1. RECOMMENDED LOCATIONS FOR ALARMS

• Locate the first alarm in the immediate area of the bedrooms. Try to monitor

the exit path as the bedrooms are usually farthest from the exit. If more than
one sleeping area exists, locate additional alarms in each sleeping area.

• Locate additional alarms to monitor any stairway as they act as chimneys for

smoke and heat.

• Locate at least one alarm on every floor.

• Locate an alarm in every bedroom.

• Locate an alarm in every room where electrical appliances operate (i.e.

portable heaters or humidifiers).

• Locate an alarm in every room where someone sleeps with the door closed.

The closed door may prevent an alarm not located in that room from waking
the sleeper. Kidde recommends installing a Wireless Smoke Sounder in all
rooms where older adults, individuals with partial hearing loss, and children
sleep.

• Smoke, heat, and combustion products rise to the ceiling and spread hori-

zontally. Mounting the smoke alarm in the center of the ceiling places it clos-
est to all points in the room. Ceiling mounting is preferred in ordinary resi-
dential construction.

• For mobile home installation, select locations carefully to avoid thermal barri-

ers that may form at the ceiling. For more details, see MOBILE HOME INSTAL-
LATION below.

• When mounting an alarm on the ceiling, locate it at a minimum of 4” (10

cm) from the sidewall (see figure 1).

• When mounting the alarm on the wall, use an inside wall with the top edge

of the alarm at a minimum of 4” (10 cm) and a maximum of 12” (30.5 cm)
below the ceiling (see figure 1).

• Put smoke alarms at both ends of a bedroom hallway or large room if the

hallway or room is more than 30 feet (9.1 m) long.

• Install Smoke Alarms on sloped, peaked or cathedral ceilings at or within 3 ft

(0.9m) of the highest point (measured horizontally). NFPA 72 states: “Smoke
alarms in rooms with ceiling slopes greater than 1 ft in 8 ft (.3m in 2.4 m)
horizontally shall be located on the high side of the room.” NFPA 72 states:
“A row of detectors shall be spaced and located within 3 ft (0.9m) of the
peak of the ceiling measured horizontally” (see figure 3).

0919-7201-02.qxd  1969.12.31  4:15 PM  Page 3

Summary of Contents for RF-SM-DC

Page 1: ...o that when one unit sounds it will trigger all other units to sound thereby giving a family more time to escape Kidde estimates that nearly 100 million U S homes either do not have interconnected smo...

Page 2: ...sooner than ionization alarms Home fires develop in different ways and are often unpredictable For maximum protection Kidde recommends that both Ionization and Photoelectric alarms be installed WARNIN...

Page 3: ...of the ceiling places it clos est to all points in the room Ceiling mounting is preferred in ordinary resi dential construction For mobile home installation select locations carefully to avoid thermal...

Page 4: ...larm at a minimum of 4 10 cm and a maximum of 12 30 5 cm below the ceiling see figure 1 If you are not sure about the insulation in your mobile home or if you notice that the outer walls and ceiling a...

Page 5: ...an RF signal Electronic noise may cause nuisance alarms Near large metal surfaces and bundles of wire Smoke alarms are not to be used with detector guards unless the combination alarm and guard have...

Page 6: ...alarms 8 Read the user s guide and keep it in a safe place for future reference If your Wireless smoke alarms enter alarm mode first check to see if there is a fire If a fire does not exist and the t...

Page 7: ...nstalled Removal of any or all batteries will render the alarm inoperative CAUTION Alarm will not engage to bracket unless all three batter ies are installed Removal of any or all batteries will rende...

Page 8: ...sing the Test Button All interconnected alarms should respond CAUTION Due to the loudness of the alarm always stand an arm s length away from the unit when testing Tamper Resist Features This alarm ha...

Page 9: ...ir has been cleared of the condition causing the alarm Pushing the test button on the alarm will end the HUSH period Remote HUSH Control Press the button on any Kidde Wireless device to acti vate the...

Page 10: ...t reset button is pressed thus resetting the alarm HUSH MODE CONDITION The LED will flash every 2 seconds while the alarm is in HUSH mode TESTING TEST THE ALARM WEEKLY TO ENSURE PROPER OPERATION When...

Page 11: ...mely useful in a kitchen area or other areas prone to nui sance alarms For more information refer to Section 4 OPERATION AND TEST ING If the alarm does sound check for fires first If a fire is discove...

Page 12: ...t saving time CAUTION YOUR SMOKE ALARM IS SEALED AND THE COVER IS NOT REMOVABLE CAUTION Alarm will not engage to bracket unless all three batter ies are installed Removal of any or all batteries will...

Page 13: ...re devices that can provide early warning of possible fires at a reasonable cost however alarms have sensing limitations Ionization sensing alarms may detect invisible fire particles associated with f...

Page 14: ...you all can meet if a fire occurs Familiarize everyone with the sound of the smoke alarm and train them to leave your home when they hear it Practice a fire drill at least every six months including...

Page 15: ...se a very small amount of a radioactive element in the sensing chamber to enable detection of visible and invisible combustion products The radioactive element is safely contained in the chamber and r...

Page 16: ...ations occasionally experience conditions that can result in improper operation This equipment should be installed in accordance with the National Fire Protection Association s Standard 72 NFPA Batter...

Page 17: ...ame ID Devices may not have power Button not pressed long enough There may be too much interference between units Unit is set to the same ID as a system nearby Unit is located in area prone to cause f...

Page 18: ...the following two conditions 1 this device may not cause harmful interference and 2 this device must accept any interference received including interference that may cause undesired operation The ter...

Page 19: ...CEMENT OF SMOKE ALARM AND IN NO CASE SHALL KIDDE OR ANY OF ITS PARENT OR SUB SIDIARY CORPORATIONS BE LIABLE FOR CONSEQUENTIAL LOSS OR DAMAGES RESULTING FROM THE FAILURE OF THE SMOKE ALARM OR FOR BREAC...

Reviews: