Estimated number of cycles at 100% DoD until
80% of rated watt hour capacity remains
2000
Estimated number of cycles at 80% DoD until
80% of rated watt hour capacity remains
5000
High Voltage Shutoff Protection
14.4 ±0.2 V
Low Voltage Shutoff Protection
11.5 V
Maximum Configuration - All CHLX Battery Bank
Up to 4 batteries in series OR 4 batteries in
parallel but not both.
Maximum Configuration - All HLX or Mixed
Battery Bank
Up to 4 parallel strings of 4 batteries in series
(total of 16)
Maximum Time Between Charges
6 Months
Normal Self-Discharge Current
≤20 mA
Peukert Coefficient
1.05
Rated Voltage
12.8 VDC
Self-Discharge Rate
≤2% per month
Standby Mode Activated
Current Draw from Load < 0.25 A (250 mA)
Voltage Configurations
12 V, 24 V, 36 V, 48 V
1200 CHLX Heater
64 W
1800 CHLX Heater
96 W
3600 CHLX Heater
192 W
Minimum Cell Balancing Voltage
3500 mV/Cell
Maximum Cell Balancing Current
70 mA
BMS Type
Switching Shunt Resistor
Internal Resistance
≤10m
Ω