BAC-1xx63/1xxx63 Series (6 Relays and 3 Analog Outputs) Section
29
Application Guide L
HPU (Heat Pump Unit)—
1 or 2 Compressors w/ Aux. & Emergency Heat
BILL OF MATERIALS: HPU, DAMPER ACTUATORS
REFERENCE
MAX DAMPER
AREA IN FT
2
KMC PART #
PART DESCRIPTION
OAD or RTD
6.25
MEP-5372
50 IN·LB FAIL-SAFE ACTUATOR, 2-10VDC,
19VA
OAD or RTD
15
MEP-7252
120 IN·LB FAIL-SAFE ACTUATOR, 0-10VDC,
25VA
OAD or RTD
22.5
MEP-7552
180 IN·LB FAIL-SAFE ACTUATOR, 0-10VDC,
25VA
OAD or RTD
40
MEP-7852
320 IN·LB FAIL-SAFE ACTUATOR, 0-10VDC,
40VA
NOTE: See the corresponding
BAC-1xx63
or
BAC-1xxx63
Installation Guide section for detailed drawings and input/
output connections as well as other important installation
information.
RTU (Roof Top Unit)—1 or 2 Heat and 1 or 2 Cool
NOTE: This was 2 Heat and 2 Cool in firmware R1.3.04 and earlier.
Multistage was added later.
BILL OF MATERIALS: HPU, 1/2 Compressors w/ Aux. & Emergency Heat
REFERENCE
KMC PART #
PART DESCRIPTION
FLEXSTAT
BAC-1xx63/
1xxx63
BACNET THERMOSTAT, 6 RELAY & 3 ANALOG OUTPUTS
DAT
STE-1402
DUCT TEMPERATURE SENSOR
FST
CSE-1102
AIR DIFFERENTIAL PRESSURE SWITCH, 0.05-12" WC
MAT
STE-1416
12' DUCT AVERAGING TEMP SENSOR
OAT
STE-1451
OUTSIDE TEMPERATURE SENSOR
*
STE-6011
REMOTE TEMPERATURE SENSOR, TYPE II
*
SAE-10xx
REMOTE CO
2
SENSOR, SPACE OR DUCT
CHOOSE ONE OF THE FOLLOWING TRANSFORMERS:
TX2
XEE-6311-075
TRANSFORMER, 120/208/240/480:24 VAC, 75 VA
TX2
XEE-6311-100
TRANSFORMER, 120/240/277/480:24 VAC, 96 VA
*The remote temperature and CO
2
sensor options are not shown in the sample installation
diagrams, and they are available only on BAC-12xxxx/13xxxx/14xxxx models.
BILL OF MATERIALS: RTU, DAMPER ACTUATORS
REFERENCE
MAX DAMPER
AREA IN FT
2
KMC PART #
PART DESCRIPTION
OAD or RTD
6.25
MEP-5372
50 IN·LB FAIL-SAFE ACTUATOR, 2-10VDC,
19VA
OAD or RTD
15
MEP-7252
120 IN·LB FAIL-SAFE ACTUATOR, 0-10VDC,
25VA
OAD or RTD
22.5
MEP-7552
180 IN·LB FAIL-SAFE ACTUATOR, 0-10VDC,
25VA
OAD or RTD
40
MEP-7852
320 IN·LB FAIL-SAFE ACTUATOR, 0-10VDC,
40VA
BILL OF MATERIALS: RTU, 1 or 2 Heat and 1 or 2 Cool
REFERENCE
KMC PART #
PART DESCRIPTION
FLEXSTAT
BAC-1xx63/
1xxx63
BACNET THERMOSTAT, 6 RELAY & 3 ANALOG OUTPUTS
DAT
STE-1402
DUCT TEMPERATURE SENSOR
FST
CSE-1102
AIR DIFFERENTIAL PRESSURE SWITCH, 0.05-12" WC
MAT
STE-1416
12' DUCT AVERAGING TEMP SENSOR
OAT
STE-1451
OUTSIDE TEMPERATURE SENSOR
*
STE-6011
REMOTE TEMPERATURE SENSOR, TYPE II
*
SAE-10xx
REMOTE CO
2
SENSOR, SPACE OR DUCT
CHOOSE ONE OF THE FOLLOWING TRANSFORMERS:
TX2
XEE-6311-075
TRANSFORMER, 120/208/240/480:24 VAC, 75 VA
TX2
XEE-6311-100
TRANSFORMER, 120/240/277/480:24 VAC, 96 VA
*The remote temperature and CO
2
sensor options are not shown in the sample installation
diagrams, and they are available only on BAC-12xxxx/13xxxx/14xxxx models.
NOTE: On BAC-12xxxx/13xxxx/14xxxx models, when IN7 is
configured for a remote space temperature sensor, space
temperature can be configured for onboard, remote, averaging
of the two, the lowest reading, or the highest reading. When
DCV is enabled, IN9 is assumed to be connected to an external
SAE-10xx CO
2
sensor. See the
FlexStat Operation Guide
for
more details.