Sirius Capacitor Module
–
User Manual
Model Number - 3550-48-B-1.7C-M-SD-A-G
This manual is subject to change without notice and at the sole discretion of Kilowatt Labs, Inc.
Kilowatt Labs, Inc. |
25
7.
Automatic Safety Shutdown:
The Module will automatically shut down under any excessive use conditions in order to prevent
damage to itself and to the connected equipment. Specified limits for excessive current, high voltage
and low voltage are provided in Module’s technical data sheet.
Cause
of
Shutdown
LCD Warning Message
Description
Over-Current
(OCD)
When the Module has an Over-current fault,
the counter counts for 5 seconds and if the
current does not drop lower than the cut-off
and count down has reached to zero, the
buzzer alarms and the electronic switch will
shut-down.
Module Charge
Full
When the Module voltage reaches the
maximum voltage, the electronic switch will
shut down. This means that each cell from the
Module has reached to maximum rated charge.
The event will be repeated if the charger is still
ON and operating in the same condition, the
buzzer alarms and LCD will show the warning
message.
Caution!
Charge all the Modules to 100% SOC or same voltage level before
connecting them in Series.
Note!
Modules cannot be connected in series-parallel combination under any
circumstance.
Caution!
The Bypass circuit breaker is not protected with electronic switch, therefore
during over-voltage, under voltage and high temperature conditions, the
terminals will not shutdown. It only gives protection for over current
condition.