background image

Nexus Pulse 105 Red/White Flash Sounder-Beacon

Installation Instructions

EN

DE

FR

NL

ES

PT

IT

PL

SE

DK

Texecom Ltd (Incorporating Klaxon Signals)

St Crispin Way, Haslingden, BB4 4PW, UK

Tel: +44 (0)1706 233879

 (MARCH 2016) INS593-3 

 Copyright © Texecom Ltd

email: [email protected]   www.klaxonsignals.com

Tone

Tone Type

Tone Description /Application

Dip Switch

(S1/S2)

3rd Stage

Tone

Peak Sound

Level

(dBA @1m, 24-V DC)

Sounder 

Current

(mA Avg, 24V DC)

1.

 970Hz (BS5839-1:2002)

O-O-O-O-O-O

18

105

31

2

 800Hz/970Hz @ 2Hz (BS5839-1:2002)

O-O-O-O-O-I

1

105

28

3

 800Hz – 970Hz @ 1Hz (BS5839-1:2002)

O-O-O-O-I-O

1

104

25

4

 970Hz 1s OFF/1s ON  (Apollo Fire Systems Alert Tone, BS5839-1:2002)

O-O-O-O-I-I

1

105

17

5

 970Hz, 0.5s/ 630Hz, 0.5s (Apollo Fire Systems Evacuate Tone, BS5839-1:2002)

O-O-O-I-O-O

1

105

27

6

 554Hz, 0.1s/ 440Hz, 0.4s  (France – AFNOR NF S 32 001 ) 

O-O-O-I-O-I

1

103

20

7

 500 – 1200Hz, 3.5s/ 0.5s OFF (Netherlands – NEN 2575:2000 Dutch Slow Whoop) 

O-O-O-I-I-O

1

108

19

8

 420Hz 0.625s ON/0.625s OFF (Australia AS1670 Alert tone) 

O - O - O - I - I - I

1

102

10

9

 500 – 1200Hz, 0.5s/ 0.5s OFF x 3/1.5s OFF (Australia AS1670 Evacuation tone) 

O-O-I-O-O-O

1

106

13

10

 550Hz/440Hz @ 0.5Hz 

O-O-I-O-O-I

19

104

21

11

 970Hz, 0.5s ON/0.5s OFF x 3/ 1.5s OFF (ISO 8201 Low tone)

O-O-I-O-I-O

1

105

13

12

 2850Hz, 0.5s ON/0.5s OFF x 3/1.5s OFF (ISO 8201 High tone)

O - O - I - O - I - I

1

107

16

13

 1200Hz – 500Hz @ 1Hz (DIN 33 404)

O-O-I-I-O-O

1

109

22

14

 400Hz

O - O - I - I - O - I

18

101

16

15

 550Hz, 0.7s/1000Hz, 0.33s

O - O - I - I - I - O

1

105

25

16

 1500Hz – 2700Hz @ 3Hz (Vandal Alarm)

O - O - I - I - I - I

1

113

32

17

 Simulated Bell

O-I-O-O-O-O

1

107

18

18

 2130Hz

O-I-O-O-O-I

1

110

26

19

 660Hz

O-I-O-O-I-O

10

102

25

20

 660Hz 1.8s ON/1.8s OFF

O - I - O - O - I - I

19

102

14

21

 660Hz  0.15s ON/0.15s OFF

O-I-O-I-O-O

19

102

14

22

 510Hz, 0.25s/ 610Hz, 0.25s

O - I - O - I - O - I

1

103

24

23

 800/1000Hz 0.5s each (1Hz)

O - I - O - I - I - O

1

106

25

24

 250Hz – 1200Hz @ 12Hz

O - I - O - I - I - I

1

101

23

25

 500Hz – 1200Hz @ 0.33Hz.

O-I-I-O-O-O

1

108

21

26

 2400Hz – 2900Hz @  9Hz

O - I - I - O - O - I

1

113

39

27

 2400Hz – 2900Hz @ 3Hz

O - I - I - O - I - O

1

111

39

28

 800Hz – 970Hz @ 100Hz

O - I - I - O - I - I

1

104

23

29

 800Hz – 970Hz @ 9Hz

O - I - I - I - O - O

1

104

27

30

 800Hz – 970Hz @ 3Hz

O - I - I - I - O - I

1

105

28

31

 800Hz, 0.25s ON/1s OFF

O - I - I - I - I - O

1

103

8

32

 500Hz – 1200Hz, 3.75s/0.25s OFF (AS2220)

O - I - I - I - I - I

1

108

20

33

 340Hz

I-O-O-O-O-O

1

101

17

34

 1000Hz

I-O-O-O-O-I

18

106

25

35

 1400Hz – 1600Hz, 1s/1600Hz – 1400Hz, 0.5s (NF 48-265)

I-O-O-O-I-O

1

104

34

36

 660Hz 6.5s ON/13s OFF

I - O - O - O - I - I

19

102

9

37

 1000Hz/2000Hz, 1s each

I-O-O-I-O-O

1

108

25

38

 720Hz, 0.7s ON/0.3s OFF

I - O - O - I - O - I

1

104

16

39

 970Hz, 0.25s ON/OFF 

I - O - O - I - I - O

1

105

17

40

 2800Hz, 1s ON/OFF

I - O - O - I - I - I

1

106

20

41

 2800Hz 0.25s ON/OFF

I-O-I-O-O-O

1

106

19

42

 2400/2900 @ 2Hz

I - O - I - O - O - I

1

113

38

43

 Chime, 554Hz/440Hz Single shot ‘ding dong’

I - O - I - O - I - O

1

100

15

44

 Chime, 554Hz/440Hz Repeating ‘ding dong’

I - O - I - O - I - I

1

102

15

45

 Chime, 970Hz/800Hz Single shot ‘ding dong’

I- O - I - I - O - O

1

101

36

46

 Chime, 970Hz/800Hz Repeating ‘ding dong’

I - O - I - I - O - I

1

100

36

47

 Hooter, Repeating

I - O - I - I - I - O

1

102

13

48

 Gentle alarm - Tone 2, rises slowly to full volume over 30s 

I - O - I - I - I - I

1

105

28

49

 Time-Out Alarm – As Tone 2, cuts off after 10 mins

I-I-O-O-O-O

1

105

28

50

 Time-Out Alarm – As Tone 2, cuts off after 2 mins

I - I - O - O - O - I

1

105

28

51

 750Hz 0.33s ON/0.51s OFF 

I - I - O - O - I - O

1

103

8

52

 750Hz  0.51s ON/0.33s OFF

I - I - O - O - I - I

1

103

15

53

 550Hz, 0.33s/1000Hz, 0.7s

I - I - O - I - O - O

1

106

25

54

 600Hz – 900Hz/ 0.9s  

I - I - O - I - O - I

1

104

31

55

 660Hz – 680Hz/ 0.9s 

I - I - O - I - I - O

1

101

28

56

 670Hz – 725Hz/ 0.9s 

I - I - O - I - I - I

1

104

25

57

 920Hz – 750Hz/ 0.9s 

I - I - I - O - O - O

1

104

30

58

 700Hz - 900Hz, 0.3s/0.6s OFF

I - I - I - O - O - I

1

104

11

59

 900Hz - 760Hz, 0.6s/0.3s OFF

I - I - I - O - I - O

1

105

19

60

 750Hz

I - I - I - O - I - I

18

103

22

61

 Power Only – Use with Stage 3 control for manual/intermittent chime triggering 

I - I - I - I - O - O

43

62

 Power Only – Use with Stage 3 control for manual/intermittent chime triggering

I - I - I - I - O - I

43

63

 Power Only – Use with Stage 3 control for manual/intermittent horn triggering

I - I - I - I - I - O

47

EN54-3:2001+A1:2002+A2:2006; EN54-23:2010

Fire Alarm Device – Sounder

Type B: For indoor or outdoor use

Datasheet ATS00009

Base - 18-186369

Head Type

Coverage Volume CPR Number

ENCA1000

W-3.1-11.3

0832-CPR-F0164

ENDA1000

W-2.4-7.5

0832-CPR-F0165

0832

14

Summary of Contents for Nexus Pulse 105 Red

Page 1: ...28 800Hz 970Hz 100Hz O I I O I I 1 104 23 29 800Hz 970Hz 9Hz O I I I O O 1 104 27 30 800Hz 970Hz 3Hz O I I I O I 1 105 28 31 800Hz 0 25s ON 1s OFF O I I I I O 1 103 8 32 500Hz 1200Hz 3 75s 0 25s OFF AS2220 O I I I I I 1 108 20 33 340Hz I O O O O O 1 101 17 34 1000Hz I O O O O I 18 106 25 35 1400Hz 1600Hz 1s 1600Hz 1400Hz 0 5s NF 48 265 I O O O I O 1 104 34 36 660Hz 6 5s ON 13s OFF I O O O I I 19 1...

Page 2: ...re Protection Pass Essential Characteristics EN54 23 2010 Subclause Duration of operation Pass Provision for external conductors Pass Flammability of materials Pass Enclosure protection Pass Access Pass Manufacturers adjustments Pass On site adjustment behaviour Pass Requirements for software controlled devices Pass Coverage volume Pass Variation of light output Pass Minimum and maximum light inte...

Page 3: ...eingestellt Die erforderlichen Einstellungen sind in der Tabelle auf der nächsten Seite angegeben Der Alarmton der dritten Stufe ist zur Ergänzung des Tons der ersten Stufe voreingestellt siehe Tabelle 2 Lautstärkeregelung Durch Regulierung des Potentiometers kann die Lautstärke des Geräts um bis zu 20dBA reduziert werden Um die Anforderungen der EU Norm EN54 3 zu erfüllen muss das Potentiometer a...

Page 4: ...eid voor 3 alarmstadiums negatieve spanningsactivering Gebruikstemperatuur 25 C bis 70 C Behuizing Slagvast polycarbonaat IP waard IP66 Synchronisatie Automatisch 0 5Hz 1Hz Installation 1 Le socle de la sirène doit être fixé au préalable 2 Les raccordements s effectuent directement sur le socle de la sirène 3 La sirène est ensuite vissée sur le socle via 4 vis de tour utiliser uniquement un tourne...

Page 5: ...ver os equipamentos em fim de vida para eliminação Para mais informações consultar o seguinte sítio da Web http www recyclethis info Linha Marcação Terminal Alimentação Positiva do Besouro CC 10 V a 60 VC Alimentação Negativa do Besouro 0 V Controlo de Alarme 2ª Fase Ligar a 0 V para activar S2 Controlo de Alarme 3ª Fase Ligar a 0 V para activar S3 Alimentação Positiva do Farol CC 10 V a 60 V Alim...

Page 6: ...stico si installa in primo luogo montando l unità di base e collegando quindi i cavi esterni alla base L unità principale quindi si collega automaticamente quando viene montata sulla base 2 La testa dell apparecchio acustico si separa dalla base sbloccando le quattro chiusure girevoli sugli angoli dell apparecchio acustico cacciavite consigliato Philips Nº 2 di una lunghezza minima di 100 mm 3 Not...

Page 7: ... returnere udtjent udstyr for kassering Yderligere information findes på følgende webside http www recyclethis info Ledning Klemme Positiv forsyning til lydalarm 10 til 60 V jævnstrøm Negativ forsyning til lydalarm 0 V Alarmkontrol 2 trin Slut til 0 V for at aktivere S2 Alarmkontrol 3 trin Slut til 0 V for at aktivere S3 Positiv forsyning til lyskegle 10 til 60 V jævnstrøm Negativ forsyning til ly...

Page 8: ...Texecom Ltd Incorporating Klaxon Signals St Crispin Way Haslingden BB4 4PW UK Tel 44 0 1706 233879 MARCH 2016 INS593 3 Copyright Texecom Ltd email sales klaxonsignals com www klaxonsignals com ...