Commissioning functions
Setting commissioning setpoints
20
Setting
commissioning
setpoints
The commissioning setpoints set the operational parameters and limits for the
VAV terminal unit. Setting configuration setpoints requires entering a Level 2
password which is described in the topic
Procedure to set the commissioning setpoints
Procedure
Steps
STE display
Starting display
Enter the Level 2 password. The display
changes to the
COMM
.
Select the setpoint
display.
1. From the
COMM
display, press the
or buttons to show the
CNFG
display.
2. Press the button to select the
CNFG
options. The display changes to
STPT
.
3. Press the button to select the
STPT
options.
Set the minimum
cooling setpoint
1. Press the or buttons to set the
minimum cooling setpoint. The
setpoint will change in 0.5°
increments.
2. Press the button to save the
setpoint and advance to the next
function.
Set the maximum
heating setpoint
1. Press the or buttons to set the
maximum heating setpoint. The
setpoint will change in 0.5°
increments.
2. Press the button to save the
setpoint and advance to the next
function.
PSW2
OOOO
Set
Point
Set
Point
COMM
CNFG
STPT
Set
Point
MIN
68O
Set
Point
MAX
78O