Sirius Capacitor Module
11
User Manual - 7.1kWh48VDC Module
This manual is subject to change without notice and at the sole discretion of Kilowatt Labs, Inc.
Kilowatt Labs, Inc. |
www.kilowattlabs.com
•
Connect the cables to the module terminals and ensure that the bolt enters 40mm into the
terminals. The LCD will give an error message if the terminals and bolts are not connected as
specified here.
•
Configure the PC IP in the network and internet settings of the monitoring device.
•
Connect the RJ45 cables to the COMM connector slot to start communication and monitoring.
•
Now turn on the power switch which lights up the LCD.
•
Open the monitoring software application in the monitoring device from the CD provided.
•
The module has the anti-theft feature. So an authorized password should be entered to start
operating the module.
NOTE:
Please refer to the monitoring software manual in the CD provided with the module
for the details.
•
Now the module stays functional even when the RJ45 connector is removed (monitoring
OFF).
NOTE
: Authorization is required again when the module is either powered OFF or the cables
are removed.
•
The module can be shutdown either by the ON/OFF switch or by removing the output cables
from the module terminals.
NOTE:
Switch OFF the module when not in use as the module is self-powered or else, it can
result in the self-discharge of the super-capacitors.