WARNING

GENERAL

WARRANTY

This product must be disconnected from the circuit if subjected to any high voltage or 
insulation resistance testing. Irreparable damage will occur if this instruction is not 
followed. 
Recommended routine test procedure in accordance with BS5266.
Daily check – check that the status GREEN LED indicator is illuminated.
Monthly functional test – simulate a mains supply failure for approx. 30 secs by operation 
of key switch or switching off a circuit breaker.  Ensure normal supply is restored after test 
and the indicator status LED is illuminated.
Twice yearly conduct a one hour duration test - simulate a mains supply failure for one 
hour continuous test by operation of key switch or switching off circuit breaker.  Ensure 
normal supply is restored after test and the indicator status LED is illuminated.
Annual full three hour duration test - conduct a three hour continuous duration test.  
Simulate a mains supply failure for three hour continuous test by operation of key switch or 
switching off circuit breaker. Ensure normal supply is restored after test and the indicator 
status LED is illuminated.
If the luminaire fails any of the above tests, please contact a qualified electrician.  See 
overleaf for test record sheet.

The unit should be recycled in the correct manner when it reaches the end of its life. Check 
local authorities for where facilities exist.
Clean with a soft dry cloth only, do not use aggressive cleaning products or solvents which 
may damage the fitting.

This product has a warranty of 3 years (excluding battery) from date of purchase. Failure 
to install this product in accordance with the current edition of the IEE Wiring Regulations, 
improper use, or removal of the batch codes will invalidate the warranty. If this product 
should fail within its warranty period it should be returned to the place of purchase for 
a free of charge replacement. ML Accessories does not accept responsibility for any 
installation costs associated with the replacement product. Your statutory rights are not 
affected. ML Accessories reserve the right to alter product specification without prior 
notice.

7

Summary of Contents for BT14EMA

Page 1: ...02 IP 44 230V 50Hz INSTALLATION MAINTENANCE MANUAL BT14EMA BT20EMA 1 IP BT14EMA BT20EMA...

Page 2: ...heck the total load on the circuit including when this luminaire is fitted does not exceed the rating of the circuit cable fuse or circuit breaker Please note the IP Ingress of Protection rating of th...

Page 3: ...e fixing holes and drill the holes ensuring not to infringe with any joists gas or water pipes or electrical cables Feed the cable via the entry point on the base of the luminaire Connect the Live bro...

Page 4: ...2 5m The switch on position is 1 on the table the switch off position is 0 on the table below Time setting can range from 10sec to 12min It is recommended to select the shortest time when adjusting t...

Page 5: ...ghting conditions This setting is to adjust brightness level of the luminaire when dimmed This setting is to adjust the length of time you want the luminaire to remain on dimmed mode before completely...

Page 6: ...the luminaire will automatically switch to 100 power until the user selected Time setting has elapsed 10s 1 Min 6 Min 12 Min When no motion is detected the luminaire will automatically dim down to th...

Page 7: ...uous test by operation of key switch or switching off circuit breaker Ensure normal supply is restored after test and the indicator status LED is illuminated If the luminaire fails any of the above te...

Page 8: ...ECOND YEAR THIRD YEAR FOURTH YEAR FIFTH YEAR MONTH TEST SIGNED DATE SIGNED DATE SIGNED DATE SIGNED DATE SIGNED DATE 1 FUNCTIONAL 2 FUNCTIONAL 3 FUNCTIONAL 4 FUNCTIONAL 5 FUNCTIONAL 6 1 HOUR 7 FUNCTION...

Reviews: