KMC Controls
Revision A
Commissioning functions
The commissioning sequence
14
The
commissioning
sequence
Set the commission functions in the following sequence.
1.
2.
Setting up network communications
3.
4.
Setting commissioning setpoints
5.
6.
Enter the
commissioning
mode
For access to the commissioning functions you will need a Level 2 password.
◆
If the controller has not been previously set up, no password is required.
◆
A new Level 2 password can be entered in the advanced commissioning
functions. See the topic
Enter the commissioning mode
Procedure
Steps
STE display
Starting display
Start from the temperature display.
Enter the
commissioning
password
1. Press the and buttons together
and hold them down until the
display changes to
PSW2
.
2. Press the or button to change
the first digit.
3. Press the button to select the next
digit. Repeat for all four digits.
4. When the button is pushed for the
fourth correct digit, the display
changes to
COMM
.
Note:
If a Level 2 password has not
previously been entered the display
will change to the
COMM
display after
Step 1.
Select a
commissioning
function
Access to the commissioning
functions always start at the
COMM
display.
72
12S1
Set
Point
Set
Point
PSW2
OOOO
COMM