background image

Instructions and warnings – Mineral Insulated 

Cables and Terminations, Rev. 02 del 11/12

operating  temperatures  of  above  250°C  must be take
account what described about the GF sealant

-

The  MICO

  cables  can  operate  at  temperatures above

200°C,  without  be  susceptible  to  adverse  effects;
other  hand,  cracks  can  occur  on  the  additional coating in
LSF  at  temperatures  below  -20°C  without
functionality of the cable. This is why you should not run the
installation  of  coated  cable  with  extra  cover in LSF at
temperatures below -20°C. 

TERMINATION EXECUTION 

Cut the end of the cable by a small saw; place the stripper on
the cable and tighten it: the blade must be in contact with the
copper  outer  sheath  and  the  V  shaped  clamp must be
tightened on the cable by its screw, so to let the tool spin round
with the cable without stopping it. 

R e g u l a t i o n

s c r e w

B l a d e

m o b i l

" V "

" V "   f i x e d

Start  rotating  the  tool  pushing  it  towards  the  inner part of the
cable;  avoid  the  rolling  up  of  the  copper  shaving on the
conductors, fixing it on the suitable hook. 
When you have stripped enough copper sheath, you can insert
the pliers to cause the drop of the copper shaving

Clean the conductors and insert the gland components (body,
double cone and press cone). 
Only for use in explosion-proof  applications, glands
shall  be  ATEX  (or  IECEx)  marked.  For  applications in
potentially explosive areas (zone 1 and zone 21) use only RAD
ISO or RAD GAS fittings marked as follows: 

 II 2G Ex eb IIC Gb 

Ex db IIC Gb 

 II 2D Ex tb IIIC Db 

IP65 

Tamb -20 °C 

÷

 +70°C

Service Temperature: -20 °C 

÷

 +250 °C.

In  case  that  the  fitting/housing  coupling  is subjected to
vibrations it is necessary, in order not to cause breakage of the
cable,  to  make  a  compensation  bend  in  the vicinity of the
housing.  In  case  of  ATEX  applications  the fitting/housing
coupling  shall  guarantee  at  least  5  threads  and the minimum
housing  thickness  must  be  greater  than  or  equal to 10 mm,
moreover, the lock nut (see last figure) is not present in these
coupling. 
The  seal  is  guaranteed  by  the  full  tightening of the metal
double  cone  through  the  cone  press  and  is  ent
care of the installer. 

Screw the self threaded brass pot on the cable sheath, placing
the inner part of the hole on the copper sheath

Cables and Terminations, Rev. 02 del 11/12

/2017 

s of above 250°C  must  be  take 

the GF sealant. 

can operate at temperatures  above -

usceptible to adverse  effects;  on  the 

the additional  coating  in 

20°C without  affect  the 

This is why you should not run the 

nstallation of coated cable with extra cover  in  LSF  at 

l saw; place the stripper on 

the cable and tighten it: the blade must be in contact with the 
copper outer sheath and the V shaped clamp  must  be 
tightened on the cable by its screw, so to let the tool spin round 

Start rotating the tool pushing it towards the  inner  part  of  the 
cable; avoid the rolling up of the copper  shaving  on  the 

When you have stripped enough copper sheath, you can insert 

to cause the drop of the copper shaving. 

Clean the conductors and insert the gland components (body, 

glands and seals 

For  applications  in 

potentially explosive areas (zone 1 and zone 21) use only RAD 

housing coupling is  subjected  to 

vibrations it is necessary, in order not to cause breakage of the 
cable, to make a compensation bend in the  vicinity  of  the 

In case of ATEX applications the  fitting/housing 

ds and  the  minimum 

housing thickness must be greater than or equal  to  10  mm, 
moreover, the lock nut (see last figure) is not present in these 

The seal is guaranteed by the full tightening  of  the  metal 

and is  entrusted  to  the 

Screw the self threaded brass pot on the cable sheath, placing 
the inner part of the hole on the copper sheath. 

Remove  from  the  brass  pot  the Magnesium Oxide shattered
during previous operation. 

Check  with  a  Megger,  at  500 Vcc, that cable insulation
resistance is higher than 100 M
the brass pot. 

After pulling the conductors by a pliers, place the stub cap as
close as possible to the brass pot, then start crimping us
suitable tool. 

Cut  some  lengths  of  sleeving and, after removing eventual
exceeding sealant, place them on the stub cap

Junction box wall

Gland

Seal 

Conductor

Sleevings 

Brass locknut

 

To make a termination, you need the following components (in
addition to the cable, of course): seal
LSF shroud (if cable is LSF required)
stripper, spare blades, crimping tool

Check  MICO

®

  cables  general  brochure for tools dimension or

technical manual for MICO

®

 cables

UNINSTALLING AND DISPOSAL

Before  proceeding  to  final  dismantling it is necessary to
separate  the  various  parts  that could cause pollution, make a
selection of materials in order to facilitate recycling, to earmark
separate disposal. 

NO

Remove from the brass pot the  Magnesium  Oxide  shattered 

Check with a Megger, at 500  Vcc,  that  cable  insulation 
resistance is higher than 100 M

; then pour the sealant inside 

After pulling the conductors by a pliers, place the stub cap as 
close as possible to the brass pot, then start crimping using the 

Cut some lengths of sleeving  and,  after  removing  eventual 
exceeding sealant, place them on the stub cap. 

Junction box wall

 

Mi neral  insulated  cabl e 

Copper sheath 

Gland 

To make a termination, you need the following components (in 

the cable, of course): seal, gland, sealant, eventual 

LSF shroud (if cable is LSF required), and the following tools: 

crimping tool. 

cables general  brochure  for  tools  dimension  or 

cables installation. 

UNINSTALLING AND DISPOSAL 

Before proceeding to final dismantling  it  is  necessary  to 
separate the various parts that  could  cause  pollution,  make  a 
selection of materials in order to facilitate recycling, to earmark 

SI

SI

YES

YES 

Summary of Contents for MICO

Page 1: ...zioni Prestare attenzione al peso del materiale da trasportare e movimentare e sicuramente se superiore ai 20 kg non trasportare manualmente ma utilizzare idonei mezzi di sollevamento e trasporto Durante l installazione e l esecuzione delle terminazioni identificare sempre in modo visibile ed inequivocabile i cavi alle due estremità Al termine di installazione ed esecuzione delle terminazioni effe...

Page 2: ...ità del cavo ne risenta per questo motivo non si deve eseguire a del cavo con rivestimento supplementare in LSF in LLE TERMINAZIONI Tagliare l estremità del cavo da terminare con un seghetto posizionare l asportaguaina in presa con il cavo la lama deve appoggiare sul bordo della guaina di rame e il morsetto a V deve essere stretto sul cavo a mezzo dell apposita vite in attrezzo solidale con il cav...

Page 3: ... excessive crushing or bending At the end of installation and execution of terminations perform a strength test and an insulation resistance test before powering up the system Use only KME tools for installation and execution of terminations Use only KME terminations and accessories When you install at altitude constrain the cables through the use of KME staples using an adequate fixing distance D...

Page 4: ...ble by its screw so to let the tool spin round Start rotating the tool pushing it towards the inner part of the cable avoid the rolling up of the copper shaving on the When you have stripped enough copper sheath you can insert to cause the drop of the copper shaving Clean the conductors and insert the gland components body glands and seals For applications in potentially explosive areas zone 1 and...

Reviews: