation
(8) LED
c
– On: Continuous manual mode active
(9) Button
ON/
n
- Switching on or move hanging up / stop
(10) LED
ON/
n
– ON: Switched on or hanging moves up, manual mode
(11) Button
OFF/
o
- Switch off or move hanging downwards,manual mode
(12) LED
OFF/
o
– ON: Switched off or hanging moves down, manual mode
(13) Button
ALL OFF
– All outputs off and stop drives.
In operation with the button field the device distinguishes between a short and a long press.
-
Short: pressing for less than 1 second
-
Long: Pressing for between 1 and 5 seconds
Status indication
The status LED
A1...
(5) indicate the states of the outputs (figure 1).
-
Off: Output switched off
-
On: Output switched on
-
Flashes slowly: Output in manual mode
-
Flashes quickly: Output disabled via continuous manual mode
Operating modes
-
Bus operation: Operation via push-button sensors or other bus devices
-
Short-term manual operation: Manual operation locally with button field, automatic return to
bus operation.
-
Continuous manual mode: Exclusively manual operation on the device
i
No bus operation is possible in manual mode.
i
No manual mode is possible in case of bus failure.
i
After a bus failure and restoration the device switches to bus operation.
i
After a power failure and restoration the device switches to bus operation.
i
The manual mode can be disabled in ongoing operation via a bus telegram.
3/11
82560023
J:0082560023
05.08.2013
Switch actuator / blinds actuator