4. Connect brown cable from connector plug of smoke alarm to live (red

or brown) mains power cable .

5. If interconnection is desired, connect orange or white cable from con-

nector to interconnect strand on the 3 core & earth cable. See section,
“Interconnecting Smoke Alarms.”

NOTE:

If this will be a single-station smoke alarm, cover orange or white
cable with electrical tape and tuck into pattress. 

Steps 6-9 for Models KF1 and KF2 ONLY:

6. Lift open battery pocket door. 
7.

Connect new 9-volt battery to battery connector inside battery pocket. BE
SURE BATTERY IS SECURELY CONNECTED. Smoke alarm may beep
briefly when battery is installed.

8. Close battery pocket door, snapping it into place. 
9. Push button and hold button on front cover of smoke alarm for three

(3) seconds. Smoke alarm should sound its alarm horn if battery is fit-
ted correctly.

10. Attach connector plug to pins on back of smoke alarm. Plug will only

fit one way and will snap into place. 

11. Gently tug connector to be sure it is attached securely. 
12. Position smoke alarm to mounting plate so that keyslot on side of

smoke alarm is to left of tab on mounting plate. Turn clockwise to lock
into 

place. 

NOTE: (For Models KF1 and KF2 only):

Smoke alarm will not mount to plate if battery is not installed.

13. Turn on power at main fuse box or circuit breaker. The green LED on the

cover should be illuminated.

14. Test smoke alarm. See “TESTING THE SMOKE ALARM”.

INTERCONNECTING

SMOKE ALARMS

Use 1.5mm

2

minimum solid or stranded cable with a rating of 230V.

When interconnecting, maximum cable length between any two is 450
m for 1.5mm

2

or 1200 m for 2.5mm

2

(20 OHMS loop resistance).

NOTE: Maximum length under BS7671 17th Edition wiring regs
amendment 1 for CB/RCBO type B is 72 metres for TN-S or TN-C-S
systems (source "On-Site Guide" page 59) 

This smoke alarm may be interconnected with as many as 23other
Models KF1, KF1R, KF2 and KF2R smoke alarms. DO NOT connect to
any other type or model smoke alarm.

Connect smoke alarms to a single circuit. Wiring must conform to IEE
Regulations for electrical installation.

RED AND GREEN LED

INDICATORS

This smoke alarm features red and green LED indicators that can be seen
through the Push-to-Test button or the LED lens above the test button. 
The LEDs indicate the following:

GREEN LED
ON

— 

AC power is present

.

OFF

— 

AC power is not present. 

RED LED

Blinks once a minute

— indicating normal operation.

Blinks once a second

— smoke alarm senses smoke and simulta-

neously sounds an audible alarm.

Blinks once every 10 seconds — smoke alarm is quieting an unwanted

alarm. (Models KF1, KF1R, KF2 and
KF2R)

(Interconnected system only):

4

BLUE

ORANGE OR WHITE

BROWN

LI

NE

IN

T

ER

LI

NK

NEUTRAL

CEILING

DRY LINING  BOX

DRY LINING  BOX

OR PATTRESS

BLUE

BLU

E

ORANGE OR WHITE

BROWN

LINE

NEUTRA

L

INTERLI

NK

CEILING

OR PATTRESS

MODELS KF1, KF2

MODELS KF1R, KF2R(Rechargeable)

BLACK OR BLUE

ORANGE OR WHITE

ORANGE OR WHITE

RED OR BROWN

FOR INTERCONNECT: USE STANDARD 3 core & earth cable 1.5mm2 cable

NEUTRAL

LINE

1227-7201-00_EN_V4:_  2012.3.29  9:46 AM  Page 4

Summary of Contents for KF1

Page 1: ...READ AND SAVE THESE INSTRUCTIONS W A R N I N G DO NOT paint or cover the smoke alarm with tape This smoke alarm should be out of the reach of children AC smoke alarms require constant 230V AC 50Hz po...

Page 2: ...can only sound their alarms when they detect smoke Smoke alarms detect combustion particles in the air They do not sense heat flame or gas This smoke alarm is designed to give audible warning of a dev...

Page 3: ...ent Building Regulations and or BS5839 Pt6 current I E E Regulations CAUTION Alarm should not be exposed to dripping or splashing HOW TO INSTALL THIS SMOKE ALARM DANGER ELECTRICAL SHOCK HAZARD Turn of...

Page 4: ...ARM INTERCONNECTING SMOKE ALARMS Use 1 5mm2 minimum solid or stranded cable with a rating of 230V When interconnecting maximum cable length between any two is 450 m for 1 5mm2 or 1200 m for 2 5mm2 20...

Page 5: ...Test button NOTE If smoke alarms are interconnected all smoke alarms should sound an alarm within three seconds after any test button is pushed and the tested smoke alarm sounds 3 If smoke alarm does...

Page 6: ...o not attempt to remove the cover or clean inside the smoke alarm THIS WILL VOID YOUR GUARANTEE REPAIR CAUTION Do not attempt to repair this smoke alarm Doing so will void your guarantee If smoke alar...

Page 7: ...onnector 3 Clean smoke alarm Smoke alarm beeps about 1 Turn off power and once a minute replace battery See KF1 and KF2 only in the MAINTENANCE AND CLEANING section 2 Clean smoke alarm KF1R and KF2R o...

Page 8: ...ASE SHALL KIDDE BE LIABLE FOR ANY INCIDENTAL OR CONSEQUENTIAL DAMAGES FOR BREACH OF THIS OR ANY OTHER WARRANTY EXPRESS OR IMPLIED WHATSOEVER EVEN IF THE LOSS OR DAMAGE IS CAUSED BY ITS NEGLIGENCE OR F...

Reviews: