Installation & Operation Manual
37
6
Hydronic piping
(continued)
PRESSURE
REDUCING VALVE
BACKFLOW
PREVENTER
PRESSURE
GAUGE
SYSTEM SUPPLY
SENSOR
AIR
SEPARATOR
FROM
SYSTEM
NOT TO EXCEED 4 PIPE DIA. OR A MAX. OF 12” APART
DRAIN POINT
(TYPICAL)
BOILER
CIRCULATOR
ANTI-SCALD
MIXING VALVE
DOMESTIC
HOT WATER
CIRCULATOR
COLD WATER
IN
PRESSURE
RELIEF VALVE
UNION
(TYPICAL)
TEMPERATURE /
PRESSURE
GAUGE
BOILER
CIRCULATOR
BOILER
CIRCULATOR
BOILER
CIRCULATOR
DRAIN
BOILER 2
(MEMBER 1)
BOILER 1
(LEADER)
INDIRECT
DHW TANK
BOILER 3
(MEMBER 2)
BOILER 4
(MEMBER 3)
SYSTEM
CIRCULATOR
BALL VALVE
(TYPICAL)
EXPANSION
TANK
TO
SYSTEM
MAKE UP WATER
Figure 6-9
Multiple Boilers - Non-Zoned Primary/Secondary Piping
Model
Number of Units
2
3
4
5
6
7
8
Required Pipe Sizes
80
1-1/4" 1-1/2"
2"
2-1/2" 2-1/2" 2-1/2" 2-1/2"
105
1-1/2"
2"
2"
2-1/2" 2-1/2" 2-1/2"
3"
150
2"
2"
2-1/2" 2-1/2" 2-1/2"
3"
3-1/2"
210
2"
2-1/2"
3"
3"
3-1/2"
4"
4"
285
2-1/2" 2-1/2"
3"
3-1/2" 3-1/2"
4"
5"