Sirius Capacitor Module 

12 

User Manual - 7.1kWh48VDC Module 

 

This manual is subject to change without notice and at the sole discretion of Kilowatt Labs, Inc. 

 

Kilowatt Labs, Inc. | 

www.kilowattlabs.com

  

Trouble shooting: Faults and Solutions 

This section explains how to correct faults: 

Over-voltage (OV) 

The OV cut-off is at 56V. Set the 

charger’s limit below 

56V to prevent an OV event. If the voltage 

exceeds 56V, the module shuts down and locks.  

The module unlocks 

when the module’s surface charge is 

cleared, and the voltage drops below 

54V. The event can be repeated if the charger is still ON and operating in the same condition. 

Procedure

:

  C

heck the charger’s 

upper cut off limit and ensure it is set below 56V.  

Under-voltage (UV) 

The  UV  cut-off  is  44V.  If  the  voltage  goes  below  44V,  the  module  shuts  down  and  locks.  The 

module unlocks when the voltage goes above 44V. The event can be repeated if the load is still 

ON and operating in the same condition. 

Procedure

:

    Check  for  the  operating  load  lower  cut  off  limit  and  ensure  it  is  above  the  lower 

threshold limit of 44V.  

Over-Current (OC) 

OC occurs when the current goes above 296A or when the module is short-circuited. In this event 

the module shuts down and locks. 

Procedure

:

  Switch off the module and check the voltage across the module terminals to find 

whether it is a short circuit. In case of short circuit, check the operating circuitry and clear the 

short circuit. The module can be unlocked in 30 seconds after the current goes below 296A. 

Over-Temperature (OT) 

OT occurs when the module temperature goes above 75°C. In this event, the module shuts down 

and locks.  

Summary of Contents for 7100-48-S-2C-DC-L-T

Page 1: ...SIRIUS CAPACITOR MODULE User Manual Model number 7100 48 S 2C DC L T Version 1 0 Release Date JAN 24 2018...

Page 2: ...pecifications without advance notice Users are encouraged to consult the Company or its authorized representatives before using the Manual Neither the Company nor its authorized representatives shall...

Page 3: ...s Inc www kilowattlabs com Table of Contents Unpacking and Handling 4 Installation 4 Parallel Connection 5 Product Overview 5 Panel Description 6 LCD Description 7 COMM LED 9 COMM Connector 9 Power Sw...

Page 4: ...ication software NOTE The original shipping materials are approved for both air and ground shipment Handling The Sirius Capacitor modules are designed to provide years of trouble free operation Proper...

Page 5: ...labs com handled only by qualified and trained personnel Installation should not exert bending or twisting torque to the module enclosure Parallel Connection of Sirius Modules The parallel combination...

Page 6: ...hange without notice and at the sole discretion of Kilowatt Labs Inc Kilowatt Labs Inc www kilowattlabs com Panel Description The figure below describes the front panel components of the module 1 Posi...

Page 7: ...Power Switch the module gets power and the LCD shows the following message until the cables are connected to the module terminals Once the cables are connected the LCD shows the following information...

Page 8: ...urpose only the OV has to be set at 54V The LCD shows the voltage at that time as well Undervoltage UV When the module has an undervoltage fault UV the LCD shows the followig warning message This mean...

Page 9: ...his is a RJ45 connector to monitor the module using the application software Power Switch When the power is switched ON using the ON OFF switch on the front panel the module electronics are powered up...

Page 10: ...off This feature will be activated when the module temperature exceeds the maximum temperature limit of 75 C These features work as follows Disconnect Event Disconnect Value Reconnect Feature Over vo...

Page 11: ...wer switch which lights up the LCD Open the monitoring software application in the monitoring device from the CD provided The module has the anti theft feature So an authorized password should be ente...

Page 12: ...V Under voltage UV The UV cut off is 44V If the voltage goes below 44V the module shuts down and locks The module unlocks when the voltage goes above 44V The event can be repeated if the load is still...

Page 13: ...not require periodic maintenance Safety Never touch the positive or negative terminals as the module can be charged and cause fatal electrical shocks Always verify that the module is fully discharged...

Page 14: ...ut affecting the projected cell cycle life of 1 000 000 cycles Projected Calendar Life the projected life of the module in years from the date it is first operated is 45 years for the supercapacitor c...

Page 15: ...30 after 30 days 80 after 60 days Self discharge only when not charging or discharging No memory effect Module can be recharged to 100 at any time Storage Can be stored at any SOC for as long as requi...

Reviews: