A
Page 12 / 14
User Manual
MD15-FTL-315
Datasheet 3.09-20.315-09-EN
Issue 2012-08-16
EnOcean Equipment Profiles EEP A5-20-01 (Battery Powered Actuator)
DATA BYTES
Transmit mode:
Message from the actuator to the controller
DB_3:
Current Value value 0...100 %, linear n=0...100
DB_2.BIT_7:
Service on
DB_2.BIT_6
Energy input enabled (not applicable)
DB_2.BIT_5
2
Energy Storage > xx% charged (not applicable)
DB_2.BIT_4
Battery capacity < 10%
DB_2.BIT_3
2
Contact, cover open
DB_2.BIT_2
Failure temperature sensor, out of range
DB_2.BIT_1
Detection, window open
DB_2.BIT_0
Actuator obstructed
DB_1:
Temperature 0...40°C, linear n=0...255
DB_0.BIT_7:
Not used
DB_0.BIT_6
Not used
DB_0.BIT_5
Not used
DB_0.BIT_4
Not used
DB_0.BIT_3
LRN Bit 0b0 Teach-in telegram
0b1 Data telegram
DB_0.BIT_2
1
Self-controlled mode 0b0 off
0b1 on
DB_0.BIT_1
Not used
DB_0.BIT_0
Not used
Receive mode:
Commands from the controller to the actuator
rx time = max. 1s
Note:
The data transfer from the wireless partner to the wireless small actuator
must be completely finished within a maximum time window of 1 s.
DB_3:
Valve set point 0...100 %, linear n=0...100
Temperature set point 0...40°C, linear n= 0...255
DB_2:
Temperature actual from RCU = 0b0, Room controller-unit …
DB_1.BIT_7:
Run init sequence, only active in service mode
DB_1.BIT_6
Lift set, only active in service mode
DB_1.BIT_5
Valve open, only active in service mode
DB_1.BIT_4
Valve closed, only active in service mode
DB_1.BIT_3
Summer bit, reduction of energy consumption