background image

USSC 

11

10 

USSC

In

st

alla

tio

n

PRIMAR

Y

 FURNACE

">;^

`

;;>K^>"

When installed as a secondary furnace, it may only be connected to the ductwork of the existing primary furnace (Gas, 

Electric, etc.). It should not be wired in conjunction with the existing furnace’

s circuitry

A

 Duct Damper must be installed 

between the air discharge of the 8500 furnace and the primary furnace.  

This duct damper prevents the air of the pri-

 

 

<"

 

<

‡

ˆ

a simple closure switch to determine if the damper is opened or closed.  

The damper will connect to the 8500’

s printed 

circuit board (PCB) as a signal connection only

.  See wiring diagram in this manual. 

The PCB will not supply power to 

   #

+@# +

CAUTION: Do not connect your furnace’

s ductwork to the cold air return duct of your existing furnace because a pos-

sibility exists of components of the central furnace overheating and causing it to operate other than intended. Only con-

"  

In

st

alla

tio

n

THROUGH THE W

ALL

 INST

ALLA

TION

 

(RECOMMENDED INST

ALLA

TION)

T

o

 vent the unit through the wall, connect the pipe adapter to the exhaust motor adapter

. If the exhaust adapter is at least 

24-inches above ground level, a straight section of pellet vent pipe can be used through the wall.

Y

our furnace dealer should be able to provide you with an installation kit, which will 

include a wall thimble that will allow 

the proper clearance through a combustible wall. Once outside the structure, a 3-inch clearance should be maintained 

from the outside wall and a clean out tee should be placed on the pipe with a 90-degree turn away from the house.  

At 

this point, a 3-foot (minimum) vertical section of pipe should be added with a horizontal cap, which would complete the 

installation.

A

 support bracket should be placed just below the termination cap or one every 4-feet to make the system more stable. 

If you live in an area that has heavy snowfall, it is recommended that the installation be taller than 3-feet to get above the 

snowdrift line. 

This same installation can be used if yo

ur furnace 

is below ground level by simply adding the clean-out 

section and vertical pipe inside until ground level is reached. With this installation you have to be aware of the snowdrift 

line, dead grass, and leaves.  W

e

 recommend a 3-foot minimum vertical rise on the inside or outside of the house.

=

?

deck, in an alcove, under a window

, or between two windows.  W

e

 recommend Simpson Dura-V

ent

®

 or Metal-Fab

®

 kits.

THROUGH THE ROOF/CEILING INST

ALLA

TION

When venting the furnace through the ceiling, the pipe is connected in the same manner as a wall installation, except 

the clean-out tee is always on the inside of the house, and a 3-inch adapter is placed in front of the clean-out tee. 

{

 

‡

<

 “

 

manufacturer

’s

 directions).  It is important to note that if your vertical run of pipe is more than 15-feet, the pellet vent 

pipe size should be increased to 4-inches in diameter

.  

Do not exceed more than 4-feet of pipe on a horizontal run and use as few elbows as possible.  If an of

fset is required, 

it is better to install 45-degree elbows rather than 90-degree elbows.

1 V

ertical 

Cap

2 Storm 

Collar

Adjustable Roof Flashing

Cathedral Ceiling Support Box

5 Pipe

6 45° 

Elbow

7 90° 

Elbow

8 Horizontal 

Cap

9 W

all 

Thimble

10 

Black Ceiling Support Firestop Spacer

1

1

 

Single 

T

ee with Clean-Out 

Adapter

12 

T

ee Support Bracket

13 

Double 

T

ee with Clean-Out 

Adapter

This appliance requires the installation of a cold air return duct system. 

The return air will provide a better distribution 

 !"  

CAUTION: MAINT

AIN COMBUSTION 

AIR SUPPL

Y

 T

O

 BOTH FURNACES, 

AIR ST

AR

V

A

TION  IS DANGEROUS. 

OPERA

TE 

THE EXISTING FURNACE 

PERIODICALL

Y

 T

O

 ENSURE THA

T

 IT

 

WILL

 OPERA

TE SA

TISF

ACT

ORIL

Y

WHEN NEEDED.

DO NOT

 RELOCA

TE OR BYP

ASS 

ANY

 

OF 

THE SAFETY

 CONTROLS IN 

THE 

EXISTING FURNACE INST

ALLA

TION.

REFER T

O

 THE 

MANUF

ACTURER’S 

INSTRUCTIONS OF 

YOUR EXISTING 

FURNACE.

DO NOT

 USE DUCT

 ELBOWS HA

V

-

ING 

AN INSIDE RADIUS OF LESS 

THAN 150mm (6 in.).

DO NOT

 CONNECT

 

T

O

 

A

 DOWN 

FLOW FURNACE.

@+@

K@\&

*

THA

T

 A

 REVERSE FLOW IS POSSIBLE.

This appliance must be installed by 

experienced personnel and in accor-

dance with the instructions of the man-

ufacturer and in a manner acceptable 

to the authority having jurisdiction. 

When required by the authority having 

jurisdiction, such personnel must be 

licensed  to perform this service.

 

 

the use of a return air system unless 

#+

Summary of Contents for 8500

Page 1: ...E 800 750 2723 FAX 423 837 2109 UNITED STATES STOVE COMPANY Keeping North America Warm Since 1869 MULTI FUEL FURNACE MODEL 8500 Report 215 S 22b 2 TESTED LISTED BY PORTLAND OREGON USA Part No 851976 Safety tested and listed to UL 391 2010 ASTM E1509 04 and CSA B366 1 11 C residential or mobile home as a stand alone or add on furnace ductwork connection only Approved for US and Canadian use French ...

Page 2: ...ype 8 Pellet Vent Installation 8 Pellet Vent Termination 8 Vent Termination Clearances 9 Through the Wall Installation 10 Through the Roof Ceiling Installation 10 Primary and Secondary Furnace Illustrations 11 OPERATION 12 How Your Furnace Works 12 Damper Control Adjustment 12 Control Panel 13 Unit Preparation 14 Start Up Procedure 14 Shut Down Procedure 14 Daily Operation 15 Safety and Convenienc...

Page 3: ... the fuel supply Store your pellets in a dry place to prevent them from absorbing added moisture To decrease sawdust buildup the hopper will need to be vacuumed out after every 6 8 bags of pellets or more often if the pellets are poor quality You may have to screen sift each bag of pellets if sawdust becomes a problem Z _ _ with small to midsize pellets Low ash content pellets will allow you to bu...

Page 4: ...g cut down on operation time Ì Installation IMPROPER INSTALLATION The manufacturer will not be held responsible for damage caused by the mal function of a furnace due to improper venting or installation Call 800 750 2723 and or consult a professional installer if you have any questions FLOOR PROTECTION K non combustible surface should be large enough to extend a minimum of 6 inches in front 6 inch...

Page 5: ...al vent MUST NOT exceed 4 feet this does not include the clean out tee Use no more than 180 degrees of elbows two 90 degree elbows or two 45 degree and one 90 degree elbow etc to maintain adequate draft PELLET VENT TYPE J K Z connector provided on the back of the furnace use a 3 inch to 4 inch adapter for 4 inch pipe Use 4 inch vent if the vent height is over 12 feet or if the installation is over...

Page 6: ...ut section and vertical pipe inside until ground level is reached With this installation you have to be aware of the snowdrift line dead grass and leaves We recommend a 3 foot minimum vertical rise on the inside or outside of the house deck in an alcove under a window or between two windows We recommend Simpson Dura Vent or Metal Fab kits THROUGH THE ROOF CEILING INSTALLATION When venting the furn...

Page 7: ...the unit has reached operating temperature The room fans will automatically adjust their speed in accordance with the heat range setting By pressing the Room Fan A which is automatic or how many fans are running The z J J for easy removal for cleaning The agitator when in Automatic mode will operate at set intervals However these can J X The Auger Delay button can be used to pause rotation of the ...

Page 8: ...spected and cleaned at least monthly during the burning season Be aware less creosote is deposited and that weekly cleaning can be necessary in mild weather even though monthly cleanings can be enough in the coldest months Check the clean out tees periodically to determine the required cleaning schedule 3 or 4 inch chimney brushes are available for chimney cleaning If the exhaust system or outside...

Page 9: ...e backside of the cleanouts on the front of the unit If gaskets become torn or damaged they must be replaced FAN MOTORS Clean the air holes on the motors of both the draft fan and room air fans annually Remove the draft fan from the exhaust duct and clean out the internal fan blades as part of your fall start up A new gasket may be purchased from United States Stove s Parts Department PAINTED SURF...

Page 10: ...ition Duct 10 Round 1 34 891331 Spring Handle Brushed Nickel 1 35 891364 Hearth Plate 1 36 891374 Access Panel Plenum 1 37 891423 Pin Door Hinge 2 38 891445 Ash Pan Assembly 1 39 891455 Weldment Burnpot 1 40 891461 Cover Exhaust Cleanout 1 41 891471 Lid Weldment 1 42 891440 Cleanout Ash 2 43 891262 1 44 891457 Cleanout Ash Lower 2 45 891485 Weldment Damper 1 46 89586 Auger Nipple 1 47 80501 Thermi...

Page 11: ...tion air Fuel has too much moisture Viewing window becoming black shortly after start up Adjust the air damper to a more open position Use a fuel with less moisture content PROBLEM CAUSE Not enough combustion air Fuel has too much moisture Z chamber Adjust the air damper to a more open position Use a fuel with less moisture content Stove might be cycling excessively due to temperature cut backs Re...

Page 12: ...ce of Purchase Retailer ______________________________________________________ City____________________________________________ State_______ Zip_________________ If internet purchase please list website address___________________________________ Date of Purchase _______________________________________________________________ Reason for Purchase Alternative Heat Main Heat Source Decoration Cost Oth...

Page 13: ...24 USSC CUT HERE CUT HERE Fold Here Fold Here United States Stove Company P O Box 151 South Pittsburg TN 37380 Fold Here PLACE STAMP HERE ...

Reviews: