Summary of Contents for KTIM series

Page 1: ...ur way Cassette Type INSTALLATION MANUAL Thank you very much for purchasing our air conditioner Before using your air conditioner please read this manual carefully and keep it for future reference KTI...

Page 2: ...door Unit Installation 11 a Outdoor Unit Installation Instructions 11 b Outdoor Unit Types and Specifications 12 c Notes on Drilling Hole in Wall 13 Drainpipe Installation 14 Table of Contents Install...

Page 3: ...efrigerant Piping Connection Instructions 17 Wiring 19 a Outdoor Unit Wiring 19 b Indoor Unit Wiring 20 c Power Specifications 21 d Wiring Diagram 22 Air Evacuation 23 a Evacuation Instructions 23 b N...

Page 4: ...lation sheath some models 1 Drainpipe Fittings Outlet pipe sheath some models 1 Outlet pipe clasp some models 1 Drain joint some models 1 Seal ring some models 1 Installation Accessory some models Cei...

Page 5: ...ong winds typhoons and earthquakes that might affect your unit and locate it accordingly Failure to do so could cause the equipment to fail After installation ensure there are no refrigerant leaks and...

Page 6: ...7 8 Install the indoor unit Page 7 INSTALLATION ORDER Install the outdoor unit Page 11 Install the drainpipe Page 14 Evacuate the refrigeration system Page 23 Connect the wires Page 19 Connect the ref...

Page 7: ...property damage or death Install the indoor unit at a height of more than 2 5m 8 above the floor DO NOT install the indoor unit in the bathroom or laundry room as excessive moisture can short the unit...

Page 8: ...cations In areas with oil drilling or fracking In coastal areas with high salt content in the air In areas with caustic gases in the air such as near hot springs In areas with power fluctuations such...

Page 9: ...rom ceiling relative to height of indoor unit MODEL Length of A mm inch Length of H mm inch 18 205 8 235 9 3 24 205 8 235 9 3 30 205 8 235 9 3 30 48 245 9 6 275 10 8 48 60 287 11 3 317 12 5 Step 2 Han...

Page 10: ...board Main body 10 18mm 0 4 0 7 L NOTE Ensure that the indoor unit is level The unit is equipped with a built in drain pump and float switch If the unit is tilted against the direction of condensate...

Page 11: ...length between the outdoor and indoor unit may not exceed the maximum allowable pipe length If possible DO NOT install the unit where it is exposed to direct sunlight If possible make sure the unit i...

Page 12: ...ble 5 2 Fig 5 7 Fig 5 8 Fig 5 9 Outdoor Unit Installation Fig 5 6 Fig 5 5 A B D W H W H Fig 5 4 Outdoor Unit Dimensions W x H x D Mounting Dimensions Distance A Distance B 760x590x285 29 9x23 2x11 2 5...

Page 13: ...int 90 until it clicks in place facing the front of the unit 4 Connect a drain hose extension not included to the drain joint to redirect water from the unit during heating mode NOTE Make sure the wat...

Page 14: ...ation may cause unit and property damage CAUTION Insulate all piping to prevent condensation which could lead to water damage If the drainpipe is bent or installed incorrectly water may leak and cause...

Page 15: ...Wall Indoor Outdoor 12mm 0 5 inch Fig 6 5 NOTE When drilling the wall hole make sure to avoid wires plumbing and other sensitive components 4 Pass the drain hose through the wall hole Make sure the wa...

Page 16: ...rant leakage after completing the installation work Notes On Pipe Length and Elevation Ensure that the length of the refrigerant pipe the number of bends and the drop height between the indoor and out...

Page 17: ...while cutting Be extra careful not to damage dent or deform the pipe while cutting This will drastically reduce the heating efficiency of the unit 1 Make sure that the pipe is cut at a perfect 90 angl...

Page 18: ...ue wrench to tighten the flare nut according to the torque values in table 7 5 NOTE Use both a spanner and a torque wrench when connecting or disconnecting pipes to from the unit Fig 7 8 CAUTION Ensur...

Page 19: ...t 3mm 0 118 DO NOT modify the length of the power cord or use an extension cord CAUTION Connect the outdoor wires before connecting theindoor wires Make sure you ground the unit The grounding wire sho...

Page 20: ...onnection a Using wire strippers strip the rubber jacket from both ends of signal cable to reveal about 15cm 5 9 of the wires inside b Strip the insulation from the ends of the wires c Using wire crim...

Page 21: ...420V 208 240V 208 240V CIRCUIT BREAKER FUSE A 25 20 32 25 32 25 45 35 Independent Power Supply Specifications MODEL Btu h 18K 19K 24K 25K 36K 37K 48K 49K 60K POWER indoor PHASE 1 Phase 1 Phase 1 Phase...

Page 22: ...e 1 Phase 1 Phase 1 Phase 1 Phase FREQUENCY AND VOLT 220 240V 220 240V 220 240V 220 240V 220 240V CIRCUIT BREAKER FUSE A 15 10 15 10 15 10 15 10 15 10 POWER outdoor PHASE 1 Phase 1 Phase 1 Phase 1 Pha...

Page 23: ...he manifold gauge Keep the High Pressure side closed 4 Turn on the vacuum pump to evacuate the system 5 Run the vacuum for at least 15 minutes or until the Compound Meter reads 76cmHG 1x105Pa 6 Close...

Page 24: ...The additional refrigerant to be charged can be calculated using the following formula Liquid Side Diameter 6 35 1 4 9 52 3 8 12 7 1 2 R22 orifice tube in the indoor unit Total pipe length standard p...

Page 25: ...d drain sides Hang the four latches of the decorative panel to the hooks of the indoor unit Tighten the panel hook screws evenly at the four corners See Fig 10 3 NOTE Tighten the screws until the thic...

Page 26: ...e height of the indoor unit needs to be adjusted you can do so through the openings at the panel s four corners Make sure that the internal wiring and drainpipe are not affected by this adjustment CAU...

Page 27: ...rature is being registered correctly d Ensure the indicators on the remote control and the display panel on the indoor unit work properly e Ensure the manual buttons on the indoor unit works properly...

Page 28: ...t improvement Consult with the sales agency or manufacturer for details 2190 NW 89 Place Doral FL 33172 USA Tel 305 594 4972 Fax 305 675 2212 www klimaire com sales klimaire com The Klimaire logo is a...