Page 10 of 22
King Pigeon Hi-Tech. Co., Ltd.
Ver 1.0
GSM/GPRS/3G/4G/Cloud
Network Fault Monitoring Alarm
8.5. Alarm Settings
Channel Name:
To setup the channel name.
Threshold High,Threshold Low,Recover content,Alarm content:
The SMS content Can be defined.
High Alarm SMS,Low Alarm SMS:
Once current voltage value higher/lower than threshold value will
send this SMS content to authorized numbers.
Alarm Verify Time:
Stands for delay 2 seconds to confirm alarm or recovery, to prevent false alarm,
(0~65535s),
default 2 seconds.
PING Target Domain Name 1,2:
Can set 2 external network domain name or IP,Only if unable PING 2 external
network IP will alarm.
PING Target IP:
Can set 7 IP address,When set to 0.0.0.0 or 255.255.255.255,stands for the target IP is empty and
the PING test will not be performed.
Confirm PING failure times settings:
Can be set 1~255,default is 3,stands for confirm alarm if PING failure 3 times.
Alarm-link Relay:
Tick it stands for when the network failure, the alarm link the output relay open for 2 seconds, if
the network not recover,it will open for 2 seconds again, if still not recover 5 minutes later,will the last time open
for 2 seconds.