Sensor Setup
SENSOR SETUP
IN 2:
DISCH AIR TEMP
The Input 2 sensor (AI2) can be configured for
discharge air temperature (Type III thermistor is the
default), fan status (dry contact), or unused.
• If set for discharge air temperature, the sensor
can be calibrated and changed from the default
Type III thermistor to a Type II. See
(Advanced)
Inputs on page 8
.
• If set for discharge air temperature, Trend Log
#2 is automatically created and monitors the
discharge air temperature, but it has no effect on
operation.
• If set for fan status and no closed contact is
detected when there is a call for fan operation, a
Fan Fail Alarm is created. See
Alarms on page 11
.
• If set for unused, built-in applications will not
use AI2, but the input would be available to
custom programming.
Staging Setup
STAGING
STG DELAY (MINS):
3
Valve Setup
VALVE SETUP
TYPE:
ACTION: NRM OPEN
2–POSITION
(Advanced) CB (Control Basic) Programs
CB PROGRAMS
PROG1:
PROG2: RUNNING
PROG3: RUNNING
PROG4: RUNNING
PROG5: RUNNING
PROG6: HALTED
PROG7: IDLE
RUNNING
PROGRAM #1
SETPOINTS & MODES
AUTO-RUN: TRUE
CHANGE: READY
STATE: RUNNING
HALT REASON: NORMAL
HALT DESC:
OUT OF SERVICE: FALSE
To halt or load/run the built-in (1–5) and custom
(6–10) Control Basic programs, press:
1. Up
/
Down
to move among entries.
2. Enter
to select.
3. Right
/
Left
to move among value fields.
4. Up
/
Down
to increment/decrement value.
NOTE: If
custom
Control Basic programs are
installed and
a restore to factory settings
is performed, all factory programs are
restarted but all custom Control Basic
programs are halted.
Change the state
of each program by loading/running the
program from the CB Programs menu (or
BACstage).
NOTE: If
custom
Control Basic programs are
installed
and set to autorun
, whenever the
firmware is updated
,
ALL (factory and
custom) programs are halted.
If
custom
Control Basic programs are
installed
but NOT set to autorun,
whenever the firmware is updated, factory
programs are restarted but any (manual)
running custom programs are halted at
restart.
Change the state of each custom program
by using the Update Manager or loading/
running each program from the CB
Programs menu (or BACstage).
UPDATE MANAGER
PROGRAM CONFIG ERROR
ENABLE FACTORY:
ENABLE CUSTOM: NO
EDIT CB PROGRAMS
DONE
NO
NOTE:
Customized programs are the responsibility
of the user.
KMC Controls does not provide
support for such programs.