Instructions and warnings – Mineral Insulated
Cables and Terminations, Rev. 02 del 11/12
operating temperatures of above 250°C must be take
account what described about the GF sealant
-
The MICO
cables can operate at temperatures above
200°C, without be susceptible to adverse effects;
other hand, cracks can occur on the additional coating in
LSF at temperatures below -20°C without
functionality of the cable. This is why you should not run the
installation of coated cable with extra cover in LSF at
temperatures below -20°C.
5
TERMINATION EXECUTION
Cut the end of the cable by a small saw; place the stripper on
the cable and tighten it: the blade must be in contact with the
copper outer sheath and the V shaped clamp must be
tightened on the cable by its screw, so to let the tool spin round
with the cable without stopping it.
R e g u l a t i o n
s c r e w
B l a d e
m o b i l
" V "
" V " f i x e d
Start rotating the tool pushing it towards the inner part of the
cable; avoid the rolling up of the copper shaving on the
conductors, fixing it on the suitable hook.
When you have stripped enough copper sheath, you can insert
the pliers to cause the drop of the copper shaving
Clean the conductors and insert the gland components (body,
double cone and press cone).
Only for use in explosion-proof applications, glands
shall be ATEX (or IECEx) marked. For applications in
potentially explosive areas (zone 1 and zone 21) use only RAD
ISO or RAD GAS fittings marked as follows:
II 2G Ex eb IIC Gb
Ex db IIC Gb
II 2D Ex tb IIIC Db
IP65
Tamb -20 °C
÷
+70°C
Service Temperature: -20 °C
÷
+250 °C.
In case that the fitting/housing coupling is subjected to
vibrations it is necessary, in order not to cause breakage of the
cable, to make a compensation bend in the vicinity of the
housing. In case of ATEX applications the fitting/housing
coupling shall guarantee at least 5 threads and the minimum
housing thickness must be greater than or equal to 10 mm,
moreover, the lock nut (see last figure) is not present in these
coupling.
The seal is guaranteed by the full tightening of the metal
double cone through the cone press and is ent
care of the installer.
Screw the self threaded brass pot on the cable sheath, placing
the inner part of the hole on the copper sheath
Cables and Terminations, Rev. 02 del 11/12
/2017
s of above 250°C must be take
the GF sealant.
can operate at temperatures above -
usceptible to adverse effects; on the
the additional coating in
20°C without affect the
This is why you should not run the
nstallation of coated cable with extra cover in LSF at
l saw; place the stripper on
the cable and tighten it: the blade must be in contact with the
copper outer sheath and the V shaped clamp must be
tightened on the cable by its screw, so to let the tool spin round
Start rotating the tool pushing it towards the inner part of the
cable; avoid the rolling up of the copper shaving on the
When you have stripped enough copper sheath, you can insert
to cause the drop of the copper shaving.
Clean the conductors and insert the gland components (body,
glands and seals
For applications in
potentially explosive areas (zone 1 and zone 21) use only RAD
housing coupling is subjected to
vibrations it is necessary, in order not to cause breakage of the
cable, to make a compensation bend in the vicinity of the
In case of ATEX applications the fitting/housing
ds and the minimum
housing thickness must be greater than or equal to 10 mm,
moreover, the lock nut (see last figure) is not present in these
The seal is guaranteed by the full tightening of the metal
and is entrusted to the
Screw the self threaded brass pot on the cable sheath, placing
the inner part of the hole on the copper sheath.
Remove from the brass pot the Magnesium Oxide shattered
during previous operation.
Check with a Megger, at 500 Vcc, that cable insulation
resistance is higher than 100 M
the brass pot.
After pulling the conductors by a pliers, place the stub cap as
close as possible to the brass pot, then start crimping us
suitable tool.
Cut some lengths of sleeving and, after removing eventual
exceeding sealant, place them on the stub cap
Junction box wall
Gland
Seal
Conductor
s
Sleevings
Brass locknut
To make a termination, you need the following components (in
addition to the cable, of course): seal
LSF shroud (if cable is LSF required)
stripper, spare blades, crimping tool
Check MICO
®
cables general brochure for tools dimension or
technical manual for MICO
®
cables
6
UNINSTALLING AND DISPOSAL
Before proceeding to final dismantling it is necessary to
separate the various parts that could cause pollution, make a
selection of materials in order to facilitate recycling, to earmark
separate disposal.
NO
Remove from the brass pot the Magnesium Oxide shattered
Check with a Megger, at 500 Vcc, that cable insulation
resistance is higher than 100 M
Ω
; then pour the sealant inside
After pulling the conductors by a pliers, place the stub cap as
close as possible to the brass pot, then start crimping using the
Cut some lengths of sleeving and, after removing eventual
exceeding sealant, place them on the stub cap.
Junction box wall
Mi neral insulated cabl e
Copper sheath
Gland
To make a termination, you need the following components (in
the cable, of course): seal, gland, sealant, eventual
LSF shroud (if cable is LSF required), and the following tools:
crimping tool.
cables general brochure for tools dimension or
cables installation.
UNINSTALLING AND DISPOSAL
Before proceeding to final dismantling it is necessary to
separate the various parts that could cause pollution, make a
selection of materials in order to facilitate recycling, to earmark
SI
SI
YES
YES