P/N 10-5151-501-102-01 • ISS 27NOV14
Addressing
Each module requires a numeric address between 128 and
252 for identification purposes. This is set using DIP switches
1-7. See the address table at the end of this document.
Status LED
The status LED is configured using DIP switch 8 in the DIP
switch selector:
•
If set to ON the LED will flash during all communications
between the module and the control panel.
•
If set to OFF it will flash only during selected
communications between the module and control panel
(see control panel manual for further details).
The status LED is lit constantly during alarm.
Maintenance and testing
Basic maintenance consists of a yearly inspection. Do not
modify internal wiring or circuitry.
To test the module:
1. Remove a detector head from its base or activate a
manual call point connected to the module detection zone.
2. If the status LED and control panel fail to indicate the test
all connections should be checked and the module
address verified.
Specifications
Operating voltage
22 to 38 VDC
Loop current consumption
at 24 VDC (standby)
at 35 VDC (standby)
Alarm
90 µA
105 µA
<3.0 mA
Current consumption
24 VDC aux. supply
(standby)*
24 VDC aux. supply (alarm)*
200 µA
<85 mA
End-of-line resistor
4.7 k
Ω
Operating temperature
Storage temperature
−10 to +50ºC
−10 to +70ºC
Relative humidity
10 to 95% (noncondensing)
Weight
370 g
Dimensions
182 × 142 × 77 mm
* Excluding loop devices
Regulatory information
This section includes both regulatory information and a
summary on the declared performance according to the
Construction Products Regulation 305/2011. For detailed
information refer to the product Declaration of Performance.
Certification
Certification body
0370
Declaration of
Performance number
360-4109-0599
Year of first CE marking
08
Product identification
KAL710
Intended use
See DoP point 3
Essential characteristics See DoP point 9
Manufacturer
UTC CCS Manufacturing Polska Sp. Z o.o.
Ul. Kolejowa 24. 39-100 Ropczyce, Poland
Authorized EU manufacturing
representative: UTC Fire & Security B.V.
Kelvinstraat 7, 6003 DH Weert, Netherlands
2012/19/EU (WEEE directive): Products
marked with this symbol cannot be
disposed of as unsorted municipal waste in
the European Union. For proper recycling,
return this product to your local supplier
upon the purchase of equivalent new
equipment, or dispose of it at designated
collection points. For more information see:
www.recyclethis.info.
Contact information
For contact information, see www. utcfssecurityproducts.eu.
ES: Instrucciónes de instalación
Descripción
El módulo KAL710 se utiliza para conectar una zona
convencional a un bucle del sistema de incendios
direccionable.
El módulo puede utilizarse en los sistemas de detección sin
subdivisión de áreas o cuando no se necesiten los datos de
ubicación exactos.
Se puede utilizar un módulo para conectar hasta 20 detectores
convencionales y un número ilimitado de puntos de llamadas
manuales o contactos normalmente abiertos (NA) al sistema
de detección de incendios.
Instalación
Precaución:
Consulte el estándar EN54:14 y las normativas
locales para obtener información acerca de las directrices de
planificación, diseño, instalación, funcionamiento, utilización y
mantenimiento del sistema.
Instalación del módulo
Desconecte la fuente de alimentación del sistema de incendios
e instale el módulo en la carcasa protectora proporcionada.
Conecte el hilo apantallado del cable de bucle al tornillo de
tierra e instale una resistencia de fin de línea de 4,7 k
Ω al final
de la zona de detección.
Una fuente de alimentación auxiliar debe proporcionar
alimentación de 24 V al módulo.