background image

Page 9 of 22

King Pigeon Hi-Tech. Co., Ltd.

Ver 1.0

GSM/GPRS/3G/4G/Cloud

Network Fault Monitoring Alarm

8.4. Number Settings

Alarm Tel Number:

Set the alarm receiver numbers, please includes the country code, e.g: in China is 0086, input

008613570810254, if cannot received the SMS or dial, then try to set as +8613570810254, but cannot be
8613570810254. Also, some GSM/3G Operators not required input country code, so please remove country code,
e.g. in China is 0086, and China Mobile not required country code, so can set as 13570810254.

Dial:

Tick it stands for enable while alarm, Dial to the authorized numbers.

Timer-Report:

Tick it stands for enable to SMS report to this authorized numbers.

Alarm:

Tick it stands for enable while alarm, send SMS to the authorized numbers

Alarm Recovery:

Tick it stands for enable the SMS notification when the alarm recovery to normal value.

GPRS Failure:

Tick it stands for enable the SMS notification when the GPRS connection failure.

Summary of Contents for RTU5023

Page 1: ... by free phone call or SMS Interval Report Status to Your Mobile Phone by SMS User Manual Ver 1 1 RTU5028E Date Issued 2020 01 07 All rights reserved by King Pigeon Hi Tech Co Ltd www iot solution com GSM GPRS 3G 4G Cloud Network Fault Monitoring Alarm ...

Page 2: ...t RTU5029SA Phase Loss Monitoring Alarm 3 Phase Input 12VDC Output RTU5029SB Phase Loss Monitoring Alarm Single Phase Input 12VDC Output DATE VERSION DESCRIPTION 2019 07 18 Ver 1 0 RTU5028E Origin Version 2020 01 07 Ver 1 1 Optimized configuration software connection This handbook has been designed as a guide to the installation and operation of RTU5029S temperature humidity voltage power Failure ...

Page 3: ... and inquiry by SMS commands Moreover it also can support Modbus RTU Modbus TCP and MQTT protocol to connect to cloud Platform automatic switching to cellular network when the wired network failed then monitor the current status in real time through GSM 3G 4G network RTU502E power failure and network fault monitoring alarm suitable for classrooms public places hospitals stations Food warehouses of...

Page 4: ...lly send its status value to the authorized number Support remotely read 100 historic data via SMS or configuration software Rechargeable backup battery inside can last 6 hours Modular structure design replace a module can upgrade the network from 2G to 3G 4G or 3G to 4G Compatible wall installation and DIN35mm industrial rail installation Support Modbus RTU Modbus TCP and MQTT protocol can be con...

Page 5: ...the light will 2 seconds flick once registered successfully will be on 2s off 1s Flicks quickly means data transmission Power indicator LED ON when connect power otherwise it is OFF Alarm Indicator Alarm will ON Normally is OFF Relay Indicator Relay open will ON Relay close will OFF 6 2 Interface Instruction Protocol Modbus RTU Modbus TCP MQTT Ethernet Port 1 RJ45 Support DHCP dynamic obtain IP or...

Page 6: ...tput no polarity distinction Ethernet 1 RJ45 ANT GSM 3G 4G antenna interface 6 3 Backside Switch Card Slot At the backside of the panel please use the tool to remove the screw and you can see switch button RESET button reset button has the function 1 upgrade press it and switch on the device will enter upgrade state 2 reset press it then hold on 3 seconds in the state of power on will reset and ca...

Page 7: ...to other IP addresses in the same network segment if the device is directly connected to the computer please use a crossover network cable and configure the computer network parameters before connecting the device 8 1 Search Device Search Device Click to search for all terminal devices in the LAN Note that the computer and the device must be on the same network segment in the same LAN and the subn...

Page 8: ...he device will automatically convert to the correct time according to the selected time zone Please select the correct time zone according to the current location of the device If there is no corresponding time zone you can directly enter the difference minute time between current time and the GMT such as the difference between Beijing time and Greenwich Mean Time is 480 minutes then enter 480 SMS...

Page 9: ...equired input country code so please remove country code e g in China is 0086 and China Mobile not required country code so can set as 13570810254 Dial Tick it stands for enable while alarm Dial to the authorized numbers Timer Report Tick it stands for enable to SMS report to this authorized numbers Alarm Tick it stands for enable while alarm send SMS to the authorized numbers Alarm Recovery Tick ...

Page 10: ...false alarm 0 65535s default 2 seconds PING Target Domain Name 1 2 Can set 2 external network domain name or IP Only if unable PING 2 external network IP will alarm PING Target IP Can set 7 IP address When set to 0 0 0 0 or 255 255 255 255 stands for the target IP is empty and the PING test will not be performed Confirm PING failure times settings Can be set 1 255 default is 3 stands for confirm a...

Page 11: ...Settings Cellular Network 0 Disable 1 Enable Cellular network will be enabled when LAN disconnect Connection Mode TCP UDP APN user name user password GPRS parameters of the SIM card if the customer SIM card can not access the internet consult the local network operator and fill in the correct parameters Server Settings Server 1 IP Domain Server Port Primary server address supports 3 protocol 1 Mod...

Page 12: ...then try to reconnect according to Server Offline 3 Times Device Reconnection Time Heartbeat Interval Network keep online heartbeat interval time can be set 0 9999 default is 60 0 stands for will not send MQTT Parameter Settings MQTT username password if need to connect to King Pigeon cloud platform username default is MQTT password default is MQTTPW if connect to your own server set the parameter...

Page 13: ...he units can t return the SMS confirmation in some gsm operators but it can performance the functions correctly Also you can try to add the country code before the number see the below settings For example E g the country code is 0086 or 86 The user cell phone number is 13600000000 and has been assigned as a SMS Alert number the sim card number in the panel is 13512345678 When you setup the number...

Page 14: ...device will automatically convert to the correct time according to the set time zone Command Return SMS Example Setup PWD TZ s x s stands for or x stands for min Set success The minute difference between the time zone of the equipment and Greenwich Mean Time 1 time zone 60 min Eg Device located at Beijing east 8 zone 480 minutes difference from GMT SMS command 1234TZ 480 5 Setup Authorized User nu...

Page 15: ...for internet 9 stands for external power voltage low alarm 10 stands for high alarm y stands for alarm content max 40 characters Eg 1234AINA8Tfault to set internet fault alarm Alarm Content y Inquiry PWD AINA x Setup Recover Content PWD AINN x T y x 1 9 1 7 stands for network device 1 7 8 stands for internet 9 stands for external power y stands for recovery alarm content max 40 characters Eg 1234A...

Page 16: ...umber even answering if without press a key avoid alarm calling is transferred to voicemail leads to user missed alarm reminding Command Return SMS Not continue dialing Default PWD COFF Once anyone answered the device will not call next authorized number if nobody answer will circular dialing for 3 times Set successfully Continue dialing PWD CON After answering the device will continue to call nex...

Page 17: ... Port PWD ETHIP x y x local IP y listening port Used to listen for TCP client connections acquire data via Modbus TCP after connection 1234ETHIP192 168 1 101 1234 to set local IP as 192 168 1 101 port 1234 Local IP x Port y Inquiry PWD ETHIP If delete local IP address the device will automatically obtain IP address through DHCP Delete PWD ETHIPDEL Setup gateway address PWD GATE x x gateway address...

Page 18: ...onnect time after disconnection Command Return SMS Setup PWD RECONT x x60 65535 seconds default is 600 seconds stands for no data is sent within 600 seconds after the device is connected to the server and the server will be automatically disconnected and reconnected to the server Reconnect time x seconds Inquiry PWD RECONT 20 Setup the Login Message Command Return SMS Setup PWD RTP x x stands for ...

Page 19: ...etting that domain name is mqtt my m2m com port is 1883 If want to connect own server pls setup GPRS communication protocol first then setup server parameter 25 Setup Server Parameter Command Return SMS Setup Server1 PWD IP x y Server2 PWD IPB x y x server IP or domain y port range 0 65535 1234IPmodbusrtu kpiiot com 4000 to setup server1 address As modbusrtu kpiiot com 4000 IP x Port y Inquiry Ser...

Page 20: ...fault 1 normal 3 Device 4 status bool 2 0 fault 1 normal 4 Device 5 status bool 2 0 fault 1 normal 5 Device 6 status bool 2 0 fault 1 normal 6 Device 7 status bool 2 0 fault 1 normal 7 Internet status bool 2 0 fault 1 normal 8 External Power status bool 2 0 fault 1 normal 9 Network cable status bool 2 0 fault 1 normal 0 External Power voltage 16bit unsigned int 3 4 Actual Register Value 10 10 2 MQ...

Page 21: ...evice 2 identification addTime 2019 01 02 12 34 56 switcher 1 Switch type data 0 is fault 1 is normal flag DI3 Network device 3 identification addTime 2019 01 02 12 34 56 switcher 1 Switch type data 0 is fault 1 is normal flag DI4 Network device 4 identification addTime 2019 01 02 12 34 56 switcher 1 Switch type data 0 is fault 1 is normal flag DI5 Network device 5 identification addTime 2019 01 0...

Page 22: ...Server Device will subscribe topic towards server before the server can publish message to device for control the DO Device subscribe topic device serial number sensorDatas sensorsId 211267 server sensor identification switcher 0 switch type data 0 is open 1 is close flag DO1 DO identification down down server downlink 11 Warranty 1 This system is warranted to be free of defects in material and wo...

Reviews: