Page 9
E06
AC output load connected is close
to overload limit
Reduce load
E07
Internal temperature is high and is
close to shutdown limit
Reduce load and check if any ventilation
of the unit is blocked
AC Load on Inverter
Although the Power Inverter can provide high surge power up to two times the rated output power,
some high surge loads like sump-pumps, heavy duty motors etc. may still trigger the inverter
protection system even though the load falls within the power rating of the inverter. A higher power
Inverter is required for these appliances.
Important: Each 3-pin AC socket provided can only handle 20A AC current. For appliances that
require more than 2400W (20A) AC Power, hardwiring to the AC Output port 3 is required.
Do not plug surge-protected power bars into the unit’s 120 VAC outlets. The surge protected
components on the surge-protected power bar may not like the modified sinewave output
generated by the inverter.
Some appliances like speed controllers found in some fans, power tools and some power tools’
AC charger may not like the modified sinewave generated by the inverter. Those appliances may
not work or may be damaged if they are connected to the inverter. If you are unsure about
powering a device with the inverter, contact the manufacturer of the device.
Estimated Run Time
Following run times are estimates for reference, based on using different battery bank sizes.
Actual run times may vary.
Estimate run time on different 12V Battery Bank Size
AC Load
60AH 120AH 180AH 240AH 300AH
50 W
11 hrs.
22 hrs.
33 hrs.
44 hrs.
55 hrs.
100 W
5 hrs.
11.5 hrs.
17 hrs.
23 hrs.
29 hrs.
200 W
2.5 hrs.
5 hrs.
8 hrs.
11 hrs.
13.5 hrs.
500 W
49 mins
2 hrs.
3 hrs.
4 hrs.
5 hrs.
1000 W
15 mins
49 mins
1.5 hrs.
2 hrs.
2.5 hrs.
1500 W
8 mins
27 mins
49 mins
1 hr
1.5 hrs
2000 W
N.R.
15 mins
34 mins
49 mins
1 hrs
2500 W
N.R.
11 mins
25 mins
37 mins
49 mins
3000 W
N.R.
N.R.
17 mins
27 mins
37 mins
Note: N.R. - Not Recommended
5. FEATURE
SETTING
To understand more about the unit features, read the following section and follow the instructions
to make desired changes to the setting.
Understanding the Unit Settings
Battery Under Voltage Setting
SdL
Battery under voltage protection setting is set to LOW (used for normal operation)
Under voltage alarm: 11.0 Vdc
Under voltage alarm recovery: 11.3 Vdc
Under voltage shutdown:
10.5 Vdc
Under voltage recovery:
12.0 Vdc
SdH
Battery under voltage protection setting is set to HIGH (setting to avoid battery over
discharge, this setting is used when the inverter is connected to the car start battery)
Under voltage alarm: 12.1 Vdc
Under voltage alarm recovery:
12.3 Vdc
Under voltage shutdown: 11.8 Vdc
Under voltage recovery:
12.6 Vdc
Alarm Setting