83003702.K Operating Instruction
Type KPC 108-L-U/S
page 70
\\FILER02\ALLGEMEIN\02 - TECHNISCHE UNTERLAGEN KKT\ORIGINALE\830XXX BEDIENUNGSANLEITUNGEN\KPC\83003702.K KPC108- L-US.DOC
Third control level: Setting of A-Parameters
This level contains the safety relevant characteristics which are pre-set by the factory.
Access to the third control level is granted when selecting the last P-parameter on the second control level. Continue to
press the UP key for approximately 10 seconds until “PA” appears.
Continue to press the UP key and additionally press the DOWN key for about 4 seconds and the first A-parameter of the
third control level is indicated.
With the keys UP and DOWN you can scroll the list in both directions. Pressing the SET key will give you the value of
respective parameter. Pressing the SET key will give you the value of the respective parameter. If the parameter value
is to be changed, the SET key is to be kept pressed while adjusting the parameter value with the keys UP and DOWN.
Return to the initial position takes place automatically, if no key is pressed for 60 seconds, or by simultaneously
pressing the UP and DOWN keys for approx. 4 seconds.
Settings for the parameter values A1 … A59, as far as L0 and L1 – see chapter 4.5 Operating Instructions.