Kingsman Fireplaces FDV200S Installation Instructions Manual Download Page 47

FDV200S   

 

Vertical Vent Installation 

 

A firestop must be installed on the bottom side of the joists when passing through a ceiling or floor. If an attic insulation shield is to be 
used, a firestop is not required. 

One pair (two) 45° elbows may be used to provide an offset in order to avoid cutting of joists and to clear other obstructions. 

When using 45° elbows, an elbow support is required directly above the highest elbow. 

When installing a bend in a joist area a minimum of 2

” clearance to combustible to the top of bend must be maintained, sides and 

bottom o

f pipe, a 1” clearance to combustibles must be maintained. If running horizontally through an area, a 1” clearance to the top of 

the horizontal pipe must be maintained. 

Maximum vertical height of system should not exceed 45 feet.

 

Spacer springs to be installed on 4" flex pipe every 3 ft. on vertical runs. On 45° elbows or 90° elbows a spacer spring is needed on the 
start of the bend and on the end of bend. 

 

NOTE: You may be required to connect 2 lengths of flex pipe 
together to achieve the desired length. 
The parts are listed below: 
ZDV4FC Flex Connector 4” diameter (needed to join 4” flex 
together) and (4) screws. 

FDVVSK: Vertical Vent Starter Kit 

Starter Kit contains: Attic Insulation Shield, Decorative Ceiling Trim Ring, 
Black Band, brass Band, Roof Support, Spacer Springs (6), Mill Pac. 

FDVVT40 Termination 

ZDV7SC Storm Collar 

ZDVRS Roof Support 

ZDVAAF (Flashing 1/12 to 7/12) c/w Storm Collar 
ZDVAF2 (Flashing 8/12 to 12/12) c/w Storm Collar 
ZDVAF3 (Flashing Flat) c/w Storm Collar 

ZDV48GP Pipe Galvanized (Always needed, used in 
roof support and to support pipe / termination) 

ZDVAIS Attic Insulation Shield (required when passing through attic space) 

FDV48P (7” Diameter x 48”) Black Pipe 
FDV36P 

(7” Diameter x 36”) Black Pipe 

FDV24P 

(7” Diameter x 24”) Black Pipe 

FDV12P 

(7” Diameter x 12”) Black Pipe 

ZDV4FP8 Flex Pipe 4” Diameter (4’ unexpanded to 8’ expanded) 
ZDV

4FP20 Flex Pipe 4” Diameter (10’ unexpanded to 20’ expanded) 

ZDVFS Firestop Spacer (required when passing through floors and ceilings) 

ZDVVOS Offset Support Strapping (needed to support pipe when bending) 

FDV

E45 (7” diameter x 45°) Black Elbow 

FDVE90 (7” diameter x 90°) Black Elbow 

ZDV

4SS Spring 4” Standoff Spacer (Used for spacing off 4” flex from 7” black pipe) 

This would be a 3/12 Pitch 

12” Rule 

Level 

Roof 

3” 

Adjustable Clamp 

2 self-tapping screws 

3 self-tapping screws to 
secure rigid pipe and 
termination 

Rigid Pipe 

Roof Support 

Vertical Venting in Cold Climates 

In cold climate conditions where temperatures go below -10°C [14°F], we recommend that the chase be insulated and where the 
vent pipe enters into the attic space that the pipe be wrapped with an insulated Mylar sleeve. This will increase the temperature of 
the vent and help the appliance to vent properly in cold weather conditions. 

It is also important in vertical vented direct vent appliances that the appliance be operated daily during the winter months as this will 
help stop the Termination from freezing up. We recommend using a thermostat set at room temperature to allow the unit to cycle. 
For IPI models it may be necessary to set the appliance to Standing Pilot mode to maintain heat in the cavity. The purpose of this 
procedure is to prevent cold air from penetrating the chimney and then onto the living space. Therefore, when the internal 
temperature is slightly elevated the fireplace is able to freely exhaust its combustion and hence making it easier to startup. 

 
 
An Attic Insulation Shield must be 
installed where the vent passes from 
a lower living space into an attic 
space where the chimney is not 
enclosed. It is designed to keep 
insulation materials away from the 
chimney. 

When installing the Attic Insulation 
Shield where the chimney passes 
from a living space to an attic space, 
install

 the shield from below and 

nail in place using 1" spiral nails. 

18” Min 

24

” Min 

Clearance to perpendicular wall 24 inches  

(60 cm). (Recommended to prevent re-

circulation of exhaust products. For additional 

requirements check local codes.) 

 

Clearance above highest point 

of exit on roof 18 inches (45cm). 

47

Summary of Contents for FDV200S

Page 1: ...y or the gas supplier Installation Instructions This appliance may be installed in an aftermarket permanently located manufactured home USA only or mobile home where not prohibited by local codes This...

Page 2: ...t Part B series 0190XYZ 21 Gas Conversion for Modulator PART C 22 Millivolt System Lighting and Burner Control 23 Electronic Ignition Lighting Instructions 24 Troubleshooting the Gas Control System 25...

Page 3: ...PARTS LIST FDV200S Parts List 48 49 WARRANTY Glass Safety Termination Cap Safety 50 Limited Lifetime Warranty 51 3...

Page 4: ...Top Hooks into Top Slots 3 Engage Bottom Hooks into Bottom Slots Top Slot Bottom Hook Top Hook To remove Safety Screen Wait Until Fireplace is Completely Cool and reverse these steps Bottom Hook Top H...

Page 5: ...sounds produced by a furnace or heating duct This noise does not affect the operation or longevity of your fireplace It is also normal for the fan to make some noise when it comes on This noise can be...

Page 6: ...condition of vent and vent terminal for sooting or obstruction and correct if present 6 Vacuum and clean any debris in the firebox that is not supposed to be there 7 Test and measure the flame failure...

Page 7: ...due to excessive lint from carpeting bedding material et cetera It is imperative that control compartments burners and circulating air passageways of the appliance be kept clean Make sure that the ga...

Page 8: ...ication plate shall be mounted at the exterior of the building four feet directly above the location of vent terminal The plate shall be of sufficient size to be easily read from a distance of eight f...

Page 9: ...IN MANUFACTURED MOBILE HOMES IN CANADA Please follow the current ANSI NFPA 70 National Electrical Code in the USA and CAN CSA C22 1 Canadian National Electrical Code in Canada An appliance must be gro...

Page 10: ...rotection being required This unit has been tested in an Alcove Minimum Dimensions of Alcove are as follows Depth 30 Height 55 5 Width 52 5 THE FOLLOWING MINIMUM DISTANCES TO COMBUSTIBLES MUST BE OBSE...

Page 11: ...Remote Receiver Battery Backup Remote Receiver Battery Backup Piezo Igniter Piezo Igniter Valve Valve Valve Battery Backup Battery Backup Fan Speed Control Fan Speed Control Fan Speed Control Proflame...

Page 12: ...y remove the Rear Tabs from the unit To Install Component Cover Hook the Rear Tabs over the back of the Component Tray Next attach front of Component Cover with 2 DT screws WARNING Wait until unit is...

Page 13: ...FDV200S Optional Fan Installation Part F45FK 13...

Page 14: ...rounding plug for your protection against shock hazard and should be plugged directly into a properly grounded three prong receptacle Label all wires prior to disconnection when servicing controls Wir...

Page 15: ...oval diagram 2 Place Back Brick Panel up to rear of firebox leaving bottom of panel slightly forward for support 3 Remove left and right Brick Clips using a 1 4 nut driver Do not discard Brick Clips 4...

Page 16: ...Tabs 3A and 3B Do not place Log 3 on top of Locating Tabs Step 4 Place Log 4 onto notched areas of Log 1 and Log 3 Step 5 Place Log 5 up against the 2nd Grate Bar from the left as shown Step 6 Place G...

Page 17: ...Door and Glass Information FDV200S Safety Screen Frame Assembly Glass Front Door Assembly Screw Screw 17...

Page 18: ...olated from the gas supply piping system by closing its individual shutoff valve during any pressure testing of the gas sup ply piping system at test pressures equal to or less than 1 2 PSIG 3 5 KPa G...

Page 19: ...ription Pilot Orifice Burner Orifice Brass 1000 255 Brass Nipple Air Shutter Hi Lo Regulator 200DV CKLP FDV200SLP Propane Conversion Millivolt 1001 P167SI 30 977 167 1 16 1000 253 closed Full Open 100...

Page 20: ...to convert the valve from one type of fuel to the other Step 8 Check for gas leaks around the pilot burner tube and face of valve Step 9 Attach conversion label to label plate on bottom of unit writi...

Page 21: ...njector near the top Propane injectors have a groove machined around their circumference near the top while NG injectors do not have a groove fig 4 Refer to the Appliance Manufacturer s instruction sh...

Page 22: ...Gas Conversion for Modulator PART C 22...

Page 23: ...ly the pilot burner located on the rear center left hand side of the main burner If a flame has appeared then continue to depress the control knob for 20 seconds If the flame did not appear then conti...

Page 24: ...all electric power to the appliance 4 This appliance is equipped with an ignition device which automatically lights the pilot Do not try to light the pilot by hand 5 Wait five 5 minutes to clear out...

Page 25: ...as valve Should read 325 millivolts minimum while holding valve knob depressed in pilot position and wall switch off Replace faulty generator if reading is below specified minimum Plugged burner orifi...

Page 26: ...13 1002 P033SI TC Pilot Burner IPI Assembled NG 199 033 14 1002 P047SI TC Pilot Burner IPI Assembled LP 199 047 15 1001 P166SI TC Orifice Pilot NG 977 166 62 IPI 16 1001 P168SI TC Orifice Pilot LP 977...

Page 27: ...s required The following sequence must be followed to reset the PF2 Module Press the Red SW1 button until you hear three beeps Within 10 seconds press the SW1 button again until you hear it beep The P...

Page 28: ...the main burner has been cycled ON OFF and the pilot is also out follow the procedures described in this manual to light the pilot To switch from IPI to CPI Mode 1 Turn the fireplace OFF using the ON...

Page 29: ...Proflame 2 Remote Control 29...

Page 30: ...Note When Smart Thermostat is activated manual flame height adjustment is disabled Note This function is only available in Room Thermostat or Smart Thermostat Control Mode Halogen lights only 30...

Page 31: ...iring Diagram For use with all Kingsman manufactured IPI Proflame 2 models for all types of gas noted on rating plate Supply 120VAC 60Hz 3A 6 volts battery backup Pour utilisation avec tous les mod le...

Page 32: ...ck This component permits the IPI system to operate without the need for an external AC Adapter power source The advantage to using the battery backup is that in the case of a power failure the applia...

Page 33: ...hat the room thermostat is ON and the set temperature is now displayed To adjust the set temperature press the Up or Down Arrow Keys until the desired set temperature is displayed on the LCD screen of...

Page 34: ...P 977 168 35 IPI 11 1002 P012SI IPI Stepper Kit LP 907 012 12 1002 P013SI IPI Stepper Kit NG 907 013 13 1002 P014SI IPI Reg Kit LP Hi Lo 907 014 14 1002 P016SI IPI Reg Kit NG Hi Lo 907 016 15 1002 P01...

Page 35: ...Configuration 1 Basic manual HI LO and manual ON OFF capabilities 35...

Page 36: ...s with remote HI LO capabilities a modulating servo is required to be installed on the valve The connectors to this servo must be connected to the Remote Harness as shown SCHEMATIC PICTURE NOTE Fan Op...

Page 37: ...er Adapter P N 1002 P850si The Remote Receiver IPI or Millivolt system can be powered by the AC Adapter This is advantageous if you do not want to use batteries Simply connect the AC Adapter into the...

Page 38: ...lities Refer to the fan installation removal section for fan installation NOTE Fan Option is not available on some models of fireplace Check with your dealer NOTE This Configuration is not available o...

Page 39: ...3 m horizontally L Clearance above paved sidewalk or paved driveway located on public property 7 ft 2 13 m Notes 2 M Clearance under veranda porch deck or balcony 12 in 30 cm 12 in 30 cm N Where a ve...

Page 40: ...g in bend or before and after See Fig 1 Horizontal runs require support metal straps every 2 feet In offset installation support straps should be used to stabilize pipe Expand 4 and 7 flex pipe to the...

Page 41: ...installed in either the horizontal or vertical runs Minimum clearances on venting 4 to top of elbow 2 1 2 from top of horizontal pipes 1 on all other existing pipes Only trim kit s supplied by the ma...

Page 42: ...m and the number of elbows required 2 Use the Venting Chart to determine the maximum horizontal distance allowed Note For each 45 elbow installed in the horizontal run the length of the horizontal run...

Page 43: ...he pipe extends properly through wall thimble and into vent termination 7 Before joining pipes to fireplace flue apply a bead of high temperature sealant Mill Pac to end of pipe First attach the four...

Page 44: ...w well is recommended with adequate and proper drainage as per local codes Leave 2 clearance below snorkel to prevent water from entering the Snorkel Termination Do not enclose the Snorkel within a wa...

Page 45: ...VENTING AIR INTAKE PLATE ADJUSTMENT NOTE Unit comes preset for vertical venting under 15 feet Follow these instructions when venting exceeds 15 feet vertical 1 Locate the 3 x 1 4 hex screws and using...

Page 46: ...f pitch card Slide a Roof Flashing suitable to your roof slope over the vent Place the edge of the flashing plate that will be on the higher part of the roof slope under the shingles Both the sides an...

Page 47: ...anded to 20 expanded ZDVFS Firestop Spacer required when passing through floors and ceilings ZDVVOS Offset Support Strapping needed to support pipe when bending FDVE45 7 diameter x 45 Black Elbow FDVE...

Page 48: ...lve Nova LP Hi Lo 0820651 1001 P634SI Valve Nova NG Hi Lo 0820652 1001 P713SI Pilot Burner LP 199 713 TC SIT 1001 P714SI Pilot Burner NG 199 714 TC SIT 1000 214 Piezo Igniter 1244 17 Mark21 1001 P144S...

Page 49: ...ains Horizontal Vent Termination Zero Clearance Wall Sleeve Black Wall Trim Ring 7 Dia Black Pipe 24 Length 7 Dia Black Pipe 48 Length 7 90 Degree Black Elbow 4 Flex 48 Unexpanded 96 Expanded 7 Black...

Page 50: ...eep toddlers young children and other at risk individuals out of the room and away from hot surfaces Do not leave the fireplace remote control where it is accessible to children Termination Cap Safety...

Page 51: ...hemicals other than in a normal residential environment c damages caused by any unauthorized alteration or repair of the unit affecting its stability or performance d damages caused by improper matchi...

Reviews: