FOOD DRYING APPLICATIONS (e.g. SAUSAGES) - HEATING MODE WITH COUNTDOWN
When the parameter
rHC = 2,
the relay operates in heating mode based on the parameter
Hod
while “
SET”
is displayed. By pressing
the relay is activated and the
indication “
rUn
” is displayed. By pressing
the remaining time is displayed. When timeρ elapses, the relay is deactivated and “
End
” is displayed on screen. By pressing
again, the procedure starts over. The thermostat constantly controls the relay based on the adjusted Set Point (SPo). If
SPo
changes during “
rUn
”, automatically the
control of the relay is adjusted. If timer “
Hod
” changes during “
rUn
” mode, it will not change until the next running cycle.
ATTENTION
: according to safety standards, the device must be properly positioned and protected from any contact with electrical parts. The device must be fastened in such a way that it cannot
be removed without the use of tools. Disconnect the main safety switch of the installation before proceeding to any maintenance. Disconnect the power supply of the device before proceeding to
any maintenance. Do not place the device near heat sources, equipment containing strong magnets, in areas affected by direct sunlight or rain. Prevent electrostatic discharges and sharp objects
from been inserted to the device. Separate signal cables from power supply cables to prevent electromagnetic disorders. Signal cables must never be in the same pipe with the power supply cables.
ATTENTION
: Read carefully the technical specifications and make sure that the working conditions are appropriate. According to safety standards, the device must be fastened in such a way that
it cannot be removed without the use of tools.
Dimensions are in mm. The device is mounted on panel hole with cut 29x71mm and restrained with plastic side brackets.
PARAMETER TABLE
#
description
min
max
VD1F
UOM
1
SΡo
SET POINT: room temperature setting
LSP
HSP
2.0
°C/°F
2
LSP
Lower setting limit of SPo
-50.0
HSP
-2.0
°C/°F
3
HSP
Maximum setting limit of SPo
LSP
+110
8.0
°C/°F
4
diF
Differential of room temperature SPo (thermostat delay)
0.1
25.0
3.0
°C/°F
5
Cod
Access code to the following parameters Cod = 22.
0
255
0
-
6
Co1
Compressor’s minimum time OFF
0
4
0
min
7
CF3
Compressor’s operation in case of sensor’s malfunction (LF1) and in cooling mode:
0 = 40% compressor’s operation (3min ΟΝ, 4min OFF) / 1 = compressor is ΟΝ continuously.
In heating mode the relay is deactivated.
0
1
0
-
8
dFr
Time between two successive defrost
: where dFr = 0 or relay in heating mode, the defrost is deactivated.
0
50
6
hours
9
dd2
Defrost duration
(manual and automatic)
1
90
18
min
10
dE5
Defrost end temperature is the room temperature
Automatic defrost stops if room temperature is greater than defrost end temperature dE5.
Manual defrost starts regardless of the room’s temperature and ends after time adjusted in parameter dd2 elapses.
0
25.0
10.0
°C/°F
11
CAb
(not in use)
-
-
-
-
12
dP3
Dripping timer, where the compressor is OFF after defrost
0
10
0
min
13
dY4
Display indication during defrost
0 = indication of room’s temperature
1 to 40 min = indication of “dFr” from 1 to 40 min counting from the beginning of defrost
0
99
20
min
14
SΕ1
Sensor offset
-9.9
+15.5
0
°C/°F
15
nU1
(not in use)
-
-
-
-
16
tdS
Time delay for refreshing the temperature indication on screen
0
20
0
sec
17
C_F
Temperature measurement unit: toggling between °C/°F do not adjust the SPo automatically, it must be changed by the user
0 = °C / 1 = °F
0
1
0=°C
°C/°F
18
Ηοd
Countdown timer when the relay is in heating mode with countdown, adjust also parameter
rHC = 2
1
255
1
min
19
trE
Response time of the device on network
5
100
40
msec
20
dHL
Time delay in activating “AΗi”, “ΑLo”
and the buzzer among them.
This setting does not apply to sensor failure “LF1” and door alarm “dor”.
0
99
0
min
21
UF
(not in use)
-
-
-
-
22
ΑLo
Low alarm room threshold
-50.0
+110
-4.0
°C/°F
23
ΑHi
High alarm room threshold
-50.0
+110
+15.0
°C/°F
24
dor
Door switch operation
0=OFF / 1 = NC (normally close) / 2 = NO (normally open)
In heating mode, the door switch is deactivated.
0
2
0=OFF
-
25
tdH
Time delay in activating the high temperature alarm “AHi” after defrost.
During deFrost, the alarm “AHi” is deactivated.
1
255
1
sec
26
dEd
Time delay when the doors open, for the deactivation of the compressor and the activation of open door alarm “dor”
When the door closes, the compressor starts to operate and the alarm disappears.
0
99
0
min
27
rHC
Relay operation, where 0 = cooling / 1 = heating / 2 = heating with countdown based on timer
Hod
0
2
0=cooling
-
28
dEC
Temperature indication as integer or decimal, where 0 = integer / 1 = decimal
0
1
1=decimal
-
29
Add
Device address on network. To connect with Mini Logger enter
Add=1
.
0
255
1
-
30
Sen
Sensor type NTC/PTC
0 = PTC / 1 = NTC
0
1
1=NTC
-
ALARM TABLE
1
LF1
Sensor malfunction
2
ΑLo
Low room temperature
3
ΑHi
High room temperature
4
dοr
Open door alarm
5
EEr
Error in memory RAM: re-enter the SPo (see ADJUSTING TEMPERATURE – SET POINT back page)
The alarms are automatically deactivated when the cause of the alarm disappears.
Made in Greece.