MQVL60 / MQVLBG60
VENTED CHASE REQUIREMENTS
FIREPLACE CHASE MUST BE VENTED AT TOP AND BOTTOM
- Minimum
200 square inches free air opening at the top of the chase, and minimum 102
square inches free air opening at the bottom of the chase.
Platform must have minimum 550 Square inches free air opening.
Chase Vent Openings LARGER than the required minimums ARE allowed and
will reduce surface temperatures.
HEAT CANNOT BE DISCHARGED INTO THE WALLS, FLOOR, OR CEILING.
Heat must exit through the required vented chase opening near the ceiling.
ELECTRICAL WIRES IN CHASE MUST BE
PROPERLY ATTACHED TO INSIDE WALL OF
CHASE. DO NOT RUN WIRES ABOVE
APPLIANCE.
Please follow the current CSA C22.1 Canadian
Electrical Code or the National Electrical Code;
ANSI/NFPA 70 when installed in the United
States.
If using insulation in vented chase (i.e. for outside wall), wall board / drywall is required to support all insulation.
Vented chase must be clean and free of all debris (i.e. loose insulation, pieces of wood, etc.)
-Framing for Vented Chase with Grills-
MQVL60 / MQVLBG60
-Framing for Vented Chase with Openings - No Grills-
102
Sq. In.
Air Option
Fireplace Support must be
open to allow air to flow
through fireplace.
Uses Kingsman
VL60EG Front Grill,
VL60EGS Side Grills,
Or Grill with
Minimum
220
Sq. In.
Free Air Equivalent
Required
Minimum
102
Sq. In. Free Air
Fireplace Support must be
open to allow air to flow
through fireplace.
Ceiling
Ceiling
102
Sq. In.
Air Option
Optional –
Secondary
Vent can be added
Required
Minimum
102
Sq. In. Free Air
Required
Minimum 102
Sq. In. Free Air
102
Sq. In.
Air Option
Required
Minimum
200
Sq. In. Free
Air in Sides or
Front
102
Sq. In.
Air Option
Required
Minimum
102
Sq. In. Free Air
*
This area must
be open -
MIN 550 Sq. In.
Grill with
Min
220
Sq. In.
Must be in the
same Pressure
Zone
(Room / Area)
This area must
be open -
MIN 550 Sq. In.
*
Ceiling
Flush or 3/4”
MAX
from top
of Chase
Optional Adjustable Vented Platform (VL60AVP)
Optional –
Secondary
Vent can be added
Min
200
Sq. In.
Must be in the
same Pressure
Zone
(Room / Area)
Can be vented at Side, Front, or Rear. MIN 220 Sq. In. Grill
Required
Minimum
200
Sq. In. Free
Air in Sides or
Front
Can be vented at Side, Front, or Rear. MIN 200 Sq. In. Opening
Front or Sides
Front or Sides
Front or Sides
Front or Sides
Flush or 3/4”
MAX
from top
of Chase
Uses Kingsman
VL60EG Front Grill,
VL60EGS Side Grills,
Or Grill with
Minimum
220
Sq. In.
Free Air Equivalent
11