background image

               

User’s Information Manual

2  

Maintenance schedule 

(continued)

7

Clean/Inspect Trap Assembly

1.  Remove the clean out cap on the bottom of the trap.  Let 

the condensate and any debris drain out.

2.  Refill the trap according to the instructions on page 6.

 WARNING

Figure 2-1 Condensate Trap

Condensate disposal

1.  This boiler is a high efficiency appliance that produces 

condensate.

2.  The bottom of the boiler has a 1 1/4 inch pipe for 

connection of the condensate trap (FIG. 2-2).

3.  Slope condensate tubing down and away from the 

boiler into a drain or condensate neutralizing filter.  
Condensate from the Knight wall mount boiler will be 
slightly acidic (typically with a pH from 3 to 5).  Install 
a neutralizing filter if required by local codes.

 

A Neutralizer Kit is available from the factory (Kit 
3087).

4.  Do not expose condensate line to freezing temperatures.

5.  Use only plastic tubing or piping as a condensate drain 

line (FIG. 2-2).

Use materials approved by the authority 
having jurisdiction.  In the absence of 
other authority, PVC and CPVC pipe 
must comply with ASTM D1785 or D2845.  
Cement and primer must comply with 
ASME D2564 or F493.  For Canada use 
CSA or ULC certified PVC or CPVC pipe, 
fittings, and cement.

6.  A condensate removal pump is required if the boiler is 

below the drain.  When installing a condensate pump, 
select one approved for use with condensing boilers 
and furnaces.  The pump should have an overflow 
switch to prevent property damage from condensate 
spillage.  Call your qualified service technician to inspect 
the boiler and system. 

 NOTICE

 NOTICE

To allow for proper drainage on large 
horizontal runs, a second line vent may 
be required and tubing size may need to 
increase to 1 inch.

The condensate line must remain 
unobstructed, allowing free flow of 
condensate.  If condensate is allowed to 
freeze in the line or if the line is obstructed 
in any other manner, condensate can exit 
from the boiler tee, resulting in potential 
water damage to property.  Call your 
qualified service technician to inspect 
the boiler and system. 

Figure 2-2 Condensate Disposal

The condensate trap (FIG. 2-1) must have 
the float ball in place during all times of 
boiler operation to avoid flue gas emission 
from the condensate drain line.  Failure to 
ensure the float ball is in place could result in 
severe personal injury or death.

CONDENSATE

DRAIN

REMOVABLE CAP TO

CLEAN OUT TRAP

COMPRESSION

FITTING

FLOAT BALL

IMG00209

CONDENSATE

TRAP

REMOVABLE CAP

FOR CLEANING 

TRAP

CONDENSATE DRAIN CONNECTION -

ROUTE TO FLOOR DRAIN OR

NEUTRALIZING FILTER USING

3/4" PVC TUBING

IMG00159

Summary of Contents for WH 399

Page 1: ...are likely to be present WHAT TO DO IF YOU SMELL GAS Do not try to light any appliance Do not touch any electric switch do not use any phone in your building Immediately call your gas supplier from a near by phone Follow the gas supplier s instructions If you cannot reach your gas supplier call the fire department Installation and service must be performed by a qualified installer service agency o...

Page 2: ...y result in property damage NOTICE indicates special instructions on installation operation or maintenance that are important but not related to personal injury or property damage Contents HAZARD DEFINITIONS 2 PLEASE READ BEFORE PROCEEDING 3 1 PREVENT COMBUSTION AIR CONTAMINATION 4 2 MAINTENANCE SCHEDULE 5 Maintenance Procedures 6 Boiler Must Be Serviced and Maintained 6 Check Boiler Area 6 Check ...

Page 3: ...ctrical supply to the circulator Instead shut off the gas supply at a location external to the appliance Do not use this boiler if any part has been under water The possible damage to a flooded appliance can be extensive and present numerous safety hazards Any appliance that has been under water must be replaced Boiler water Thoroughly flush the system without boiler connected to remove sediment T...

Page 4: ...shments Swimming pools Metal fabrication plants Beauty shops Refrigeration repair shops Photo processing plants Auto body shops Plastic manufacturing plants Furniture refinishing areas and establishments New building construction Remodeling areas Garages with workshops Table 1A Corrosive Contaminants and Sources WARNING If the boiler combustion air inlet is located in any area likely to cause cont...

Page 5: ...n 54 F above return water temperature If combustion or performance indicate need Clean heat exchanger Remove and clean burner using compressed air only Clean the blower wheel Owner maintenance see pages 6 8 for detailed instructions Daily Check boiler area Check pressure temperature gauge Monthly Check vent piping Check air piping Check air and vent termination screens Check relief valve Check con...

Page 6: ...iler intake air will cause acidic condensate in the boiler This will cause significant damage to the boiler if allowed to continue Read the list of potential materials listed in Table 1A on page 4 of this manual If any of these products are in the room from which the boiler takes its combustion air they must be removed immediately or the boiler combustion air and vent termination must be relocated...

Page 7: ...ipe fittings and cement 6 A condensate removal pump is required if the boiler is below the drain When installing a condensate pump select one approved for use with condensing boilers and furnaces The pump should have an overflow switch to prevent property damage from condensate spillage Call your qualified service technician to inspect the boiler and system NOTICE NOTICE To allow for proper draina...

Page 8: ...the system is equipped with a low water cutoff test the low water cutoff periodically during the heating season following the low water cutoff manufacturer s instructions Reset button low water cutoff 1 Testing the low water cutoff shuts the unit off Press the RESET button on the low water cutoff to turn the unit back on Check boiler piping gas and water 1 Remove the boiler front access door and p...

Page 9: ...User s Information Manual 9 3 Operating instructions o Figure 3 1 Operating Instructions Models 55 285 ...

Page 10: ...User s Information Manual 10 3 Operating instructions Figure 3 2 Operating Instructions Model 399 ...

Page 11: ... SELECT keys on either corner and the NAVIGATION dial in the center MENU Left SELECT Key SETPOINTS NAVIGATION Dial Pressing Down SHDN Right SELECT Key Adjusting parameters Time and date The control uses an internal clock for the night setback feature and for logging of events For these features to work properly the clock must be set when the boiler is first installed or any time the boiler has bee...

Page 12: ...emperatures are available The reset curve parameters can be changed by the installer by accessing the Outdoor Reset menu There are three 3 individual user set points for better zone control These are listed as SH1 Set Point through SH3 Set Point These set points provide a maximum boiler water temperature limit to the outdoor reset curve If an outdoor sensor is not installed the boiler will operate...

Page 13: ...tional postpurge period to clear the combustion chamber and vent system of residual flue products SHUTDOWN The unit has been placed in the OFF position SETPOINT MET The controlled temperature has exceeded its set point and its offset BLOCKED The unit has detected a condition that has temporarily interrupted the current call for heat B Call for Heat Indicators Room Thermostat 1 has a call for heat ...

Page 14: ...asured by the flame sense circuit FAN SPEED The speed of the combustion blower BOILER PUMP The status of the boiler pump output SYSTEM PUMP The status of the system pump output DHW PUMP The status of the DHW pump output BMS VOLTAGE The voltage received from a BMS system BLR PUMP OUTPUT The speed signal sent to a variable speed boiler pump in percent SYS PUMP INPUT The speed signal received from a ...

Page 15: ...t Setback Skip Screen E NAVIGATION Dial Function Turning the NAVIGATION dial will select the next or previous Status Screen Pressing the NAVIGATION dial will show the next fault NSB Night Setback trigger or ramp delay setting Pressing the NAVIGATION dial will select the setting indicated by the cursor Pressing the NAVIGATION dial will display the Set Points Screen Turning the NAVIGATION dial will ...

Page 16: ... in the Night Setback Override section on page 12 Revision C ECO C09197 updates made to the SMART SYSTEM control ECR R04523 Revision D ECO C09843 reflects the addition of the manual air vent in the outlet tubing and the new condensate trap pipe R04984 Revision E ECO C10143 reflects updates made to the ignition timing information Revision F ECO C11102 reflects outdoor air reset updates WH USER Rev ...

Reviews: