Technical Data Sheet 2.50-35.021-01-en Rev

FSM21 Front Switch Module

For connection to the FBM38 fieldbus module. 

 

D e v i ce   De s c ri p ti on  

A

In

.

  stallation 

Electrical installation and device connection in the switchboard may only be carried out 
by qualified technicians. The power must be disconnected from the switchboard. 

 

 

1

Ausgangskontakte K1..K4: max. 230 V AC/24 V DC, 6 (3) A

17

18

19

20

4

5

6

7

8

9

10

17

18

19

20

Zentrale

DDC3000-System

FSM21

3

4

5

6

Fe

ld

bu

s

 +

Fe

ld

bu

s

 -

12

 V

 D

C

0 V

 D

C

Netz-

gerät

12 V DC +

-

12

 V

 D

C

0 V

 D

C

Da

ta

Clk

+12 V DC

0 V DC

FBM38

QBSchnittstelle 

Be

tr

ie

b

s

-

sp

a

n

n

u

ng

QBSchnittstelle 

Feldbus (CAN)

Feldbus (CAN)

Backbone

2

3

21

22

24

K2

31

32

34

K3

2

1

Vordere

Hintere

Anschluss-

klemmen

Hintere

Anschluss-

klemmen

Vordere

Anschluss-

klemmen

0V

51
IN

52
IN

53
IN

54
IN

55
IN

56
IN

57
IN

58
IN

59
IN

60
IN

0V

paarig
verdrillt

paarig
verdrillt

11

12

14

K1

7

8

9

10

FBM38

SBM21/41

0 V

 D

C

L-

Te

s

t

SS

M

SS

M

-Q

7

8

9

10

Anschluss alternativ

1)

2)

    meldung

(nicht DDC3010/3035/3100)

Relais K1
(Stufe 1.1)

1) Taster: LED-Test
2) Taster: Quittierung
    der Sammelstör-

(Adressein-
 stellung >16)

Backbone-Anschluss
an max. 63 FBM38 
und max. 16 SBM21/41

37/37

33/32

34/33

35/34

L

N

Gerät/Aggregat 1

41

42

44

K4

Die binären Eingänge
55/IN..58/IN können
als Schließer oder 
Öffner angeschlossen
werden.
Umschaltung am
FBM38.

Relais K2
(Stufe 1.2)

Relais K3
(Stufe 2.1)

Relais K4
(Stufe 2.2)

Gerät/Aggregat 2

-

51/IN..54/IN zusätzliche

Betriebsmeldungen

nur bei Betriebsart Fern

Störmeldungen 1..4

1

2

3

4

 

Ensure that this process complies with VDE guidelines and local wiring regulations.  

 

 

Danger 

The FSM21 front switch module is connected to the QB interface of the FBM38 fieldbus module. 

 

The 4-wire QBS connection line can have a maximum length of 200 m. 

 
Wiring diagram 
 
 

 

Displayed in 
wiring diagram: 

Switch levels with reciprocal 
hardware locking (e.g. for 
fan control (OR function)). 
 
When the switch levels are 
switched together, then the 
K2 and K4 inputs must be 
connected directly to “L” 
(e.g. for electric air heaters 
(AND function)). 

 

Bridges K1-K2 and K3-K4 
are omitted. 
 
The software setting of the 
AND/OR function is made 
on the FBM38. 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

Connection of the DC 12 V operating voltage is only made on connection terminals 1 and 2 of the 
FBM38. 

Note 

Continue to observe the connection instructions in the device description of the FBM38 fieldbus module 
(Technical Data Sheet 2.50-30.038-01-en). 

Page 5 / 12 

Summary of Contents for FSM21

Page 1: ...FSM21 front switch module is used for the direct operation of 1 or 2 stage unit or device switches The module functions through macro assignments on the FBM38 fieldbus module A load rolling switch wit...

Page 2: ...be carried out by qualified technicians See the Qualified Technicians section Each person who uses the devices must have read and understood the descriptions on the technical data sheet If the device...

Page 3: ...Power is supplied over the QB interface Connection Terminal connection to QB interface 4 wire maximum cable length 200 m Controls Two manual automatic switches for the Automatic Off Position1 Positio...

Page 4: ...ilable as an accessory for wall mounting Mounting on a switchboard or in a 19 KA rack may only be carried out by qualified technicians The power must be disconnected from the switchboard Switchboard e...

Page 5: ...ackbone Anschluss an max 63 FBM38 und max 16 SBM21 41 37 37 33 32 34 33 35 34 L N Ger t Aggregat 1 41 42 44 K4 Die bin ren Eing nge 55 IN 58 IN k nnen als Schlie er oder ffner angeschlossen werden Ums...

Page 6: ...de on the FBM38 fieldbus module The FBM settings and a detailed macro description are found in technical data sheets 2 50 30 038 01 en and 2 50 30 038 02 en Both of these are included with the FBM38 f...

Page 7: ...4 in automatic and manual mode each lock against each other or switch together The switching delays apply in the same way when the load rolling switch is switched on in automatic and manual operation...

Page 8: ...the operating message input and control signal match Green signal LED 1 1 1 2 2 1 2 2 with Local operating mode activated Two signal LEDs are found to the right of each manual automatic switch They a...

Page 9: ...onnel e g a commissioning technician The power must be disconnected from the switchboard Danger Check the mounting installation and device connections with the power disconnected from the FBM38 fieldb...

Page 10: ...or On 6 s Off 3 s Malfunction message inversion Yes No Operating mode Remote Local Control of unit 1 Control of unit 2 _____________________________ _____________________________ Mechanical limitation...

Page 11: ...Technical Data Sheet 2 50 35 021 01 en Rev FSM21 Front Switch Module For connection to the FBM38 fieldbus module Device Description A Other setting notes Page 11 12...

Page 12: ...Page 12 12 Technical Data Sheet 2 50 35 021 01 en Rev Device Description FSM21 Front Switch Module For connection to the FBM38 fieldbus module A...

Reviews: