PLC Data acquisition protocol conversion gateway
-D225
The Modbus Poll tool connection configuration is as follows
Operation instructions: (1) Click the "Connect..." of "Connection" to pop up the connection
configuration box, (2) The communication protocol with D225 is: Modbus TCP, (3) Fill in the address
of the D225 device, note: the address should be the same as D225 The [IP address] configuration
of [Network Settings] on the configuration software is the same. (4) Fill in the port number of the
D225 device. Note: The port number must be consistent with the [Port] configuration of the
[protocol parameter] on the configuration software. The port here No. is not the [port number] of
[Service Settings], (5) Other options can be defaulted or modified according to your needs. Click
"OK" to communicate with D225 to collect data on the three-phase meter