STE-8001 and STE-8201 sensors
Revision A
Commissioning functions
Setting the airflow setpoints
23
Setting the
airflow setpoints
The airflow setpoints configure the airflow limits for the VAV terminal unit.
Setting the airflow setpoints requires entering a Level 2 password which is
described in the topic
.
Note
If the VAV unit is a heat only or cooling only unit, the airflow setpoints for the
unused mode must be set within the range of the mode in use. Failure to set the
unused setpoints correctly will result in unpredictable or erroneous air
balancing settings.
Procedure to set the airflow setpoints
Procedure
Steps
STE display
Starting display
1. Start at the temperature display.
2. Enter the Level 2 password. The
display changes to the
COMM
.
Select the flow
setpoint display.
1. From the
COMM
display, press the
or buttons to show the
CNFG
display.
2. Press the button to select the
CNFG
options. The display changes to
STPT
.
3. Press the or buttons to change
the display to
FLOW
.
4. Press the button to select
FLOW
.
72
12S1
PSW2
OOOO
Set
Point
Set
Point
COMM
CNFG
STPT
FLOW