Power/Speed (POWER):
Regulation from 50% to 100% of the power to the motors.
This parameter will also weigh on the manoeuvre speed.
Delay between the wings in closing (DELAY)
Regulation of the wings during the closing adjustable from 0 to
15 seconds.
Pause time (PAUSE):
Regulation of pause time at the end of the manoeuvre, before the
automatic reclosing from 0 to 90 seconds. The “
AUTO
” dip switch
must be ON.
Obstacle sensitivity (OBSTACLE):
Regulation of intervention time from 0.1 to 3 seconds.
The lower the trimmer is regulated, earlier the central will stop the
automation in case of impact of the wing against an obstacle.
4 - CONTROL UNIT SETTINGS
MAX
MAX
MAX
MAX
!
A change of the DIP 1 “MODE” needs the repetition of the programming procedure.
!
A variation on the setting of “FOR” trimmer (power/speed) requires the repetition of the learning
procedure (point 2), because of the change of the manoeuvre time. The slowdowns are automatically set in
the last 15% of the travel.
4B - TRIMMER SETTINGS
4A - DIP-SWITCHES SETTINGS
DIP
1
ON
OFF
ON
OFF
Opening / Stop / Closing / Stop modality (step by step)
Opening / Pause / Closing (it accepts only opening commands)
Yes automatic reclosing (set by “PAU” trimmer)
No automatic reclosing
Stop and it recloses for 2 seconds in opening (PHO2, working as pneumatic edge)
Stop and it keeps on opening after clearing in opening (PHO2 , working as photocell)
ON
OFF
STEP
2
AUTO
3
PHO 2
Flashing light
Steady light
ON
OFF
4
LAMP
Kick-back enabled
Kick-back disabled
ON
OFF
5
STRIKE
Yes rapid automatic reclosing
No rapid automatic reclosing
ON
OFF
6
FAST
START radio channel programming procedure (see paragraph 3A)
Pedestrian opening radio channel programming procedure (see paragraph 3B)
ON
OFF
7
RADIO
Standard backjump
Short backjump
ON
OFF
8
MODE
DIP STATUS FUNCTIONING
DESCRIPTION
If the dip-switch "
MODE
" is set to
ON
, the control unit manages the gate's back jump (standard) near mechanical stops.
On the contrary, if the dip-switch "
MODE
" is set to
OFF
, the control unit generates a smaller back jump compared to the
standard one.
It is recommended to pay attention to the value of dip-switch "MODE," because incorrect back jump values, in some situations,
may affect the mechanical parts of the automation.
5 - DIP-SWITCHES DESCRIPTION
5A - DIP-SWITCH 1 - MODE
If the “
STEP
” dip-switch is set to
ON
, the step-by-step function is enabled. Every time the control unit receives an input signal, it
perform an action. When the automation is stationary, it starts the motor, and when the automation is moving, it stops the motor.
If the “
STEP
” dip-switch is set to
OFF
, the modality OPEN/STOP/CLOSING is enabled. The control unit accepts only commands
(by wire or by transmitter) in opening. So, when the gate is closed, it opens. When the gate is opening, it keeps opening, and
when the gate is closing, it opens completely.
The reclosing takes place with the time set by the “
PAU
” trimmer, if the “
AUTO
” dip is set to
ON
.
Otherwise, it is necessary to give a START command (by wire or by transmitter).
5B - DIP-SWITCH 2 - STEP
If the “
AUTO
” dip-switch is set to
ON
, the automatic reclosing function is enabled. The control unit automatically closes the
wings after the time set by the “
PAU
” trimmer (see paragraph 4B).
If the “
AUTO
” dip-switch is set to
OFF
, the automatic reclosing function is disabled. It is necessary to supply a command (by
wire or by transmitter) to close the wings.
5C - DIP-SWITCH 3 - AUTO
If the “
PHO2
” dip-switch is set to
ON
, the safety devices in opening, when they intervene, stop the motion of the wings, which
will open again as soon as cleared (typical functioning of the photocell).
If the “
PHO2
” dip-switch is set to
OFF
, the safety devices in opening, when they intervene, invert the motion for 2 seconds, and
then they stop the automation. So, it is necessary to supply a command (by wire or by transmitter) to finish the travel, and close
the wings (typical functioning of the safety edge). With this setting these safety devices in closing do not intervene.
5D - DIP-SWITCH 4 - PHO2
(see also paragraph 11B)
If the “
LAMP
” dip-switch is set to
ON
, the power supply given to the lamp (terminals 8,9) is intermittent (see paragraph 12A).
If the “
LAMP
” dip-switch is set to
OFF
, the power supply given to the lamp (terminals 8,9) is direct (see paragraph 12A).
5E - DIP-SWITCH 5 - LAMP
(see also paragraph 12A)
If the “
STRIKE
” dip-switch is set to
ON
, the kick-back is enabled (see paragraph 12D). In this way, the control unit will supply a
voltage swing at the beginning of the opening cycle, and at the end of the closing cycle.
If the “
STRIKE
” dip-switch is set to
OFF
, the kick-back is disabled.
5F - DIP-SWITCH 6 - STRIKE
(see also paragraph 12D)
If the “
FAST
” dip-switch is set to
ON
, the rapid reclosing is enabled. This modality enables to reclose the gate as soon as the
control unit notices that the photocell range have been occupied and cleared. So, going through the passage, the automatic
reclosing of the automation will be enabled, without waiting the pause time.
If the “
FAST
” dip-switch is set to
OFF
, the automatic reclosing is disabled
5G - DIP-SWITCH 7 - FAST
If the “
RADIO
” dip-switch is set to
ON
, the START channel is memorized during the programming of the radio transmitter (see
paragraph 3).
If the “
RADIO
” dip-switch is set to
OFF
, the pedestrian opening channel is memorized during the programming of the radio
transmitter (see paragraph 3).
5H - DIP-SWITCH 8 - RADIO