background image

• Using the top cover as a template, mark the location for, and drill the fixing holes ensuring not to infringe with 

any gas/water pipes or electrical cables 

• Feed the mains cable through the cable entry hole in the top cover, and fix to the surface using appropriate 

fixings 

• Connect the luminaire to the mains supply ensuring the correct polarity is observed: L - Live (brown),  

N - Neutral (blue)

• For non-maintained operation, remove the 2-pin connector from the circuit board (see Fig. 2). For 

maintained operation, leave it in place. This fitting cannot be wired for switched maintained operation

INSTALLATION & MAINTENANCE MANUAL 

These instructions should be read carefully and retained after installation by the end user for future reference 

and maintenance. 

These instructions should be used to aid installation of the following product: 

EMEXIT 
SAFETY 

 

This product must be installed in accordance with the latest edition of the IEE Wiring Regulations 

(BS7671) and current Building Regulations. If in any doubt, consult a qualified electrician 

 

Please isolate mains prior to installation or maintenance 

 

Check the total load on the circuit (including when this luminaire is fitted) does not exceed the rating of 

the circuit cable, fuse or circuit breaker 

 

Please note the IP (Ingress Protection) rating of this product when deciding the location for installation 

 

This product should be installed in the upright position 

 

This product is for indoor use only 

 

This product is Class II double insulated  

 

This product is IP20 rated 

 

INSTALLATION 

 

Provide power to the required point of installation  

 

Remove the top cover (see Fig. 1) 

 

 

Fig. 1 

 

Using the top cover as a template, mark the location for, and drill the fixing holes ensuring not to 

infringe with any gas/water pipes or electrical cables  

 

Feed the mains cable through the cable entry hole in the top cover, and fix to the surface using 

appropriate fixings  

 

Connect the luminaire to the mains supply ensuring the correct polarity is observed: L - Live (brown), N 

- Neutral (blue) 

 

For non-maintained operation, remove the 2-pin connector from the circuit board (see Fig. 2). For 

maintained operation, leave it in place. This fitting cannot be wired for switched maintained operation 

Fig. 1

 

 

Fig. 2 

 

Connect the battery via the plug and socket to the PCB (see Fig. 2) 

 

Refit the luminaire to the top cover ensuring all four lugs lock into place 

 

Switch on and check for correct operation, ensuring the green indicator LED is illuminated 

 

We recommend, on commissioning the installation, a minimum charge period of 24 hours before 

carrying out an emergency duration test 

 

If the batteries have been left in a discharged state for an extended period, we recommend that one or 

more charge and discharge cycles are completed which should help to restore the battery capacity 

 

The test button can be used to simulate a power failure, to test the lamp and battery operation. This 

can be used to carry out monthly functional testing, as long as the battery holds at least a small charge 

WARNING 

This product must be disconnected from the circuit if subjected to any high voltage or insulation resistance 

testing. Irreparable damage will occur if this instruction is not followed. 

GENERAL 

The light source of this luminaire is not replaceable; when the light source reaches its end of life the whole 

luminaire should be replaced.  

Clean with a soft dry cloth only, do not use aggressive cleaning products or solvents which may damage the 

product. 

Installing in areas where the temperature consistently drops below 0°C may shorten the battery life. 

This product is non-dimmable. 

This product should be recycled in the correct manner when it reaches the end of its life. Check local authorities 

for where facilities exist.  

The batteries in this luminaire are Nickel Cadmium and must be disposed of correctly. Please contact the local 

authorities for the disposal of this toxic waste. 

WARRANTY

 

This product has a warranty of 3 years (excluding battery) from date of purchase. Failure to install this product 

in accordance with the current edition of the IEE Wiring Regulations (BS7671), improper use, or removal of the 

batch code will invalidate the warranty. If this product should fail within its warranty period, it should be returned 

to the place of purchase for a free of charge replacement. ML Accessories does not accept responsibility for 

any installation costs associated with the replacement product. Your statutory rights are not affected. ML 

Accessories reserve the right to alter product specification without prior notice. 

TESTING FOR EMERGENCY LUMINAIRES 

 

Recommended routine test procedure in accordance with BS5266  

  Daily check – check LED charge indicator is illuminated 

  Monthly functional test - simulate a mains supply failure for approx. 30 seconds by operation of key switch 

or switching off circuit breaker. Ensure normal supply is restored after test and ensure charge indicator is 

illuminated 

Fig. 2