Put 

DIP 3

 in the 

ON

 position and 

DIP 2

 in the 

OFF

 position.

In this mode, if a command is given via radio or through the “STR” input, the control unit:

- gives a steady flash of one second.

- starts the motor at the speed set on the trimmer  

FOR.

- opening is halted by the limit switch triggering, an obstacle being detected or the manoeuvre timing out. If additional commands 

are given during opening, they have no effect.

- with the automation at a standstill or in automatic pause, when a command is given, the pause count restarts from zero each 

time.

When the pause times out, the door is closed and the control unit:

- gives a steady flash of one second.

- starts the motor for one second at a reduced speed (softstart) and then at the speed set on the trimmer FOR.

 - if a command is given during closing, the control unit reopens the door fully.

- closing is halted by the limit switch triggering, an obstacle being detected or the manoeuvre timing out. 

     Keeping the opening contact closed (“STR” terminal) for example with a timed relay, the control unit opens the door 

and the automation remains disconnected and automatic closing is disabled until the contact is reopened (Company 

Function).

OPERATION MODES 

Put 

DIP 3

 in the 

OFF

 position and 

DIP 2

 in the 

ON

 position. 

The step by step command sequence is OPEN-STOP-CLOSE-STOP 

The opening and closing manoeuvres take place as described in the previous paragraph. 

STEP BY STEP MODE WITHOUT AUTOMATIC CLOSING 

Put 

DIP 3

 in the 

ON

 position and 

DIP 2

 in the 

ON

 position.

The step-step logic is OPEN/STOP/CLOSE/STOP.

When the opening manoeuvre has been completed and the pause time set on the “

PAU

” trimmer has elapsed

the control unit effects automatic closing.

If, when the automation is closed, a radio command is given, either through the “

STR

” input command or the 

STAR

 push button 

on the board, the control unit:

- commands a one second fixed pre-flash

- it activates the motor for 1,5 second at maximum power and then at the power set with the “

FOR

” trimmer.

- the opening terminates when the limit switch or the mechanical stop are triggered or the manoeuvre time has elapsed. 

If the automation is completely open, once the pause time has elapsed the closing manoeuvre takes place. The control unit:

- carries out a fixed two seconds pre-flash.

- it activates the motor for 1,5 second at maximum power and then at the power set with the “

POWER

” trimmer.

- The opening terminates when the limit switch or the mechanical stop are triggered or the manoeuvre time has elapsed. 

STEP BY STEP MODE WITH AUTOMATIC CLOSING 

Put 

DIP 3

 in the 

OFF

 position and 

DIP 2

 in the 

OFF

 position. 

Hold down the 

STAR

 button located on the electronic board, the control unit opens the door until the end of opening stroke is 

reached or the button is released. 

Hold down the  

P2/RAD 

 button located on the electronic board, the control unit closes the door until the end of closing stroke is 

reached or the button is released. 

The radio command has no effect. When the control unit is in this mode it is not possible to enter the programming of the radio 

codes. 

 

DEAD MAN'S SWITCH MODE 

Use the “

FOR

” trimmer to adjust the voltage with which the motor is powered during operation, thus adjusting its speed. This is 

settable between 50% and 100% of the maximum force and can be increased by turning the trimmer clockwise. 

Thus if the trimmer is set on the minimum then the speed is equal to about 50%, if adjusted in an intermediate position it is equal 

to 75%, while at the maximum the speed will be the largest obtainable.   

      

     A variation of the “FOR” trimmer requires the repetition of the learning procedure since the operation times, and 

thus the moments in which to start the slow-down, vary. 

TRIMMER 

Trimmer “FOR” - Motor speed 

The “

PAU

” trimmer is used to set the pause time of the control unit if the automatic closing is enabled by means of 

DIP 3

The pause time is settable between 3 and 60 seconds and can be increased by turning the trimmer clockwise. 

Thus if the trimmer is set at the minimum then the pause time is equal to about 3 seconds, if adjusted to an intermediate position 

it is equal to about 28 seconds, while at the maximum the pause time will be about 60 seconds. 

Trimmer “PAU” - Pause time 

The “

OBS

” trimmer is used to adjust both the intervention delay after detection of an obstruction and the opposing force to be 

used by the automation. This function is useful to overcome any critical points of the automation where, for a brief time interval, 

there is greater power absorption by the motor. 

 Both the intervention delay and the opposing force can be increased by turning the trimmer clockwise. The intervention delay 

can be set between 0.1 and 3 seconds. 

Thus if the trimmer is set at the minimum then the intervention time is equal to about 0.1 seconds, if adjusted to an intermediate 

position it is equal to about 1.5 seconds, while at the maximum the intervention time will be about 3 seconds. 

Trimmer “OBS” - Obstacle sensitivity 

When triggered, the photocell provokes: 

- in closing phase, an inversion of the motion, either immediate or when cleared, according to the programming, 

- in opening phase it has no effect, 

- when the access is closed it has no effect on the opening commands if set for immediate inversion, otherwise it delays the 

opening until it is cleared, 

- if the access is open it inhibits the closing commands. 

OPERATION OF THE SAFETY DEVICES 

PHOTOCELL (PHO1 input)

Safety devices can be connected (self-testing or not) to the “

PHO2

” input on the control unit (e.g. fixed wire ribs, 

pneumatically-operated ribs, etc.).

The safety acts as follows:

- in closing phase it has no effect

- in opening phase it provokes an inversion of direction for 2 seconds,

- when the gate is closed the opening commands are inhibited,

- when the gate is open the closing commands are inhibited

SAFETY IN OPENING (PHO2 input)

The control unit has a self-test function of the safeties connected to the “PHO1” and “PHO2” input. 

It switches off the transmitter to check the commutation of the corresponding receiver contact before the execution of each 

manoeuvre. In this case, the “gate open warning light” is not available. 

To activate this self-test function proceed as follows:

- switch 

DIP1 

to

 ON

- connect the positive of the photocell transmitter power to the terminal “

autotest

If the enabling of the safety self-test is not required switch 

DIP1 

to

 OFF

.

SAFETIES SELF-TEST 

1  2  3  4 

ON 

1  2  3  4 

ON 

1  2  3  4 

ON 

1  2  3  4 

TIMED AUTOMATIC CLOSING MODE 

ON 

Summary of Contents for ISTBJV01

Page 1: ...ROLLS INSTRUCTION MANUAL UK ISTBJV01...

Page 2: ...1 3 5 2 4 6 F F B A E B C D E E H G...

Page 3: ...7 9 11 8 10 12 I I I L B O O M M N N M M M M N N E A A 18 mm...

Page 4: ...13 14 15 16 17 18 H O P R Q 11 10 09 08 07 06 05 04 03 02 01...

Page 5: ...19 20 R 22 21 24 23...

Page 6: ...only Disposal of waste material has to observe local regulations Installing testing and first functioning have to observe the laws in force WARNINGS MAIN FEATURES Power supply 230 Motor power supply...

Page 7: ...TYPICAL SYSTEM 1 Gear motor 2 Photocell 3 Flashing light 4 Key selector 5 Adaptor arm 1 2 2 3 4 1 2 2 3 4 5...

Page 8: ...05 Prepare the two profiles F and the joint G supplied fig 06 Join the two guides and the joint firmly together with the fastenings supplied H fig 06 Insert the screw M8x70 E into the bracket I Inser...

Page 9: ...keep it released even after closing the gate OPERATION The user that exits from the garage can close the gate and re enter without having to repeat the release operation The automation release must be...

Page 10: ...s in opening contact PHO2 STOP contact Terminals 4 6 common START contact 12 Vdc power supply Safety autotest 12Vdc Terminals 1 8 common Safety devices in closing contact PHO1 24Vdc power supply FLASH...

Page 11: ...red LED goes off Make a transmission pressing the desired key on the transmitter During entry the red LED flashes and then remains steady on once the code is stored Power up the control unit and put D...

Page 12: ...chanical stop 8 The control unit briefly open 9 Pause for one second 10 The door close until mechanical stop Yellow LED switches off END of learning procedure 1 Put the door in an intermediate positio...

Page 13: ...or 2 sec Yellow led flashes 3 Within 5 seconds press the programming button P1 SET for 1 sec Yellow LED turned on 4 The control unit briefly open Yellow LED stays on 5 The door close until mechanical...

Page 14: ...IP 2 in the ON position The step step logic is OPEN STOP CLOSE STOP When the opening manoeuvre has been completed and the pause time set on the PAU trimmer has elapsed the control unit effects automat...

Page 15: ...ntion delay can be set between 0 1 and 3 seconds Thus if the trimmer is set at the minimum then the intervention time is equal to about 0 1 seconds if adjusted to an intermediate position it is equal...

Page 16: ...p input stops all the function To resume the cycle the stop must be deactivated and another command given BACK UP BATTERIES STOP INPUT SIGNALLING LED T fa F A The control unit has two output terminals...

Page 17: ...e of the fastenings wear on the moving parts pulleys carriages and the belt tension Fuse 2A Accessories LED Signal Line fuse 2A MAINTENANCE Motor and encoder connection SW Secondary transformer Blue C...