5
18.10.2016
Ex-proof roof fans
WP-
…
-D/Ex
3.
Reservations of Producer
A.
Manufacturer accepts no liability for any consequences following from the operational use
that is in contradiction to the purpose of application.
B.
Installing any additional elements not belonging to the normal device structure
(or accessory set) is not acceptable.
C.
Any structural changes or device
modifications on one’s own are not permitted.
D.
Protect the appliance’s housing from mechanical damage.
E.
Before installing
– it is important it examine the load carrying capability of the structural
elements of the building where the roof fan shall be installed. Unsure mounting could re-
sult in uncontrolled device detachment, its damage and hazard to people in the vicinity.
F.
Do not use the fan for conveying the air containing viscous impurities
that could deposit on the device surface, especially on the impeller.
G.
Neither use it for forwarding the air with aggressive pollutants which
will destructively effect the device structure.
H.
During operation, the maximum impeller rotations should not exceed the nominal rotations.
I.
Producer is not responsible for wounds, injuries, body laceration experienced by
User or personnel during the improper operational use.
4.
Technical Data
Table No.1
Type
Synchro-
nous
rotations
[1/min]
Supply
voltage
[V]
Motor
rate
[kW]
Ingress
protect-
tion
IP
Acoustic
pressure
level
[dB(A)]
from the
INLET
from distance
Acoustic
pressure
level
[dB(A)]
from the
OUTLET
from distance
Maximum
volume flow
[m
3
/h]
Maximum
vacuum
[Pa]
Weight
[kg]
1m
5m
1m
5m
WP-3-D/Ex
3000
3 x 400
0,37
54
58
51
61
52
900
900
19
WP-5-D/Ex
3000
3 x 400
0,55
54
63
55
64
56
1550
1400
24
WP-7-D/Ex
3000
3 x 400
1,1
54
67
61
71
62
2200
1850
26
WP-8-D/Ex
3000
3 x 400
1,5
54
72
64
77
67
2500
2200
37
WP-9-D/Ex
3000
3 x 400
2,2
54
74
67
77
68
2800
2500
43
WP-10-D/Ex
3000
3 x 400
4,0
54
75
68
78
69
4250
2400
78
WP-11-D/Ex
3000
3 x 400
4,0
54
77
69
80
70
5000
2700
80
Noise measurement has been conducted:
–
at maximum volume flow,
–
at the
TK
silencer attached at the fan inlet (silencer length
370
mm
for
WP-3-E/Ex
and 1000 mmm for the other fans from the series,
1.
Maximum temperature of the conveyed air is +
60ºC,
whereas maximum temperature within the work zone +4
0ºC.
2.
Maximum dustiness of the conveyed air should not exceed 0,3 g/m
3
.