Specifications
Input Data for Resistor (R)
Connection
2-, 3- or 4-wire
(automatic identifi cation)
Resistance range
(incl. line resistance)
Resistance measurement: 0 ... 5 kΩ
or 5 ... 100 kΩ
Max. line resistance
100 Ω
Supply current
Max. 500 μA
Line monitoring
Open circuits
Accuracy
For resistances < 5 kΩ:
± (50 mΩ + 0.05% meas.val.)
for spans > 15 Ω
For resistances > 5 kΩ:
± (1 Ω + 0.2% meas.val.)
for spans > 50 Ω
Temperature coeffi
cient at
the input
50 ppm/K of adjusted end value
(average TC in permitted operating
temp range, reference temp 23 °C)
Input Data for Potentiometer (ratio)
Input
200 Ω ... 50 kΩ
Connection
3- or 4-wire
Supply current
0 ... 5 mA
Line monitoring
Open circuits
Accuracy
< (0.2% full scale +0.05% meas.val.)
for spans > 5%
Temperature coeffi
cient at the
input
50 ppm/K of adjusted end value
(average TC in permitted operating
temp range, reference temp 23 °C)
Summary of Contents for SensoTrans R A 20230P0 Series
Page 14: ...14 DIP Schalter ON Konfigurierung über Schalter Funktionsübersicht ...
Page 26: ......
Page 27: ......
Page 29: ...The Art of Measuring www knick de English 29 SensoTrans R A 20230P0 Resistance Transmitters ...
Page 42: ...42 DIP switch ON Configuration using Switches Overview of Functions ...
Page 54: ......
Page 55: ......
Page 70: ...70 switch DIP ON Configuration via les switches Aperçu des fonctions ...
Page 82: ......
Page 83: ......
Page 85: ...The Art of Measuring ...
Page 98: ...98 Chaves DIP ligadas ON Configuração Usando Chaves Sinopse de Funções ...
Page 110: ...110 ...
Page 111: ...111 ...