PARAMETER TABLE 
 # 

code 

description 

min 

max 

RSD 

UOM 

SΡo 

SET POINT: temperature control room

 

SLo 

SHi 

0.0 

°C/°F 

ALo 

lower alarm limit temperature of the room

 

-50 

AHi 

-4.0 

°C/°F 

AΗi 

higher alarm limit temperature of the room

 

ALo 

+150 

15.0 

°C/°F 

dFr 

deFrost repetition time in hours 

12 

Cod 

code to enter parameter’s menu = “22
with Cod=1 and exit the menu 

 back to factory settings 

255 

diF 

differential operating temperature of SPo

 

0.1 

25.0 

3.0 

°C/°F 

CFA 

In case of sensor’s malfunction (LF1), the compressor operates as follows:  
0 = 40% compressor’s operation (3min ΟΝ, 4min OFF),  
1 = 100% compressor’s operation (ΟΝ continuously). 

Crt 

minimum pause time of the compressor

 

min 

dti 

maximum duration of deFrost

 

90 

25 

min 

10 

dLΕ 

Temperature limit of deFrost: above this temperature the automatic deFrost stops and it is not possible to 
start the procedure again manually.  
Manual deFrost lasts 20 min and does not stop based on “dLE” temperature limit. 

0.0 

25.5 

10.0 

°C/°F 

11 

doP 

type of deFrost: compressor OFF 

(not programmable)

 

12 

dri 

dripping time, in which the compressor remains OFF after deFrost ends

 

10 

min 

13 

tdF 

During deFrost the indication “dFr” is displayed, where: 0 = the room’s temperature is displayed during defrost.

 

99 

20 

min 

14 

ΑJ1 

zero adjustment of temperature sensor

 

-9.9 

+15.5 

0.0 

°C/°F 

15 

ΑJ2 

(not in use)

 

 

 

0.0 

 

16 

tSd 

time delay for refreshing the temperature indication on screen

 

20 

sec 

17 

F_C

 

switch °C/°F (0=°C, 1=°F) ATTENTION: changes between °C/°F do not apply on SPo

 

°C/°F 

18 

brA

 

baud rate (9600mbps)

 

19 

trE

 

time response of the device to the CAMIN network

 

100 

20 

msec 

20 

FFu

 

Fan’s relay operation (1=ON continuously, 0=ON when the compressor is ON). The fan operates during deFrost.

 

21 

UFu

 

serial input operating mode, where 0 = operates with the network and the serial key,1 = connects with an 
external device for exporting alarms. ATTENTION: if the value in 
“Add” parameter is ≠ 0, then the “Ufu” is programmed automatically to 0. 

22 

SLo

 

minimum temperature limit of SPo

 

-50 

SHi 

0.0 

°C/°F 

23 

SΗi

 

maximum temperature limit of SPo. 

SLo 

+150 

+8.0 

°C/°F 

24 

Odo

 

Door input polarity (0=OFF, 1=ON with ΝΟ contact, 2=ΟΝ with NC contact). When the door opens, the fan 
turns OFF immediately.   

25 

At2

 

Start delay time alarm, where: 
0 = activate immediately, 
1 ÷ 120 min = the alarm is activated after the selected minutes. 
For sensor and door failure alarms, the above rules do not apply.

 

120 

20 

min 

26 

U3

 

(not in use)

 

27 

U4

 

(not in use)

 

28 

U5

 

(not in use)

 

29 

Add

 

address of the device in the CAMIN network

 

255 

 

 
 

 

 

 

 Made in Greece. 

 

 
 
 
 
ATTENTION according to safety standards, the device must be properly positioned and protected from any contact with electrical parts. All parts that provide protection must 
be fastened in such a way that they cannot be removed without the use of tools. ATTENTION: disconnect the power supply of the device before proceeding to any kind of 
maintenance. ATTENTION: do not place the device near heat sources, equipment containing strong magnets, in areas affected by direct sunlight or rain. ATTENTION: 
prevent electrostatic discharges at the side slots of the device and sharp objects from been inserted. ATTENTION: separate the signal's cables from the power supply's 
cables to prevent electromagnetic disorders.

 

Signal cables must never be in the same pipe with the power supply cables. Use the device only as described in this 

document, not to use itself as a security device. The device must be disposed of in accordance with local standards for the collection of electrical and electronic 
equipment. Read and keep these instructions. 
The device is under two year's guarantee of good operation. The guarantee is valid only if the manual instructions have 
been applied. The control and service of the device must be done by an authorized technician. The guarantee covers only the replacement or the service of the device. 
 

 preserves the right to adjust its products without further notice. 

 

392 Mesogeion Avenue 153 41 Τ:+30 210 6533730 F:+30 210 6546331 [email protected] www.kiour.com

 

V1.1.230518

 

 

ALARM TABLE 

LF1 

cabinet sensor malfunction

 

ΑLo 

alarm low temperature in the cabinet

 

ΑHi 

alarm high temperature in the cabinet

 

dοr  open door alarm ( if the door is open more than 2min the alarm is activated and the compressor stops) 

The alarms are automatically deactivated when the cause of the alarm disappears.

 