Sirius Capacitor Module
–
User Manual
Model Number -7100-48-B-2C-M-SD-A-G
This manual is subject to change without notice and at the sole discretion of Kilowatt Labs, Inc.
Kilowatt Labs, Inc. |
25
Module Charge Full
When the Module voltage reaches the
maximum voltage, the electronic switch
will shut down. This means that each cell
from the Module has reached to maximum
rated charge.
The event will be repeated if the charger is
still ON and operating in the same
condition, the buzzer alarms and LCD will
show the warning message.
Low Charge Module
When the Module is in standby mode and
it reaches the minimum voltage, the LCD
will display this message every 30 seconds.
When the Module is connected to a load
and it reaches the minimum voltage, the
buzzer alarms, electronic switch will shut
down and LCD will display the message.
Over-Temperature
When the Module has an Over-
Temperature fault, the buzzer alarms, the
electronic switch will shut down and LCD
will display the message.
Terminal Over
Temperature
When the Module has a terminal Over-
Temperature fault, the buzzer alarms, the
electronic switch will shut down and LCD will
display the message.
This means that electronic switch has
reached 80
o
C.
8.
Trouble Shooting:
Check the indicators on the front to determine the state of the Module. A warning state is triggered
when a condition, such as voltage, current or temperature, is beyond design limitations. When the
Module falls outside prescribed limits, it enters a warning state. When a warning is reported, the
Module immediately stops operation.