Technical data sheet 1.10-51.110-81-en
DDC110-L1 .. DDC110-L4 technolon
®
Room Module
D e v i ce De s c ri p ti on
Operation DDC110-L2
Display depending on the configuration:
Room temperature (actual value) with function symbol
or
Room setpoint with function symbol
↕
Other function symbols can be displayed depending on the
configuration:
Day operation
Night operation
Standby operation
Automatic switchover by
Central Program or presence
detector
Function symbols
Digital readout
►
Room setpoint selection
The room setpoint for day, night or standby operation is automatically determined by the program.
Depending on the configuration release, the room setpoint can be raised or lowered by ± 3 K or ± 5 K by
manual adjustment.
The manual adjustment acts as setpoint correction for all operating modes alike:
Example:
If the current room setpoint day is raised by 2 K,
then the room setpoint night and the room setpoint standby are raised by 2 K .
Key
Press once : The Room Module switches to temperature type control setting.
Function symbols
↕
or
↕
or
↕
are displayed,
Simultaneously, the decimal place of the current control setting blinks .
Now the room setpoint can be increased or lowered with the key
in steps of 0.1 K .
With the key , it is immediately possible to switch back to the standard display.
Without pressing a key, the Room Module switches back to the standard after 5 sec
display . The new room setpoint is stored.
►
Switching ventilator speeds on and off
The ventilator speeds are automatically switched on and off by the program .
If required, the ventilator speeds can be switched by manual control.
Key
and the Room Module switches to ventilator mode for manual control.
Function symbol
is displayed,
Simultaneously, the current ventilator setting blinks 0, 1, 2, 3 or auto.
0
Ventilator off,
No function symbol
1
Ventilator level 1
on
Function symbol
2
Ventilator level 2
on
Function symbol
3
Ventilator level 3
on
Function symbol
Auto
Automatic
operation:
Function symbol
lights up in seconds beat
The new ventilator level is set with the key
.
With the key
, it is immediately possible to switch back to the standard display.
Without pressing a key, the Room Module switches back to the standard after 5 sec
display . The new room setpoint is stored.
Page 6 / 12