background image

3P05-PCR-LE 1

Setup Guide

PCR-LE Series

Three-phase Output Driver

Thank you for purchasing the PCR-LE Series Three-phase out-
put driver.
Connecting the outputs of PCR-LE Series in star connection 
and installing the Three-phase Output Driver in these power 
supplies allows them to be used as three-phase system power 
supplies.

Features

Use of this device allows the PCR-LE series to provide the fol-
lowing enhanced functions, in addition to the PCR-LE’s stan-
dard functions. 
•  Three-phase Output 

Use of the device allows the three PCR-LE to generate three-
phase output, in which the U-phase unit of the three power 
supplies acts as a master and their V and W phase units acts 
as slaves. 

•  Setting of Either the Line Voltage or Phase Voltage
•  Independent Phase Voltage Setting

The individual phase voltage setting is possible on a phase 
basis.

•  Line Voltage Measurement
•  Measurements of the Total Power, Total Apparent Power, and 

Total Power Factor of Three Phases
Use of the device allows the totals of power and apparent 
power obtained through measurement using the three PCR-
LE to be displayed. The total power factor of the three phas-
es can also be calculated from these total values.

•  Variable Phase Difference

Check at Unpacking

Upon reception of the product, confirm that the package con-
tains the necessary accessories and that the device and ac-
cessories have not been damaged during transportation. If the 
device is damaged or any accessory is missing, notify Kikusui 
distributor/agent.

U phase boards 

(1 pc.) 

Power-sync cable

 (1 m; 2 pcs.)

91-80-5099

Connecting cable (75 cm; 2 pcs.)

 

Cable: [91-80-9919]

Core: [96-00-0530]

Setup Guide 

(This guide)(1 pc.)

V and W phase boards 

(one each) 

The indications 

V

 and 

W

 on the 

panel part of each board. 

Firmware version of PCR-LE

When using the 3P05-PCR-LE, the PCR-LE must be required 
with the firmware version of 2.00 or later. If the firmware ver-
sion of the PCR-LE is 1.99 or previous version, the PCR-LE is 
required for the firmware update.
When using the 3P05-PCR-LE, the firmware of all the PCR-LE 
series that make up the system must be the same.
To check the firmware version of the PCR-LE, refer to the opera-
tion manual of the PCR-LE series. In case, the PCR-LE needs 
update, contact your Kikusui agent or distributor.

Functional Restrictions during 

Three-phase Operation

Use of the 3P05-PCR-LE allows the PCR-LE series to generate 
three-phase outputs. The following functions are not available 
when the device is installed in the power supplies.

DC mode
Regulation adjustment
High-speed response

You cannot use the 3P05-PCR-LE with the 2P05-PCR-LE Single-
Phase Three-Wire Output Driver Option.

KIKUSUI ELECTRONICS CORP.

1-1-3, Higashiyamata, Tsuzuki-ku, Yokohama, 224-0023, Japan
TEL: +81-45-593-7570 Fax: +81-45-593-7571

WEBSITE

http://www.kikusui.co.jp/en

The 3P05-PCR-LE is subject to export control laws.

The newest version of the operation manual can be downloaded from 
Download service of Kikusui website.
The contents of this manual may not be reproduced, in whole or in part, 
without the prior consent of the copyright holder.
The specifications of this product and the contents of this manual are 
subject to change without prior notice.

© 2012

3P05-PCR-LE

PART NO. Z1-006-0

6

0, IA005173

Oct. 2016

PCR-LE Manual

Summary of Contents for 3P05-PCR-LE

Page 1: ...r sync cable 1 m 2 pcs 91 80 5099 Connecting cable 75 cm 2 pcs Cable 91 80 9919 Core 96 00 0530 Setup Guide This guide 1 pc V and W phase boards one each The indications V and W on the panel part of each board Firmware version of PCR LE When using the 3P05 PCR LE the PCR LE must be required with the firmware version of 2 00 or later If the firmware ver sion of the PCR LE is 1 99 or previous versio...

Page 2: ...ow the same procedure to install the other two boards This completes installation of the phase board When a 3P05 PCR LE has been inserted into the slot1 of a PCR LE series that power supply can be used only in a three phase system To use the power supply in a single phase system the phase board must be removed from the slot1 Connecting the bords Use the connecting cable to connect the boards Conne...

Page 3: ...ngle core wires that are used to connect to the load Nominal cross sectional area mm2 AWG reference cross sectional area mm2 Allowable current A at Ta 30 C 86 F 0 9 18 0 82 17 1 25 16 1 31 19 2 14 2 08 27 3 5 12 3 31 37 5 5 10 5 26 49 8 8 8 37 61 14 6 13 3 88 22 4 21 15 115 1 Excerpt from Japanese laws related to electrical equipment The values vary depending on conditions such as the wire cov eri...

Page 4: ...rminal Master U phase W phase 2 m or less from the slave unit s L N to the master unit s L N 2 m or less from the slave unit s L N to the master unit s L N 2 m or less from the slave unit s L N to the master unit s L N Relay terminal Relay terminal PCR LE OUTPUT G N L OUTPUT G N L OUTPUT G N L OUTPUT G N L V S U R N W T G OUTPUT G N L OUTPUT G N L ...

Page 5: ...f the switchboard Power ON 1 Check that the POWER switches of PCR LEs are off 2 Use the power sync cable to connect the J1 connec tor and the J2 connector on the PCR LE rear panels Do not connect two J1 connectors to each other or two J2 connectors to each other Insert the cable firmly into the connectors until the are locked in place PCR LE Power sync cable V phase U phase W phase 3 Set the POWER...

Page 6: ...ed when you are setting three phase output 环境保护使用期限 Environment friendly Use Period 该标记为适用于在中华人民共和国销售的电子信息产品的环境保护使用期 限 只要遵守有关该产品的安全及使用注意事项 从制造年月起计算 在 该年度内 就不会对环境污染 人身 财产产生重大的影响 产品的废弃请遵守有关规定 产品的制造年月可以在以下网址中确认 http www kikusui co jp pi 毒有害物质或元素名称及含有标示 Name of hazardous materials and symbol of elemet in the equipment and quantity 有毒有害物质或元素 铅 Pb 汞 Hg 镉 Cd 六价铬 Cr VI 多溴联苯 PBB 多溴二苯醚 PBDE 本表格依据 SJ T 11364...

Reviews: