TESTING FOR EMERGENCY LUMINAIRES

Recommended routine test procedure in accordance with BS5266 
• Daily check – check LED charge indicator is illuminated
• Monthly functional test - simulate a mains supply failure for approx. 30 seconds by operation of key switch 

or switching off circuit breaker. Ensure normal supply is restored after test and ensure charge indicator is 
illuminated

• Annual three hour duration test - simulate a mains supply failure for three hour continuous test by operation 

of key switch or switching off circuit breaker. Ensure normal supply is restored after test and ensure charge 
indicator is illuminated

• If the luminaire fails any of the above tests, please contact a qualified electrician. See below for test record 