FIRE DAMPERS

366

367

Design changes reserved

Digital controller K-M200

• 

Digital controller K-M200 to control and monitor up to 200 motorized fire dampers and 
200 smoke detectors

• 

Pre-programmed for fire safety application

• 

No programming knowledge necessary! Simple parameterisation through touch screen or 
remote access via web browser

• 

Communication: Modbus RTU (RS-485) to the K-FC24’s / K-UFC24’s and the internal 
I/O’s, TCP / IP (Ethernet RJ45) for remote access or combining multiple units. Integrated 
IP-address

• 

Automatic test of the whole system including test report

FIRE

ALARM

M

odbus

Digital controller K-M200 

1

... 50

24 V AC

FIRE

ALARM

M

odbus

...50

1

24 V AC/DC

24 V AC/DC

Digital field controller 

K-FC24 

Universal digital field controller 

K-UFC24 

Digital controller K-M200 

System overview

FIRE DAMPER CONTROL

Controller / 
Building Management Level

Cabinet Level

Field / Damper Level

Digital field controller K-FC24

• 

Digital field controller to control and monitor up to 4 motorized fire dampers and 4 smoke 
detectors

• 

Communication: Modbus RTU (RS-485)

• 

The safety function of the connected devices is not affected when communication with 
Modbus is interrupted

Universal digital field controller K-UFC24

• 

Universal System Link between motorized fire or smoke extraction dampers and any Mod-
bus or BACnet system or analog control

• 

Controls and monitors max 2 fire or smoke extraction dampers as well as 1 smoke detec-
tor and 1 thermoelectrical tripping device

• 

The Universal Field Controller offers 3 different control modes (to be chosen through dip 
switch terminals) :

• 

Fire or smoke extraction application

• 

Bus protocols: Modbus (RS-485) or BACnet (Ms/Tp)

• 

Analog: Input and output signals

• 

Easy to install thanks to the mounting bracket which can be pre-installed. The UFC24 can 
be snapped on any time during the project

• 

Easy and clear indication of function, position and status with LEDs

• 

Independent functional control through test key at any time

Summary of Contents for FD25-E

Page 1: ...355 www klimaoprema hr FDC25 FIRE DAMPER 7 S4 v 2 9 en...

Page 2: ...ased 361 Installation in a flexible wall mortar based 361 Installation in ceiling mortar based 362 Installation in a rigid wall mortarless 362 Installation in a flexible wall mortarless 363 Installati...

Page 3: ...with greater fire resistance can also be used Fire damper should be installed according instal lation manual which can be found within this document Table 1 Dimensions FIRE DAMPER FDC25 Standard diam...

Page 4: ...sm type R manual mechanism E230 solenoid actuator AC230V E24 solenoid actuator AC 24V M230 electric actuator AC230V M24 electric actuator AC DC 24V Options s electric limit switches indicating damper...

Page 5: ...er blade 2 electric actuator Belimo BLF 3 thermo electric tripping device 72 C 4 intumescent strip 5 Options M230 electric actuator AC 230V M24 electric actuator AC DC 24V FDC25 R cylindrical fire dam...

Page 6: ...zed steel but on demand can be made from Galvanized steel and powder coated Stainless steel Stainless steel and powder coated Fire damper for areas with potentially explosive atmospheres are also avai...

Page 7: ...FDC25 Wall according to table 1 Installation steps Recommended wall opening for fire damper installation is 160mm but openings from 80 200 mm can also be used Insert fire damper into wall and secure o...

Page 8: ...mper blade mobility preform an opening and closing test 3 4 Fire damper FDC25 Wall according to table 1 Installation in a rigid wall mortarless 1 2 3 4 Installation steps Recommended ceiling opening f...

Page 9: ...ing test 3 4 Fire damper FDC25 Wall according to table 1 Installation material Fire damper FDC25 Mineral wool 140kg m3 Fire protection coating HILTI weichschott system Installation steps Recommended c...

Page 10: ...ble connectors are being installed very important is to install extension peace if necessary see table 2 ACCESSORIES Suspension for mortarless installation Suspension systems are required for the dry...

Page 11: ...e supplied with one or two limit switches switches can also be fitted later DAMPER OPEN DAMPER CLOSED Fire damper is shipped with closed damper blade Fire damper with manual actuating mechanism is ope...

Page 12: ...not move the damper into closed position after power failure ther moelectric fuse switch for checking for proper functioning handle for manual opening Belimo BLF24 T i BF24 T supply via safety isolati...

Page 13: ...per Level Digital field controller K FC24 Digital field controller to control and monitor up to 4 motorized fire dampers and 4 smoke detectors Communication Modbus RTU RS 485 The safety function of th...

Reviews:

Related manuals for FD25-E