KME MICO Manual Download Page 3

Instructions and warnings – Mineral Insulated Cables and Terminations, Rev. 02 del 11/12/2017 

KME ITALY SpA 

Via della Repubblica, 257  -  55051 Fornaci di Barga (Lucca)  -  Tel. 0583 701.413-412  -  Fax 0583 701406 

www.kme.com

  -  

[email protected]

 

MINERAL INSULATED CABLE MICO

®

 AND THEIR TERMINATIONS 

EN 60702 – 1: 2002-03 / EN 60702 – 2: 2002-03 / EN 60079 - 0: 2012 / EN 60079 - 1:2014 / EN 60079 - 7:2015 / EN 60079 - 31:2014

1

 

INTENDED USE 

Referring  to  the  EU  Declaration  of  Conformity,  drafted  in 
accordance with 2014/35/EU Directive – Low Voltage Directive 
(LDV), given with the product, and with reference to EY Type-
examination  certificate  issued  under  2014/34/EU  Directive  – 
ATEX Directive (only for RAD ISO e RAD GAS glands): 

-

Mineral  Insulated  Cable  (MICO

®

)  Heavy  Duty

  –  Energy

transport up to 750 V voltage.

-

Mineral  Insulated  Cable  (MICO

®

)  Light  Duty

  – –  Energy 

transport up to 500 V voltage.

-

Terminations  for  Mineral  Insulated  Cables  (MICO

®

)

Heavy Duty / Light Duty 

– Seals and / or glands to perform

termination of Mineral Insulated Cables (MICO

®

) Light Duty /

Heavy Duty with RAD ISO, RAD GAS, RN glands, according
to what marked on them.

RESIDUAL RISKS 

Here is a list of residual risks in the event of incorrect transport, 
installation,  use  or  maintenance  of  Mineral  Insulated  Cable 
(MICO

®

) and their Terminations. 

-

Electrocution

  due  to  incorrect  execution  of  the

termination,  putting  one  of  the  phases  on  the  earth
sheath.

-

Electrocution

  or  insulation  loss  due  to

incorrect  handling  or  installation  because  of
shock,  crushing,  perforations  or  excessive  bending  of  the
cable, that could damage the earth sheath.

-

Bump 

due  to  the  cable  fall  in  case  of  faulty

handling or installation.

-

Cutting / Shearing / Puncture / Burns

during  manual  operations  required  for
the installation and the termination's execution.

-

Generic hazard

 for transportation, installation, use or

maintenance  performed  by  unqualified  and  non
trained or incorrectly equipped personnel.

-

Contact with 

chemicals

.

ATTENTIONS TO FOLLOW 

The  following  are  the  attentions  to  follow  during  transport, 
installation,  operation  and  maintenance  of  Mineral  Insulated 
Cable (MICO

®

) and their Terminations. 

-

Always  wear  PPE  required  for
transportation,  installation  and
use  (gloves,  goggles,  helmets,
shoes).

-

Designate  for  these  operations  only  technical  personnel
trained  on  the  correct  procedures  for  the  transport,
installation, use and maintenance of Mineral Insulated Cable
(MICO

®

) and their Terminations.

-

During the execution of the termination connect immediately
the  earth  sheath  to  a  properly  marked  section  of  cable,
before performing the remaining steps.

-

Pay  attention  to  the  weight  to  transport  and  handle,  and
certainly if more than 20 kg, do not carry it manually but use
suitable lifting and transport equipment.

-

During  installation  and  execution  of  terminations  always
mark  in  a  visible  and  unequivocal  way  the  cables  at  both
ends.

-

At the end of installation and execution of terminations make
a  visual  check  on  the  earth  sheath,  to  check  for  any
discontinuities, perforations, excessive crushing or bending.

-

At  the  end  of  installation  and  execution  of  terminations
perform  a  strength  test  and  an  insulation  resistance  test
before powering up the system.

-

Use  only  KME  tools  for  installation  and  execution  of
terminations.

-

Use only KME terminations and accessories.

-

When you install at altitude, constrain the cables through the
use of KME staples, using an adequate fixing distance.

-

Durante  il  trasporto,  l’installazione  e  lo  stoccaggio  prestare
attenzione  in  ogni  momento  al  raggio  di  curvatura  del  cavo,
che deve essere appropriato al diametro del cavo affinché lo
stesso non venga danneggiato.

-

During  transport,  installation  and  storing  avoid  shocks,
crushing or perforations that may make the cable unusable.

-

The  mineral  insulated  cable  is  moisture  sensitive,  because
the  magnesium  oxide,  that  acts  as  insulation,  absorbs
moisture  if  left  exposed,  causing  the  decrease  of  the
insulation  resistance  value.  If  stored  for  a  long  time  or  if  it’s
necessary to hold the cable exposed to humid  environment,
it  is  good  practice  to  temporarily  seal  the  ends  by  wrapping
them with self agglomerating tape or by wrapping the ends of
the cable with common insulating tape.

-

In  case  of  storage,  even  temporarily,  use  covered  areas,
protected  from  weather  and  far  from  transit  zones;  also  the
plastic  cover  of  the  coated  cables  may  harden  and
deteriorate if kept to sunlight for a long time.

-

In  case  of  manipulation  of  chemical  agents,  follow  the
instructions of the related material safety data sheet (MSDS).

-

Before uninstall the cable, ensure that there is no voltage in
the system.

INSTALLATION 

For  the  correct  and  complete  installation  procedure  and 
execution  of  the  terminations  procedure  carefully  follow  what 
reported  extensively  in  the  full  document  “

Instructions  - 

Mineral  Insulated  Cable  (MICO

®

)  and  their  Terminations

” 

available  in  full  on  the  website 

www.kme.com

  or  by  e-mail  at 

[email protected]

.  This  document  shows  all  KME  accessories 

required 

and 

detailed 

procedures 

to 

fully 

execute 

transportation, installation and termination of Mineral Insulated 
Cable  (MICO

®

),  accompanied  by  technical  data,  tips  and 

detailed illustrations about. 

-

The  mineral  insulated  cable  is  normally  supplied  in  a  self-
supporting  coil  having  an  inner  diameter  of  500,  1200  and
1450 mm, depending on the outer diameter of the cable. To
properly  carry  out  the  coils  is  possible  to  build  a  simple
unwinder, using a metal profile or of wooden boards such as
used for the support of common cables.

-

Before fixing, the cable it must be straightened by hand or by
using a straightener or a tube bender; the final straightening
can  be  performed  using  a  block  of  wood  and  a  hammer,  or
with  a  rubber  hammer;  a  metal  hammer  should  never  be
used directly on the cable sheath to avoid compromising the
mechanical and electrical characteristics of the sheath.

-

When  the  temperature  of  the  sheath  of  a  cable  MICO

®

,

taking account of the ambient temperature and the increase
in  temperature  due  to  the  current,  does  not  exceed  70°C,
one  can  choose  between  the  bare  cable  and  the  cable
coated  in  LSF;  for  temperatures  of  the  sheath  more  than
105°C,  one  must  choose  the  bare  wire;  for  continuous

Summary of Contents for MICO

Page 1: ...zioni Prestare attenzione al peso del materiale da trasportare e movimentare e sicuramente se superiore ai 20 kg non trasportare manualmente ma utilizzare idonei mezzi di sollevamento e trasporto Durante l installazione e l esecuzione delle terminazioni identificare sempre in modo visibile ed inequivocabile i cavi alle due estremità Al termine di installazione ed esecuzione delle terminazioni effe...

Page 2: ...ità del cavo ne risenta per questo motivo non si deve eseguire a del cavo con rivestimento supplementare in LSF in LLE TERMINAZIONI Tagliare l estremità del cavo da terminare con un seghetto posizionare l asportaguaina in presa con il cavo la lama deve appoggiare sul bordo della guaina di rame e il morsetto a V deve essere stretto sul cavo a mezzo dell apposita vite in attrezzo solidale con il cav...

Page 3: ... excessive crushing or bending At the end of installation and execution of terminations perform a strength test and an insulation resistance test before powering up the system Use only KME tools for installation and execution of terminations Use only KME terminations and accessories When you install at altitude constrain the cables through the use of KME staples using an adequate fixing distance D...

Page 4: ...ble by its screw so to let the tool spin round Start rotating the tool pushing it towards the inner part of the cable avoid the rolling up of the copper shaving on the When you have stripped enough copper sheath you can insert to cause the drop of the copper shaving Clean the conductors and insert the gland components body glands and seals For applications in potentially explosive areas zone 1 and...

Reviews: