12
dust separator
WE-5,5/D
08.11.2019
To obtain the remote control follow subsequent steps:
1
.
Turn the S2 switch (in the control unit) into position “
REMOTE
”;
–
the fan starts after using the external panel.
The fan work is confirmed by the green lamp
H2
.
2
. On the external panel, (as ready for use), the white lamp
H4
lights on.
3
. Set the
S4
switch into position “
ON
”. The fan of the separator is being operated, and the
status
RUN
is signalised by the green lamp
H5
on the panel and the green lamp
H2
in
the control unit.
The s
ituations of “
ALARM
” failure / malfunctions are indicated on the signalling panel by a red
lamp
H6
, whereas on the control unit by the red lamp
H3
.
STATES OF FAILURE
In case of malfunction of the
Q1
or
Q2
motor protective switch, the
H3
lamp “
ALARM
” lights
in a blinking (pulsing) way and the fan is stopped. Necessarily, fix the switch failure reason,
and subsequently start the fan with the
S3
button “
RESET
”.
Consequences of incorrect operational use:
–
breaking of the bearings,
–
damages being caused by corrosion,
–
loss in balance of the rotary elements,
–
vibrations,
–
deformations,
–
damages being caused by friction.
Hazards that may occur due to inappropriate use
:
–
damages and other defects caused by:
rupture of the impeller,
breaking of the shaft,
fatigue rupture of the material,
fire and explosion caused by sparks.
The construction of the device provides its operational use without pre-adjustment and every-
day routine maintenance.
In case when any defective function is by noise or visually spotted, follow steps as in the Sec-
tion 8.
8.
Troubleshooting Guide
Table No.2
Problem
Possible reason
Corrective action
1.
Lack of the air flow suddenly Clogging in the ventilation
Unclog the extraction duct
occurs in one of the branches extraction duct takes place
Breaking of the bearings
Disconnect the fan from power
supply and remove the reason
of malfunction
2.
Sudden vibrations of the fan
Damage of the impeller
Disconnect the motor from the
occur
power supply. Remove the mo-
tor and send it to the producer
or
specialised servicing workshop
Impeller replacement for new can
be executed exclusively by manu-
facturer or their representative
tative.