Sirius Capacitor Module
–
User Manual
Model Number - 3550-48-B-1.7C-M-SD-A-G
This manual is subject to change without notice and at the sole discretion of Kilowatt Labs, Inc.
Kilowatt Labs, Inc. |
37
Charge rate
(C)
Charging current
(Amp)
Discharging current
(Amp)
Time
(Minutes)
0.28
20
20
Approx. 4hrs
0.5
37
37
Approx. 2hrs
1
70
70
Approx. 1hr
1.35
100
100
45 mins
1.7
125
125
35 mins
Table 2: Charge rate with its corresponding time.
Q. Why the Module needs twice of power cycle?
A. When the Module is switched OFF and the SiriusVIEW is still open you have to wait for 10 Sec (since
the application is still communicating with the Module) before turning ON the Module, or either by
terminating the SiriusVIEW or by disconnecting the communication cable.
Q. How much is the capacity of the internal storage (SD Card)?
A. 8GB SD Card is used in the Module which logs 85 bytes of data per 10 seconds. Note that data
logging should be turned ON before the Module will start logging and data logging is limited to 30
days. After reading the data the Module will delete it automatically. By default, data logging is OFF for
firmware version 2. 0 and above.
Q. Do I need to use SiriusVIEW Software?
A. The Module can work stand-alone without the software however, the software can be used to
monitor and extract the data & measurement as well as to enhance the performance of the Module.
Q. How do I know if there is firmware issue in the Module?
A. Please refer to SiriusVIEW monitoring software manual Configuration of Module and Software
section.
Q. What kind of issues can happen about firewall and antivirus programs?
A. There will be no problem as far as the software run as administrator.
Q. How to calibrate Module parameters?
A. To calibrate Module parameter like (Voltage, Current, Temperature, Energy). Kindly consult with
your Reseller for calibration procedure.
Q. What is the reason if the LED isn’t working at all?
A. Due to different reasons that may happen such as:
•
If we can get the output (Terminal, software communication), the LED may have some technical
issues.
•
The protected terminal is not working.
Please consult with your Reseller.
Q. How to troubleshoot the communication between the Module and PC?
A. If you face any communication difficulties between the Module and PC please troubleshoot as
follows:
•
Double Check the cable connection (try to use anther USB cable).
•
Try to use anther port in the PC.
•
Check the Module USB drive in your PC from setting then search for Device Manager then go to