FIRE DAMPERS

358

359

Design changes reserved

425

270

n

-2

n

+100

40

425

270

n

-2

n

+85

40

120

250

FDC25-M cylindrical fire damper with electric actuator

• 

Thermoelectric activation (72°C) with electric actuator and return spring

• 

Integrated end switches  

• 

Fully automatic operation

• 

Networking capability (MP-BUS, LonWorks, AS-i BUS)

fire damper housing

1

damper blade

2

electric actuator: Belimo BLF

3

thermo-electric tripping device (72°C)

4

intumescent strip

5

Options: 

M230 – electric actuator AC 230V    

M24 – electric actuator AC/DC 24V

FDC25-R cylindrical fire damper with manual mechanism 

• automactic closure when the temperature in the duct exceed 72°C

• manual rearmation with handle

• manual unlocking possible for periodical test of fire damper

DAMPER MODELS

fire damper housing

1

damper blade

2

manual mechanism

3

fusible link (72°C)

4

smoke seal

5

intumescent strip

6

limit switch

7

1
2

3

4

5

1
2
3

4

5

7

Summary of Contents for FD25-E

Page 1: ...355 www klimaoprema hr FDC25 FIRE DAMPER 7 S4 v 2 9 en...

Page 2: ...ased 361 Installation in a flexible wall mortar based 361 Installation in ceiling mortar based 362 Installation in a rigid wall mortarless 362 Installation in a flexible wall mortarless 363 Installati...

Page 3: ...with greater fire resistance can also be used Fire damper should be installed according instal lation manual which can be found within this document Table 1 Dimensions FIRE DAMPER FDC25 Standard diam...

Page 4: ...sm type R manual mechanism E230 solenoid actuator AC230V E24 solenoid actuator AC 24V M230 electric actuator AC230V M24 electric actuator AC DC 24V Options s electric limit switches indicating damper...

Page 5: ...er blade 2 electric actuator Belimo BLF 3 thermo electric tripping device 72 C 4 intumescent strip 5 Options M230 electric actuator AC 230V M24 electric actuator AC DC 24V FDC25 R cylindrical fire dam...

Page 6: ...zed steel but on demand can be made from Galvanized steel and powder coated Stainless steel Stainless steel and powder coated Fire damper for areas with potentially explosive atmospheres are also avai...

Page 7: ...FDC25 Wall according to table 1 Installation steps Recommended wall opening for fire damper installation is 160mm but openings from 80 200 mm can also be used Insert fire damper into wall and secure o...

Page 8: ...mper blade mobility preform an opening and closing test 3 4 Fire damper FDC25 Wall according to table 1 Installation in a rigid wall mortarless 1 2 3 4 Installation steps Recommended ceiling opening f...

Page 9: ...ing test 3 4 Fire damper FDC25 Wall according to table 1 Installation material Fire damper FDC25 Mineral wool 140kg m3 Fire protection coating HILTI weichschott system Installation steps Recommended c...

Page 10: ...ble connectors are being installed very important is to install extension peace if necessary see table 2 ACCESSORIES Suspension for mortarless installation Suspension systems are required for the dry...

Page 11: ...e supplied with one or two limit switches switches can also be fitted later DAMPER OPEN DAMPER CLOSED Fire damper is shipped with closed damper blade Fire damper with manual actuating mechanism is ope...

Page 12: ...not move the damper into closed position after power failure ther moelectric fuse switch for checking for proper functioning handle for manual opening Belimo BLF24 T i BF24 T supply via safety isolati...

Page 13: ...per Level Digital field controller K FC24 Digital field controller to control and monitor up to 4 motorized fire dampers and 4 smoke detectors Communication Modbus RTU RS 485 The safety function of th...