SPECIFICATIONS &
ELECTRICAL INFORMATION
Specifications
Outer filter ................................................................................................5 Microns
Inner filter ..................................................................................................1 Micron
Overall dimensions (LxWxH) ............................................................21” x 17” x 11”
Sound rating @ 3ft.....................................................................High speed- 69 dB
............................................................................................Medium speed- 67 dB
....................................................................................................Low speed- 62 dB
Air flow. ................................................................................High speed- 410 CFM
........................................................................................Medium speed- 362 CFM
..............................................................................................Low speed- 260 CFM
Motor....................................................................120V, 60Hz, 1 Phase, 1.0 Amps.
Weight ..........................................................................................................30 lbs.
GROUNDING
This air cleaner must be grounded. If it
should malfunction or breakdown,
grounding provides a path of least
resistance for electric current, to reduce the
risk of electric shock. This air cleaner is
equipped with a cord having an equipment-
grounding conductor and grounding plug.
The plug must be plugged into an
appropriate outlet that is properly installed
and grounded in accordance with all local
codes and ordinances.
WARNING:
TO MAINTAIN PROPER
GROUNDING, DO NOT REMOVE OR
ALTER THE GROUNDING PRONG IN ANY
MANNER.
As received from the factory, your air
cleaner is ready to run on 120V currant.
This air cleaner is intended for use on a
circuit that has an outlet and a plug which
looks like the one illustrated in Fig.1.
A separate electrical circuit should be used
for your tools. This circuit should be no less
than #12 wire and should be protected with
a 20 amp fuse. Make sure the electric
current is of the same characteristics as
stamped on the machine nameplate.
Running on low voltage will damage the
motor.
THERMAL PROTECTOR
This air cleaner is thermally protected. In
the case of an overload the fuse will blow
and will need to be replaced with an
equivalent 2 Amp. fuse.
EXTENSION CORDS
The use of any extension cord will cause
some loss of power. Use the following table
to determine the minimum wire size
(A.W.G-American Wire Gauge) extension
cord needed. Use only extension cords
which accept the tool’s plug.
For circuits that are further away from the
electrical circuit box, the wire size must be
increased proportionately in order to
deliver ample voltage to the motor. Refer to
Fig.2 for wire length and size.
Figure 1
Current
carrying
prongs
Grounded outlet
Grounding
prong
Figure 2
REQUIRED GAUGE
(AWG) 120V LINES
NO.16
NO.16
NO.14
EXTENSION
LENGTH
0-25 Feet
26-50 Feet
51-100 Feet