d) To save the new setting, press and hold button until display stops flashing.
Understanding the Unit Functions
Function
Display
Description and Available Setting
Inverter
: Use as Inverter only. No By-pass functions.
: Auto Backup. Inverter automatically turns ON when AC Blackout.
(Default)
: Manual Backup. Inverter has to be manually turned ON when AC Blackout
occurs
: Inverter function is disable. No AC backup when AC Blackout.
Load Sense
:
Continuous AC Output when inverter is ON
(Default)
10: Continuous AC Output when inverter is ON and AC load is > 10W
15: Continuous AC Output when inverter is ON and AC load is > 15W
20: Continuous AC Output when inverter is ON and AC load is > 20W
25: Continuous AC Output when inverter is ON and AC load is > 25W
Battery Low
Disconnect
10.5*
Battery Low Disconnect Voltage selectable range: 10.5 - 12.0V (0.1V steps) *
(Default: 10.5V*)
Battery Low
Warning
11.0*
Battery Low Warning Voltage selectable range: 11.0 - 12.5V (0.1V step)*
(Default: 11.0V*)
Battery Under
Voltage
Recovery
12.0*
Battery Low Recovery Voltage selectable range: 11.5 - 13.0V (0.1V step)*
(Default: 12.0V*)
Audible
Buzzer
:
Buzzer is enabled. Unit buzzes when Warning or Error occurs.
(Default)
: Buzzer is disabled. Unit does not buzz when Warning and Error occurs.
Charger
:
Charger is enabled. Charge battery when AC Input is available.
(Default)
: Charger is disabled. No battery charging when AC Input is available.
Battery Type
: GEL Battery, Default Bulk Charge/Float Voltage is 14.2V/13.8V*
(Default)
: Flooded Battery, Default Bulk Charge/Float Voltage is 14.4V/13.5V*
: AGM Battery, Default Bulk Charge/Float Voltage is 14.3V/13.4V*
: Lithium Battery, Default Bulk Charge/Float Voltage is 13.9V/13.5V*
: Program, Default Bulk Charge/Float Voltage is 13.8V/13.2V*
: Power Supply Mode, Default Power Supply Voltage 13.8V*
Bulk Current
100
12V/3000W Models
: Selectable Range:
100A (Default)
, 80A, 60A, 40A, 25A
12V/2000W Models
: Selectable Range:
80A (Default)
, 60A, 40A, 20A, 10A
24V/3000W Models
: Selectable Range:
50A (Default)
, 40A, 30A, 20A, 10A
24V/2000W Models
: Selectable Range:
40A (Default)
, 30A, 20A, 10A, 5A
Bulk/Absorpt-
ion Voltage
14.2*
Bulk/Absorption voltage is based on the battery type choose.
Selectable Range 13.8
– 14.8V*.
(Default on GEL: 14.2V*)
Absorption to
Float Current
10
12V/3000W Models
: Selectable Range: 20A, 15A,
10A(Default)
, 5A, 2A
12V/2000W Models
: Selectable Range: 15A, 10A,
8A(Default)
, 4A, 2A
24V/3000W Models
: Selectable Range: 8A, 6A,
5A(Default)
, 3A, 2A
24V/2000W Models
: Selectable Range: 6A, 5A,
4A(Default)
, 3A, 2A
Float Voltage
13.8*
Float voltage is based on the battery type chosen.
Selectable Range 13.0
– 14.0V*.
(Default on GEL: 13.8V*)
Recharge
Voltage
12.8*
Battery Recharge Voltage Selectable Range: 12.8 to 14.0V (0.1V step)*
(Default: 12.8V*)
Battery
Temperature
: High > 35 °C
: Normal 15 - 35°C
(Default)
: Low <15°C
AC Input
Circuit
Breaker
30
120 Vac Models
: Range: 30A
(Default)
, 20A, 15A
230 Vac Models
: Range: 16A
(Default)
, 13A, 10A
Factory
Default
Select
to reset all settings to default.
* for
24 V Models (BIC2430050, BIC2420040, BIC2430050i, BIC2420040i)
, all the voltage values are doubled.