General Vent Installation Information
Installation Of Side Wall Venting
1. The minimum distance from the bottom of fireplace to centre of vent is 34 inch (85 cm) (See
Figure 1). Cut a hole through the wall allowing for a 11” x 11” (inside diameter) in combustible
walls for wall thimble or an 8” diameter hole in a non-combustible wall (See Figure 2).
2. Note clearance to combustible as stated on pages 7 & 8.
3. Select the approximate vent length, precise measurements are not needed as your flex pipe
can be expanded to twice its shipped length for ease of installation.
4. To install wall thimble centre over 11” x 11” (inch) framing from both sides of wall and secure.
Route flex vent pipe through wall thimble (See Figure 1).
5. Before joining pipes, apply a bead of high temperature sealant (Mill Pac) to end of pipe. First
attach the four inch (4”) flue pipe to the vent termination with sealant, and secure with the four
screws provided. At this time make sure the spacer springs are attached to the (4”) flex pipe as
required. Then attach the seven inch (7”) pipe by the same method.
6. Mount vent termination and seal to wall using caulking around the wall thimble to weather
proof. After installing the vent termination, double check to make sure the pipe extends proper-
ly through wall thimble and into vent termination.
7. Before joining pipes to fireplace flue, apply a bead of high temperature sealant (Mill Pac) to end
of pipe. First attach the four inch (4”) flue pipe to fireplace with sealant, and secure with the
four screws provided. At this time verify that the spacer springs are attached properly to the
(4”) flex pipe as required. Then attach the seven inch (7”) pipe by the same method.
8. Support horizontal pipes every two (2) feet (61 cm) with metal strap bands. Re-check fireplace to make
sure it is levelled and properly positioned and secured.
9. Support vertical pipes to maintain a minimum of 1” or greater clearance to combustibles with metal
strapping bands.
10. If finishing the outside wall with vinyl or wood siding it is recommended that a Siding Shield be installed,
Part Number ZDVSSLR.
Note: Vent Termination must not be recessed into wall or siding.
Note: Wall Thimbles
cover com-
bustible wall up
to 11” thick.
FIG. 1
RIGID OR HARD PIPE
When using Simpson Duravent, AmeriVent pipe, ICC Excel Direct, Metal Fab Sure-Seal DV and or
Selkirk Direct Temp a Duravent hardpipe adapter must be used (
part # ZDVDFA for fireplaces and part #
ZDVDKA for Stoves, Serenity and ZDV3624B
). Follow installation instructions provided by Simpson
Duravent/AmeriVent/Selkirk Direct Temp, ICC Excel Direct, Metal Fab Sure-Seal DV for installation of
pipe and adhere to the clearance to combustibles provided in this manual. Apply a bead of Mill Pac high
temp sealant to all joints of pipes, adapters and termination, when using Kingsman Flex(Z-Flex)Venting
venting and Simpson Duravent venting.
NOTE:
Increase framing depth by one inch when using hardpipe.
Flex Pipe Venting
Kingsman Flex pipe is shipped in unexpanded length. When installing pipe expand the lengths. Pipe can be
expanded to twice their lengths e.g. 4ft. to 8ft. Fully expand pipe and cut off excess.
Do not use more than 2 couplers to extend short pipes. Single sections are preferred in an installation
attaching at the fireplace and termination.
Place the spring spaces provided approximately every two feet to stabilize 4” flex in the center of 7” flex.
When forming bends place spring in bend or before and after. (See Fig. 1).
Horizontal runs require support metal straps every 2 feet. In off set installation support straps should be
used to stabilize pipe.
Expand 4” and 7” flex pipe to the point that the 7” protrudes approximately 2 to 3 inches past outer wall and the
4” flex protrudes approximately 2 to 3 inches past the 7” flex. See Fig. 1. Attach the 4” pipe to the termination
first and secure with sealant and four screws then attach the 7” flex to the termination with caulking and four
screws. Termination may then be moved back to the outer wall and attached to home screwing into the fram-
ing. Silicone around termination to waterproof. If siding shield is going to be used attach this using same
attaching hole as the top of termination after termination has been caulked for water proofing.
Use Hi Temp Sealant
Apply a bead of mill pac high temp sealant to all joints and use four screws to secure each pipe at fireplace,
termination and any joint if joining any sections of pipe.
NOTE:
It is critical to the proper and safe operation
of this fireplace that on all connections the inner
liner and the outer casing are both caulked with lib-
eral amounts of sealant. Do not use any kind of
tape or silicone other than that recommended in
this manual, Mill Pac Sealant
FRAMING DIMENSION
Combustible Wall
Cut a 11” hole through exterior wall and frame as
shown below.
Non combustible Wall
Cut or drill 8” or 204mm diameter hole.
OPTIONAL
CLAMPS
FIGURE 1
MAX. DISTANCE BETWEEN SPACERS 2 FEET
SPRING SPACERS
OPTIONAL
CLAMPS
SEAL WITH HIGH TEMP. SEALANT
SEAL WITH HIGH TEMP. SEALANT
WARNING:
DO NOT mix parts from different systems unless
stated in the manual.
This gas appliance is approved to be vented either through the side wall or vertically through the roof.
Only Kingsman Flex(Z-Flex)Venting Kits and components
specifically approved and LABELED for this stove may be used
. This appliance is also approved for use with Simpson-Duravent Direct Vent system (Model DV-
GS Series), Ameri-Vent Direct Vent Pipe System, ICC Excel Direct, Metal Fab Sure-Seal DV and Selkirk Direct Temp.
57
Summary of Contents for HBZDV3624
Page 17: ...Fan Installation for HBZDV 36 42 47 17...
Page 31: ...Pilot Shield RSP1 RSP2 Qty 1 Shield Per Kit Back View 1 2 3 4 5 6 SLOTS SLOTS SLOTS SLOTS 31...
Page 41: ...Gas Conversion for Modulator PART C WARNING WARNING 41...
Page 45: ...Configuration 1 Basic manual HI LO and manual ON OFF capabilities 45...
Page 46: ...Receiver Module 584 523 521 221 1001 P221SI Receiver Module 584 523 521 221 1001 P221SI 46...
Page 53: ...Proflame 2 Remote Control 53...
Page 55: ...55...