BAC-1xx36/1xxx36 Series (3 Relays and 6 Analog Outputs) Section
49
Application Guide L
BILL OF MATERIALS: AHU, Modulating Heat and Modulating Cool
REFERENCE
KMC PART #
PART DESCRIPTION
FLEXSTAT
BAC-1xx36/
1xxx36
BACNET THERMOSTAT, 6 RELAY & 3 ANALOG OUTPUTS
R1
REE-3211
MULTI-VOLTAGE CONTROL RELAY, 1.2 VA
CLV
VEB-43xxxBDL
FAIL-SAFE CONTROL VALVE, W/ MEP-5372 2-10 VDC
ACTUATOR, 19 VA
HTV
FOR VALVES, CHOOSE CAPACITY/MODEL FROM KMC DATA SHEET
HUM
REE-3112
12/24 VDC CONTROL RELAY, SPDT
DAT
STE-1402
DUCT TEMPERATURE SENSOR
FST
CSE-1102
AIR DIFFERENTIAL PRESSURE SWITCH, 0.05-12" WC
MAT
STE-1416
12' DUCT AVERAGING TEMP SENSOR
OAT
STE-1451
OUTSIDE TEMPERATURE SENSOR
*
STE-6011
REMOTE TEMPERATURE SENSOR, TYPE II
*
SAE-10xx
REMOTE CO
2
SENSOR, SPACE OR DUCT
TX1
XEE-6311-075
TRANSFORMER, 120/240/277/480:24 VAC, 75 VA
CHOOSE ONE OF THE FOLLOWING TRANSFORMERS:
TX2
XEE-6311-075
TRANSFORMER, 120/208/240/480:24 VAC, 75 VA
TX2
XEE-6311-100
TRANSFORMER, 120/240/277/480:24 VAC, 96 VA
*The remote temperature and CO
2
sensor options are not shown in the sample installation
diagrams, and they are available only on BAC-12xxxx/13xxxx/14xxxx models.
BILL OF MATERIALS: AHU, DAMPER ACTUATORS
REFERENCE
MAX DAMPER
AREA IN FT
2
KMC PART #
PART DESCRIPTION
OAD or RTD
6.25
MEP-5372
50 IN·LB FAIL-SAFE ACTUATOR, 2-10VDC,
19VA
OAD or RTD
15
MEP-7252
120 IN·LB FAIL-SAFE ACTUATOR, 0-10VDC,
25VA
OAD or RTD
22.5
MEP-7552
180 IN·LB FAIL-SAFE ACTUATOR, 0-10VDC,
25VA
OAD or RTD
40
MEP-7852
320 IN·LB FAIL-SAFE ACTUATOR, 0-10VDC,
40VA
FCU (Fan Coil Unit)—2 or 4 Pipe, Modulating
BILL OF MATERIALS: FCU, 2-Pipe, Modulating
REFERENCE
KMC PART #
PART DESCRIPTION
FLEXSTAT
BAC-1xx36/
1xxx36
BACNET THERMOSTAT, 6 RELAY & 3 ANALOG OUTPUTS
R1, R2, R3
REE-3211
MULTI-VOLTAGE CONTROL RELAY, 1.2 VA
VLV
VEB-43xxxBCK
CONTROL VALVE W/ MEP-4002 0-10V ACTUATOR, 4 VA
FOR VALVE, CHOOSE CAPACITY/MODEL FROM KMC DATA SHEET
DAT
STE-1402
DUCT TEMPERATURE SENSOR
FST
CSE-1102
AIR DIFFERENTIAL PRESSURE SWITCH, 0.05-12" WC
W-TMP
STE-1454/1455
2" STRAP-ON TEMPERATURE SENSOR (w/ or w/o enclosure)
*
STE-6011
REMOTE TEMPERATURE SENSOR, TYPE II
TX
XEE-6311-050
TRANSFORMER, 120/240/277/480:24 VAC, 50 VA
*The remote temperature sensor option is not shown in the sample installation
diagrams, and it is available only on BAC-12xxxx/13xxxx/14xxxx models.
BILL OF MATERIALS: FCU, 4-Pipe, Modulating
REFERENCE
KMC PART #
PART DESCRIPTION
FLEXSTAT
BAC-1xx63/
1xxx63
BACNET THERMOSTAT, 6 RELAY & 3 ANALOG OUTPUTS
R1, R2, R3
REE-3211
MULTI-VOLTAGE CONTROL RELAY, 1.2 VA
CLV
VEB-43xxxBCK
CONTROL VALVE W/ MEP-4002 0-10V ACTUATOR, 4 VA
HTV
HUMV
VEB-43xxxBDL
FAIL-SAFE CONTROL VALVE, W/ MEP-5372 2-10 VDC
ACTUATOR, 19 VA
FOR VALVES, CHOOSE CAPACITY/MODEL FROM KMC DATA SHEET
HUM
REE-3112
12/24 VDC CONTROL RELAY, SPDT
DAT
STE-1402
DUCT TEMPERATURE SENSOR
FST
CSE-1102
AIR DIFFERENTIAL PRESSURE SWITCH, 0.05-12" WC
*
STE-6011
REMOTE TEMPERATURE SENSOR, TYPE II
TX
XEE-6311-050
TRANSFORMER, 120/240/277/480:24 VAC, 50 VA
*The remote temperature sensor option is not shown in the sample installation
diagrams, and it is available only on BAC-12xxxx/13xxxx/14xxxx models.