FOOD DRYING APPLICATIONS (e.g. SAUSAGES) - HEATING MODE WITH COUNTDOWN 

When the parameter 

rHC = 2,

 the relay operates in heating mode based on the parameter 

Hod

 while “

SET”

 is displayed. By pressing 

 the relay is activated and the 

indication “

rUn

” is displayed. By pressing 

 the remaining time is displayed. When timeρ elapses, the relay is deactivated and “

End

” is displayed on screen. By pressing

 again, the procedure starts over. The thermostat constantly controls the relay based on the adjusted Set Point (SPo). If 

SPo

 changes during “

rUn

”, automatically the 

control of the relay is adjusted. If timer “

Hod

” changes during “

rUn

” mode, it will not change until the next running cycle. 

 

ATTENTION

: according to safety standards, the device must be properly positioned and protected from any contact with electrical parts. The device must be fastened in such a way that it cannot 

be removed without the use of tools. Disconnect the main safety switch of the installation before proceeding to any maintenance. Disconnect the power supply of the device before proceeding to 

any maintenance. Do not place the device near heat sources, equipment containing strong magnets, in areas affected by direct sunlight or rain. Prevent electrostatic discharges and sharp objects 
from been inserted to the device. Separate signal cables from power supply cables to prevent electromagnetic disorders. Signal cables must never be in the same pipe with the power supply cables. 

ATTENTION

: Read carefully the technical specifications and make sure that the working conditions are appropriate. According to safety standards, the device must be fastened in such a way that 

it cannot be removed without the use of tools.

 

 

Dimensions are in mm. The device is mounted on panel hole with cut 29x71mm and restrained with plastic side brackets. 

 
 
 
 
 
 

 

PARAMETER TABLE 

 

description 

min 

max 

VD1F 

UOM 

SΡo 

SET POINT: room temperature setting 

LSP 

HSP 

2.0 

°C/°F 

LSP 

Lower setting limit of SPo 

-50.0 

HSP 

-2.0 

°C/°F 

HSP 

Maximum setting limit of SPo 

LSP 

+110 

8.0 

°C/°F 

diF 

Differential of room temperature SPo (thermostat delay) 

0.1 

25.0 

3.0 

°C/°F 

Cod 

Access code to the following parameters Cod = 22.  

255 

Co1 

Compressor’s minimum time OFF 

min 

CF3 

Compressor’s operation in case of sensor’s malfunction (LF1) and in cooling mode: 

0 = 40% compressor’s operation (3min ΟΝ, 4min OFF) / 1 = compressor is ΟΝ continuously. 

In heating mode the relay is deactivated. 

dFr 

Time between two successive defrost

: where dFr = 0 or relay in heating mode, the defrost is deactivated. 

50 

hours 

dd2 

Defrost duration 

(manual and automatic)

 

90 

18 

min 

10 

dE5 

Defrost end temperature is the room temperature 

Automatic defrost stops if room temperature is greater than defrost end temperature dE5. 
Manual defrost starts regardless of the room’s temperature and ends after time adjusted in parameter dd2 elapses.

 

25.0 

10.0 

°C/°F 

11 

CAb 

(not in use) 

12 

dP3 

Dripping timer, where the compressor is OFF after defrost 

10 

min 

13 

dY4 

Display indication during defrost  

0     = indication of room’s temperature 
1 to 40 min = indication of “dFr” from 1 to 40  min counting from the beginning of defrost 

99 

20 

min 

14 

SΕ1 

Sensor offset 

-9.9 

+15.5 

°C/°F 

15 

nU1

 

(not in use) 

16 

tdS 

Time delay for refreshing the temperature indication on screen

 

20 

sec 

17 

C_F 

Temperature measurement unit: toggling between °C/°F do not adjust the SPo automatically, it must be changed by the user 

0 = °C / 1 = °F 

0=°C 

°C/°F 

18 

Ηοd 

Countdown timer when the relay is in heating mode with countdown, adjust also parameter 

rHC = 2

 

255 

min 

19 

trE 

Response time of the device on network 

100 

40 

msec 

20 

dHL 

Time delay in activating “AΗi”, “ΑLo”

 

and the buzzer among them. 

 

This setting does not apply to sensor failure “LF1” and door alarm “dor”.

 

99 

min 

21 

UF 

(not in use) 

22 

ΑLo 

Low alarm room threshold 

-50.0 

+110 

-4.0 

°C/°F 

23 

ΑHi 

High alarm room threshold 

-50.0 

+110 

+15.0 

°C/°F 

24 

dor 

Door switch operation 

0=OFF / 1 = NC (normally close) / 2 = NO (normally open) 

In heating mode, the door switch is deactivated.

 

0=OFF 

25 

tdH 

Time delay in activating the high temperature alarm “AHi” after defrost. 

During deFrost, the alarm “AHi” is deactivated.

 

255 

sec 

26 

dEd 

Time delay when the doors open, for the deactivation of the compressor and the activation of open door alarm “dor” 

When the door closes, the compressor starts to operate and the alarm disappears.

 

99 

min 

27 

rHC 

Relay operation, where 0 = cooling / 1 = heating / 2 = heating with countdown based on timer 

Hod

 

0=cooling 

28 

dEC 

Temperature indication as integer or decimal, where 0 = integer / 1 = decimal

 

1=decimal 

29 

Add 

Device address on network. To connect with Mini Logger enter 

Add=1

.

 

255 

30 

Sen 

Sensor type NTC/PTC

 

0 = PTC / 1 = NTC 

1=NTC 

 

ALARM TABLE 

LF1 

Sensor malfunction

 

ΑLo 

Low room temperature 

ΑHi 

High room temperature 

dοr 

Open door alarm

 

EEr 

Error in memory RAM: re-enter the SPo (see ADJUSTING TEMPERATURE – SET POINT back page) 

The alarms are automatically deactivated when the cause of the alarm disappears.

 

 

Made in Greece. 

The device is under two year’s guarantee. The guarantee is valid only if the manual instructions have been applied. The control and service of the device must be done by an authorized technician. 

The guarantee covers only the replacement or the service of the device. KIOUR preserves the right to adjust its products without further notice. 

392 Mesogeion Avenue Agia Paraskevi 153 41 Τ: 210 6533730 F: 210 6546331  [email protected]  www.kiour.com

 

V1.0.190719

 

 